Bryant F, 580J*08--14D appendix Troubleshooting Alarms

Page 46

580J

Table 18 – Troubleshooting Alarms

 

BACnet

ACTION TAKEN BY

RESET

 

POINT NAME

OBJECT

PROBABLE CAUSE

CONTROL

METHOD

 

NAME

 

 

 

 

 

 

 

 

 

 

 

 

Alarm Generated

 

 

Safety Chain Alarm

safety_chain

Immediate

Automatic

Over load Indoor Fan or Electric Heater overheat.

 

 

Shutdown

 

 

 

 

Alarm Generated

 

Smoke detected by smoke detector or

Fire Shutdown Alarm

fire_alarm

Immediate

Automatic

configuration incorrect

 

 

Shutdown

 

 

 

 

 

 

 

 

 

 

Space Temp Sensor

 

Alarm Generated

 

Faulty, shorted, or open thermistor caused by

spt_alarm

Immediate

Automatic

Failure

wiring error or loose connection.

 

Shutdown

 

 

 

 

 

 

 

 

 

 

 

 

Alarm Generated

 

Faulty, shorted, or open thermistor caused by

SAT Sensor Alarm

sat_alarm

Immediate

Automatic

wiring error or loose connection.

 

 

Shutdown

 

 

 

 

 

 

 

 

 

 

High Space Temp Alarm

spt_hi

Alarm Generated

Automatic

The space temperature has risen above the cool

setpoint by more than the desired amount.

 

 

 

 

Low Space Temp Alarm

spt_lo

Alarm Generated

Automatic

The space temperature has dropped below the

heat setpoint by more than the desired amount.

 

 

 

 

High Supply Air Temp

sat_hi

Alarm Generated

Automatic

SAT is greater then 160 degrees for more than 5

minutes.

 

 

 

 

Low Supply Air Temp

sat_lo

Alarm Generated

Automatic

The supply air temperature is below 35_F for

more than 5 minutes.

 

 

 

 

Supply Fan Failed to

 

Alarm Generated

 

Tripped Circuit Breaker, Broken belt, Bad indoor

sf_fail

Immediately

Automatic

fan motor, Configuration incorrect, Bad fan status

Start

 

disable Operation

 

switch.

 

 

 

 

 

 

 

 

 

 

Alarm Generated

 

 

Supply Fan in Hand

sf_hand

Ramp down

Automatic

Bad Fan Status Switch, Configuration incorrect.

 

 

Operations

 

 

Compressor Safety

dx_compstat

Alarm Generated

Automatic

Compressor would not start.

Alarm

 

 

 

 

Setpoint Slider Alarm

slide_alarm

Alarm Generated

Automatic

STO sensor is open or shorted for more then 5

Offset set to zero

seconds.

 

 

 

 

 

 

Automatic/re

 

 

 

 

set timer

 

 

 

 

when

Dirty Filter, supply fan run time exceeded, filter

Dirty Filter Alarm

filter

Alarm Generated

configured

switch configuration wrong.

 

 

 

with or

 

 

 

 

 

 

 

without

 

 

 

 

switch

 

Switch Configuration

 

Alarm Generated

Configure

More than one binary input is configured for the

 

Disable

sw_cfg_alarm

same purpose. More then one discrete input is

Alarm

misconfigured switch

correctly

 

configured to provide the same function.

 

 

functions

 

 

 

 

 

Misconfigured Analog

 

Alarm Generated

Configure

More then one analog input is configured to

an_cfg_alarm

Disable 4 selectable

Input

correctly

provide the same function.

 

analog inputs

 

 

 

 

 

 

 

 

 

 

 

Alarm Generated

 

Faulty, shorted, or open thermistor caused by

OAT Sensor Alarm

oat_alarm

Economizer and Low

Automatic

ambient DX cooling

wiring error or loose connection.

 

 

 

 

 

lockout disabled.

 

 

 

 

Alarm Generated

 

Sensor reading is out of range. Bad sensor, bad

Space RH Sensor Alarm

sprh_alarm

Dehumidification

Automatic

wiring, or sensor configured incorrectly.

 

 

disabled

 

 

 

 

 

 

 

 

 

 

Outdoor RH Sensor

oarh_alarm

Alarm Generated

Automatic

Sensor reading is out of range. Bad sensor, bad

Alarm

wiring, or sensor configured incorrectly.

 

 

 

High Space Humidity

sprh_hi

Alarm Generated

Automatic

IRH is greater then 70% for more then 10

minutes.

 

 

 

 

Low Space Humidity

sprh_lo

Alarm Generated

Automatic

IRH is less then 35% for more then 10 minutes.

 

 

Alarm Generated

 

 

 

 

Disables IAQ

 

Sensor reading is out of range. Bad sensor, bad

IAQ Sensor Alarm

iaq_alarm

Operation

Automatic

wiring, or sensor configured incorrectly.

