Regency P33-NG3 Pilot Adjustment, GAS Pipe Pressure Testing, High Elevation, T. Valve Description

Page 25

INSTALLATION

PILOT ADJUSTMENT

Periodically check the pilot flames. Correct flame pattern has three strong blue flames: 1 flowing around the thermopile, 1 around the thermocouple and 1 flowing across the burner (it does not have to be touching the burner).

Note: If you have an incorrect flame pat- tern, contact your Regency dealer for further instructions.

P33-NG3 System Data

Conversion Kit# 431-969

For 0 to 2000 feet altitude

 

Burner Inlet Orifice Sizes:

#44

Max. Input Rating

22,500 Btu/h

Min. Input Rating

12,500 Btu/h

 

 

For 2000 to 4500 feet altitude

 

Burner Inlet Orifice Sizes:

#45

Max. Input Rating

21,000 Btu/h

Min. Input Rating

10,500 Btu/h

 

 

Supply Pressure

min.5.0" w.c.

 

 

 

Manifold Pressure

 

 

(High)

3.8"+/- 0.2" w.c.

GAS PIPE PRESSURE

TESTING

The appliance must be isolated from the gas supply piping system by closing its individual manual shut-off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig. (3.45 kPa). Disconnect piping from valve at pressures over 1/2 psig.

The manifold pressure is controlled by a regu- lator built into the gas control, and should be checked at the pressure test point.

Note: To properly check gas pressure, both inletandmanifoldpressuresshould becheckedusingthevalvepressure ports on the valve.

Incorrect flame pattern will have small, prob- ably yellow flames, not coming into proper contact with the rear burner or thermopile or thermocouple.

P33-LG3 System Data

For 0 to 4500 feet altitude

Burner Inlet Orifice Sizes: #54

Max. Input Rating

21,500 Btu/h

Min. Input Rating

10,500 Btu/h

 

 

Supply Pressure

min.12.0" w.c.

 

 

Manifold Pressure

 

(High)

11"+/- 0.2"w.c.

1)Make sure the valve is in the "OFF" posi- tion.

2)Loosen the "IN" and/or "OUT" pressure tap(s), turning counterclockwise with a 1/8" wide fl at screwdriver.

3)Attach manometer to "IN" and/or "OUT" pressure tap(s) using a 5/16" ID hose.

4)Light the pilot and turn the valve to "ON" position.

5)The pressure check should be carried out with the unit burning and the setting should be within the limits specifi ed on the safety label.

6)When fi nished reading manometer, turn off the gas valve, disconnect the hose and tighten the screw (clockwise) with a 1/8" fl at screwdriver. Note: Screw should be snug, but do not over tighten.

HIGH ELEVATION

This unit is approved in Canada for altitude to 4500 ft. (CAN/CGA-2.17-M91). For Natural Gas installations above 4500 ft. follow current CAN/CGA-B149.1.

S.I.T. VALVE DESCRIPTION

1) Gas cock knob

2)Manual high/low adjustment

3)Pilot Adjustment

4) Thermocouple Connection - option

5) Outlet Pressure Tap

6) Inlet Pressure Tap

7)Pilot Outlet

8)Main Gas Outlet

9)Alternative TC Connection Point

Regency P33-3 Zero Clearance Direct Vent Gas Fireplace

Image 25
Contents P33-3 Zero Clearance To the New Owner Information for MOBILE/MANUFACTURED Homes After First SaleTable of Contents Safety Label General Safety Information InstallationSave These Instructions Before YOU StartUnit Dimensions Installation ChecklistLocating Your GAS Stove Duct System OptionMantel LEG Clearances Clearancescombustible MantelsClearances are not adhered to Fire hazard is an extreme risk if theseRear Termination Framing and FinishingSimpson Dura-Vent Minimum Clearances Vertical Termination or Vertical Rise with HorizontalTop Standoff Assembly Unit Assembly Prior to InstallationVenting Introduction Top Facing Support Side Nailing StripsVent terminal Air supply outlet VentRegency Direct Vent System Flex Horizontal Terminations only For Regency Direct Vent System Flex Installation ProceduresRigid Pipe Venting Systems Flat Wall InstallationMax. Wall Vent Length Thickness inches Required inchesDescription Simpson Dura-Vent Selkirk Rigid Pipe Venting Components ListDirect VentGS R Direct-Temp TM Propane & Natural Gas Rigid Pipe Venting Arrangements Vertical TerminationsInstallation Regency Direct Vent System Flex Rigid Pipe Venting Arrangements Horizontal TerminationsHorizontal Venting with Three 3 90o Elbows Horizontal Venting with Two 2 90o ElbowsOption + H1 Option + V1 H + H1 Vertical Venting with Two 2 90o ElbowsOption + V1 With these options, max. totalVertical Venting with Three 3 90o Elbows Required Parts Vertical Termination With CO-LINEAR Flex SystemDescription Alternate Approved CapsInstallation Below Grade Snorkel Installation Horizontal InstallationsSnorkel Terminations Vertical Termination GAS Line InstallationGAS Pipe Pressure Testing Pilot AdjustmentHigh Elevation T. Valve DescriptionConversion Kit Contains Optional Brick Panels LOG SET InstallationNotch BracketBracketOptional Flush Trim Standard Flush DoorCutout 5th Grate TabDouble Screen Door Flush LouversOptional BAY Door Bay louvers Must be used With the Bay glass optionFlush Louver Top Heat Shield BAY LouversBay Louver Top Heat Shield Burner ON/OFF Control boxCut-Out Oblong Hole Top Flange Bottom Full Screen FrontCut-Outs Top Grill Hinge Location Bottom GrillThermostat Wire Table Optional Wall SwitchDo not cut the ground terminal off under any circumstances Wiring DiagramShut the power off Installing the Optional FANDiagram Secure left side with 2 screws Secure the 2 boxes together With one screwCopy of the Lighting Plate Instructions Operating InstructionsShutdown Procedure Lighting ProcedureAeration Adjustment Operating InstructionsMaintenance Instructions MaintenanceLOG Replacement Normal Operating Sounds GAS AppliancesThermopile Thermocouple Flush Glass ReplacementGlass Gasket Door GlassDiagram 3 Lift out Valve Tray Assembly Installing ValveRemoving Valve Shut off the gas supplyDescription Parts ListParts List Part Description Burner & Log AssemblyFlush Front & Louvers Bay Front & Louvers Regency P33-3 Zero Clearance Direct Vent Gas Fireplace Conditions WarrantyInstaller Please complete the following information