Heat & Glo LifeStyle SLR (COSMO) owner manual Remove any contaminants that may have accumulated on

Page 59

Intellifire Ignition System - (continued)

Symptom

Possible Cause

Corrective Action

 

 

 

 

a. A shorted or loose connection in flame

Verify all connections to wiring diagram in manual. Verify

4. Pilot lights but contin-

sensing rod.

connections underneath pilot assembly are tight. Verify

ues to spark, and main

 

connections are not grounding out to metal chassis, pilot

burner will not ignite.

 

burner, pilot enclosure or screen if present, or any other

(If the pilot continues

 

metal object.

to spark after the

 

 

b. Poor flame rectification or contaminated

With fixed glass assembly in place, verify that flame is en-

pilot flame has been lit,

flame sensing rod.

gulfing flame sensing rod on left side of pilot hood. Flame

flame rectification has

 

sensing rod should glow shortly after ignition. Verify cor-

not occurred.)

 

 

rect pilot orifice is installed and gas inlet is set to pressure

 

 

 

 

specifications. Clean flame sensing rod with emery cloth to

 

 

remove any contaminants that may have accumulated on

 

 

flame sensing rod.

 

 

 

 

c. Module is not grounded.

Verify module is securely grounded to metal chassis of

 

 

appliance. Verify that wire harness is firmly connected to

 

 

the module.

 

 

 

 

d. Damaged pilot assembly or contami-

Verify that ceramic insulator around the flame sensing

 

nated flame sensing rod.

rod is not cracked, damaged, or loose. Verify connection

 

 

from flame sensing rod to white sensor wire. Clean flame

 

 

sensing rod with emery cloth to remove any contaminants

 

 

that may have accumulated on flame sensing rod. Verify

 

 

continuity with a multimeter with ohms set at lowest range.

 

 

Replace pilot if any damage is detected.

 

 

 

 

e. Module.

Turn ON/OFF rocker switch or wall switch to OFF position.

 

 

Remove ignitor wire “I” from module. Place ON/OFF rocker

 

 

switch or wall switch in ON position. If there is no spark at

 

 

“I” terminal module must be replaced. If there is a spark at

 

 

“I” terminal, module is fine.

 

 

 

Heat & Glo • SLR • 2143-900 Rev. B • 7/08

59

Image 59
Contents What to do if you smell gas Model SLR CosmoHomeowner Reference Information CongratulationsUser Guide Table of ContentsReference Materials Appliance SetupTroubleshooting FinishingLimited Lifetime Warranty Heat & GLO GAS Appliance Products Limited Lifetime WarrantyListing and Code Approvals Requirements for the Commonwealth of Massachusetts Installation of Carbon Monoxide DetectorsYour Fireplace Gas Fireplace SafetyOperating Instructions User Guide Decorative Doors and Fronts Fixed Glass AssemblyRemote Controls, Wall Controls and Wall Switches Clear SpaceFinal inspection by Lighting Instructions IPIAfter Fireplace is Lit Frequently Asked QuestionsInitial Break-in Procedure Remote Control Maintenance and ServiceMaintenance Tasks-Homeowner Glass CleaningFirebox Maintenance Tasks-Qualified Service TechnicianGasket Seal and Glass Assembly Inspection VentingTypical Appliance System Getting StartedInspect Appliance and Components Design and Installation ConsiderationsTools and Supplies Needed Selecting Appliance Location Framing and ClearancesClearances Constructing the Appliance ChaseFront Side Finishing Detail Mantel and Wall ProjectionsCombustible Mantels Non-combustible MantelsAIR Space Vent Termination Minimum Clearances Termination LocationsCovered Alcove Applications Vent Information and Diagrams Minimum Maximum Top Vent Horizontal Termination Venting with 1 elbowTop Vent Horizontal Termination Venting with 2 elbows Venting with 3 elbows Top Vent Horizontal TerminationTop Vent Horizontal Termination Venting with 3 elbows Exhaust restrictor Instructions Top Vent Vertical Termination No Elbows V1 = 44 ft. Max .4 mV1 Minimum Maximum V1 + V2 Minimum Top Vent Vertical Termination Venting with 2 elbowsTop Vent Vertical Termination Venting with 3 elbows V1 MIN H1 MAX V2 MIN H2 MAX V3 MIN Top Vent Vertical Termination Venting with 4 elbowsCombustible Wall Penetration Vent Clearances and FramingPipe Clearances to Combustibles Wall Penetration FramingPipe SLP Install the Ceiling FirestopVaulted Ceiling Installation Install Attic Insulation ShieldFlat Ceiling Installation Top Vent Appliance PreparationProper Positioning, Leveling And Securing Of An Securing and Leveling the ApplianceAssemble Vent Sections Installing Vent Pipe SLP PipeSecure The Vent Sections Assemble Slip SectionsDisassemble Vent Sections Install Decorative Ceiling ComponentsAssemble and Install Storm Collar Install Metal Roof Flashing15 Secure Pipe with SLP-FS Install RF4-8Heat Shield Requirements for Horizontal Termination Install Vertical Termination CapInstall Decorative Wall Components 22 Venting through the wall Install Horizontal Termination CapGas Pressure Gas InformationFuel Conversion Gas Connection Gas Fitting AccessElectrical Information Wiring RequirementsIntellifire Ignition System Wiring Optional Accessories RequirementsJunction Box Detail Electrical Service and Repair Junction Box InstallationFraming and Finishing Instructions FinishingFinishing Details Confirm Fireplace Opening Dimension Opening 12 Overlap Fit Method Tonic or Martini Decorative Front Facing Material14 Inside Fit Method Tonic Decorative Front Only 17 Tonic Decorative Front Decorative FrontsAccessories Appliance SetupRemove Fixed Glass Assembly Clean the ApplianceRock Media Instructions Cleaning the RockScrew Air Shutter Settings Install the MeshAir Shutter Setting Intellifire Ignition System TroubleshootingSymptom Possible Cause Corrective Action Remove any contaminants that may have accumulated on Reference Materials Appliance Dimension DiagramDVP-BEK2 Vent Components DiagramsRF4-8 SLP-45 45 ElbowSLP90- 90 Elbow Extended Heat ShieldAdapter PVK-80Support Box-Black Horizontal Ceiling FirestopPart number list on following Service PartsAt Depot Service Parts ListStocked IPI Valve Assembly Contact Information