Regency G36D installation manual Rigid Pipe Venting Systems, Alternate

Page 13

INSTALLATION

RIGID PIPE VENTING SYSTEMS

Horizontal or Vertical Terminations

The minimum components required for a basic horizontal termination

 

Flat Wall Installation

are:

 

Wall Thickness

Vent Length Required

 

 

1

Horizontal Termination Cap

(inches)

(inches)

4" -

5-1/2"

6"

1

90o Elbow

1

Rigid Pipe Adaptor

7" -

8-1/2"

9"

 

 

1Wall Thimble

1 Length of pipe to suit wall thickness (see chart)

 

10" - 1-1/2"

12"

Wall thickness is measured from the back standoffs to the inside mounting

9" - 14-1/2"

11" - 14-5/8" Adj. Pipe

15" - 23-1/2"

17" - 24" Adj.

surface of termination cap. For siding other than vinyl furring strips may

be used, instead of the vinyl siding standoff, to create a level surface to

Corner Installation

mount the vent terminal. The Terminal must not be recessed into siding.

Wall Thickness

Vent Length Required

Measure the wall thickness including furring strips.

 

 

(inches)

(inches)

 

 

If a Vinyl Siding Standoff is required (it must be used with vinyl siding),

3-1/4" - 6-3/4"

11" - 14-5/8" Adj. Pipe

measure to outside surface of wall without siding and add 2 inches.

7-3/4" - 16-1/4"

17" - 24" Adj. Pipe

 

 

Vertical

 

7-1/4" - 8-3/4"

6" + 12"

 

 

9" + 9"

Terminal

 

4-1/4" - 5-3/4"

6" + 9"

 

 

Storm Collar

 

 

 

(Part # 953)

Vinyl Siding

 

 

 

Standoff (Optional)

 

Alternate

Flashing

(Part #950)

 

Horizontal Ter-

943 or 943S

 

 

mination Caps

Ceiling Firestop

 

Horizontal

 

(Part # 963)

 

Termination Cap

 

(Part# 946-523/P)

 

Wall Thimble

 

(Part # 942)

Pipe Length

Adj.Pipe Length

 

 

11" - 14-5/8"

 

90o Elbow

24" Pipe Length

WARNING:

Do not combine venting components from different venting systems.

However use of the the AstroCapTM and FPI Riser is acceptable with all systems.

Rigid Pipe Adaptor

(Part# 510-994)

When using Rigid Vent piping other than Simpson Dura-Vent, 3 screws must be used to secure rigid pipe to adaptor.

This product has been evaluated by Intertek for using a Rigid Pipe Adaptor in conjunction with Dura-Vent Direct Vent GS, Selkirk Direct- Temp, Ameri Vent Direct venting and Security Secure Vent systems. Use of these systems with the Rigid Pipe adaptor is deemed acceptable and does not affect the Intertek WHI listing of components.

The FPI AstroCapTM and FPI Riser Vent terminal are certifi ed for installations using FPI venting systems as well as Simpson Dura-Vent® Direct Vent GS, American Metal Products Ameri Vent Direct Vent and Selkirk Direct-Temp. AstroCapTM is the proprietary trademark of FPI Fireplace Products International Ltd. Dura-Vent® and Direct Vent GS are registered and/or proprietary trademarks of Simpson Dura-Vent Co. Inc.

UltraGlow® G36D Zero Clearance Direct Vent Gas Fireplace

13

Image 13
Contents 12/18/05 G36D Zero Clearance Direct Vent Gas FireplaceTo the New Owner Information for MOBILE/MANUFACTURED Homes After First SaleTable of Contents Copy of Safety Decal for G36D-NG1 Safety Label300 Certified for/Certifiée pour Canada and U.S.AInstallation Checklist InstallationImportant Message Save These Instructions Before YOU StartDiagram G36D Unit DimensionsLocating Your GAS Stove Manufactured Mobile Home Additional RequirementsMantel LEG Clearances ClearancesFraming Finishing Combustible Mantels Top Standoff Assembly Unit Assembly Prior to InstallationVenting Introduction Top Facing Support Side Nailing StripsExterior Vent Area where terminal is not permitedLocations Vertical TerminationVenting Secure Vent Rigid Pipe Venting Components ListAlternate Rigid Pipe Venting SystemsUltraGlow Direct Vent System Flex Rigid Pipe Venting Arrangements Horizontal TerminationsInstallation Rigid Pipe Venting Arrangements Vertical Terminations Installation Required Parts Vertical Termination With CO-LINEAR Flex SystemDescription Flex LinerVenting Arrangements Vertical Terminations I g h t Achieved Diagram 3aSnorkel Terminations Diagram Roof Pitch Firestop spacer must be installedCeiling to the position Continue to assemble pipe lengthsOffset Chart Installation ProceduresFor UltraGlow Direct Vent System Flex GAS Line Installation Pilot AdjustmentGAS Pipe Pressure Testing High ElevationLPG Conversion Kit Contains Installation of LPG Conversion KitQty DC Sparker Kit Contains QtySparker Ignitor Wire Ignitor WireGround Wire from Kit Piezo IgnitorHeat Shield Install the 1/2 bushing to the heat shieldChain 02-75 02-55 02-52 LOG SET Installation02-53 02-51 02-54 Log indentation 5th Grate TabRear Grate Tab Front BracketsPlace embers in these 3 locations On the burner tray Install fl ush glass as per instructions in manualFlush Louvers Standard Flush DoorOptional Flush Trim Wall Switch Remote ControlThermostat Wire Table Wall ThermostatDo not cut the ground terminal off under any circumstances Wiring DiagramTo Remove the Fan Installing the Optional FANOpen the bottom louver door Operating Instructions Copy of the Lighting Plate Instructions Maintenance InstructionsNormal Operating Sounds of GAS Appliances Maintenance Removing Valve Installing ValveG36D Main Assembly Pilot Assembly Gasket Parts ListG36D Flush Front Assembly UltraGlow G36D Zero Clearance Direct Vent Gas Fireplace UltraGlow G36D Zero Clearance Direct Vent Gas Fireplace Conditions WarrantyExclusions Register your UltraGlow online at