 

 

Economizer moves

 

 

 

 

 

 

 

to minimum position

 

 

OAQ Sensor Alarm

oaq_alarm

Alarm Generated Set

Automatic

Sensor reading is out of range. Bad sensor, bad

OAQ to 400

wiring, or sensor configured incorrectly.

 

 

 

High Carbon Dioxide

co2_hi

Alarm Generated

Automatic

CO2 reading is above 1200ppm.

Level

 

 

 

 

Supply Fan Runtime

sf_rntm

Alarm Generated

clear the

Supply fan run time exceeded user defined limit.

Alarm

timer

 

 

 

Compressor 1 Runtime

dx1_rntm

Alarm Generated

clear the

Compressor run time limit is exceeded.

Alarm

timer

 

 

 

Compressor 2 Runtime

dx2_rntm

Alarm Generated

clear the

Compressor run time limit is exceeded.

Alarm

timer

 

 

 

46

Image 46
Contents Table of Contents Safety ConsiderationsGeneral Unit Arrangement and AccessWhat to do if you smell gas Routine Maintenance Seasonal MaintenanceSupply Fan Belt-Drive Supply FAN Blower SectionManual Outside Air Hood Screen Adjustable-Pitch Pulley on Motor Supply-Fan Pulley Adjustment BearingsCondenser Coil Coil Maintenance and Cleaning RecommendationCooling Evaporator CoilRoutine Cleaning of Novation Condenser Coil Surfaces Routine Cleaning of Evaporator Coil SurfacesEvaporator Coil Metering Devices Refrigerant System Pressure Access PortsPuronr R-410A Refrigerant Refrigerant ChargeSeatcore Cooling Charging Charts Cooling Charging Charts 08D,F Both CircuitsCooling Charging Charts 12D,F Both Circuits TON Circuit TON Circuit Cooling Service Analysis Problem Cause RemedyTroubleshooting Cooling System Condenser-Fan Adjustment 08D-12D,F sizeCondenser-Fan Adjustment 14D,F size CompressorsUnit-Powered Type Installing Weatherproof CoverNon-Powered Type Convenience OutletsSmoke Detectors Smoke Detector Locations SensorSupply Air Return Air Without Economizer Completing Installation of Return Air Smoke SensorFiop Smoke Detector Wiring and Response All UnitsSensor and Controller Tests Dirty Controller Test Procedure Controller Alarm TestController Alarm Test Procedure Dirty Sensor Test ProcedureRemote Test/Reset Station Dirty Sensor Test Detector CleaningSD-TRK4 Remote Alarm Test Procedure Dirty Sensor Test Using an SD-TRK4Troubleshooting Protective Devices Compressor ProtectionControl Circuit GAS Heating SystemFuel Types and Pressures Combustion-Air Blower Supply Pressure SwitchFlue Gas Passageways Liquid Propane Supply Line Pressure RangesMain Burners Burners and IgnitersOrifice Projection Check Unit Operation and Make Necessary Adjustments Cleaning and AdjustmentLimit Switch LED Indication Error Code Description LED Error Code DescriptionBurner Ignition Orifice Replacement Gas ValveRed LED-Status Altitude Compensation Orifice SizesLP Orifice Minimum Heating Entering Air Temperature Troubleshooting Heating SystemHeating Service Analysis IGC Board LED Alarm Codes IGCRTU-MP Control System Condenser Coil ServiceRepairing Novation Condenser Tube Leaks Replacing Novation Condenser CoilRTU-MP Multi-Protocol Control Board Typical RTU-MP System Control Wiring Diagram RTU-MP Controller Inputs and Outputs Supply Air Temperature SAT SensorOutdoor Air Temperature OAT Sensor OutputsEconoMi$er Space Temperature SPT SensorsConnect T-55 Economizer Controls Outdoor Air Enthalpy Control PNO HH57AC077Return Air Enthalpy Sensor Wiring the Indoor Air Quality SensorDifferential Enthalpy Control Indoor Air Quality CO2 SensorWeatherproof Enclosure Connecting Discrete InputsOutdoor Air Quality Sensor PNO 33ZCSENCO2 plus Filter StatusPower Exhaust output Communication Wiring ProtocolsProtocol DS8 DS7 DS6 DS5 DS4 DS3 DS2 DS1 RTU-MP TroubleshootingCommunication LEDs Baud Rate DS2 DS1LEDs LEDs on the RTU-MP show the status of certain functionsTroubleshooting Alarms Alarms BACnet MS/TPModule Status Report Modstat Example Manufacture Date Basic Protocol TroubleshootingModbus Code Name MeaningECONOMI$ER Systems EconoMi$er IV Component LocationsEconoMi$er IV Wiring EconoMi$er IV Input/Output Logic EconoMi$er IV Functional ViewEconoMi$er IV Control Modes Supply Air Temperature SAT SensorOutdoor Air Lockout Sensor Outdoor Dry Bulb ChangeoverDifferential Dry Bulb Control Outdoor Enthalpy ChangeoverIndoor Air Quality IAQ Sensor Input Exhaust Setpoint AdjustmentMinimum Position Control Thermostats Damper MovementDemand Control Ventilation DCV CO2 Sensor Standard Settings CO2 Sensor ConfigurationAnalog CO2 EconoMi$er IV Preparation DCV Demand Controlled Ventilation and Power ExhaustEconoMi$er IV Sensor Usage Differential EnthalpyDCV Minimum and Maximum Position Wiring DiagramsEconoMi$er IV Troubleshooting Completion Supply-Air Sensor Input580J Typical Unit Wiring Diagram Power 08D,F, 208/230-3-60 C09157 Unit Preparation PRE-START-UPSTART-UP, General Gas PipingReturn-Air Filters Internal WiringRefrigerant Service Ports Outdoor-Air Inlet ScreensUnit Start Delay Field Service TestConfiguration START-UP, RTU-MP ControlCompressor1 Service Hours Filter Service HoursSupply Fan Service Hours Compressor2 Service HoursInput 1 Function InputSpace Sensor Type Input 2 FunctionHeating, Units Without Economizer Operating SequencesBase Unit Controls Cooling, Units Without Economizer Cooling, Unit With EconoMi$erSupplemental Controls Heating With EconoMi$erDemand Controlled Ventilation RTU-MP Sequence of OperationLocal Schedule Always Occupied Default OccupancyScheduling BACnet ScheduleCooling Power ExhaustEconomizer Demand Limit Fastener Torque ValuesIndoor Air Quality Torque ValuesSerial Number Format Appendix I. Model Number SignificanceModel Number Nomenclature Position NumberPhysical Data Appendix II. Physical Data12.5TONS 580J**08 580J**12 580J**14 Gas Connection Heat Anticipator Setting AmpsPhysical Data Heating 12.5TONS Natural Gas Heat, Liquid Propane Heat580J**08 Appendix III. FAN PerformanceCFM RPM BHP 580J**12 579580J**14 RPM BHPGeneral fan performance notes 1260Pulley Adjustment Unit MOTOR/DRIVE Motor Pulley Turns Open ComboElectrical Information Type DISC. Size Unit Combustion PowerNOM IFM FAN Motor Exhaust No P.E MocpAppendix IV. Wiring Diagram List Wiring DiagramsAppendix V. Motormaster Sensor Locations Catalog No.SM580J---02580J Unit START-UP Checklist Preliminary Information

580J*08--14D, F specifications

The Bryant F,580J*08--14D is an advanced heating and cooling system engineered for optimal performance and energy efficiency in residential and commercial applications. This innovative unit is designed to provide exceptional climate control while reducing operational costs, making it an ideal choice for those seeking reliable HVAC solutions.

One of the standout features of the Bryant F,580J*08--14D is its versatile heating and cooling capabilities. This system employs a two-stage compressor, which allows for precise temperature regulation and improved energy efficiency. This dual-stage operation ensures that the system can adapt to varying environmental conditions, providing enhanced comfort without excessive energy use.

The system is equipped with advanced inverter technology, which enables smoother operation and quieter performance. This technology adjusts the compressor speed based on the heating or cooling demand, leading to increased efficiency and reduced energy consumption. Additionally, the inverter system contributes to less noise during operation, creating a serene indoor environment.

The Bryant F,580J*08--14D also features a user-friendly thermostat that allows for easy temperature adjustments and scheduling. This smart thermostat is compatible with mobile devices, enabling users to monitor and control their HVAC system remotely. This feature provides added convenience and ensures that the system is operating efficiently, even when homeowners are away.

Energy efficiency is a hallmark of the Bryant F,580J*08--14D. The system meets and often exceeds ENERGY STARĀ® standards, making it one of the more eco-friendly options available in the market today. By utilizing energy-saving technologies and innovative designs, the system helps to lower utility bills and reduce the environmental impact.

Durability and reliability are key characteristics of the Bryant F,580J*08--14D. Constructed with high-quality materials and components, this unit is designed to withstand the rigors of changing weather conditions while maintaining consistent performance. Additionally, it comes equipped with a robust warranty, providing peace of mind for users investing in this heating and cooling solution.

In summary, the Bryant F,580J*08--14D is a top-tier HVAC system that boasts advanced technologies, exceptional energy efficiency, and user-friendly features. Its combination of reliable performance and modern conveniences makes it a standout choice for anyone looking to enhance their home's or business's climate control system, providing comfort and savings for years to come.