INSTALLATION
RIGID PIPE VENTING SYSTEMS
Horizontal or Vertical Terminations
The minimum components required for a basic horizontal termination |
| Flat Wall Installation | |||
are: |
| Wall Thickness | Vent Length Required | ||
|
| ||||
1 | Horizontal Termination Cap | (inches) | (inches) | ||
4" - | 6" | ||||
1 | 90o Elbow | ||||
1 | Rigid Pipe Adaptor | 7" - | 9" | ||
|
|
1Wall Thimble
1 Length of pipe to suit wall thickness (see chart) |
| 10" - | 12" | |
Wall thickness is measured from the back standoffs to the inside mounting | 9" - | 11" - | ||
15" - | 17" - 24" Adj. | |||
surface of termination cap. For siding other than vinyl furring strips may | ||||
be used, instead of the vinyl siding standoff, to create a level surface to | Corner Installation | |||
mount the vent terminal. The Terminal must not be recessed into siding. | Wall Thickness | Vent Length Required | ||
Measure the wall thickness including furring strips. |
| |||
| (inches) | (inches) | ||
|
| |||
If a Vinyl Siding Standoff is required (it must be used with vinyl siding), | 11" - | |||
measure to outside surface of wall without siding and add 2 inches. | 17" - 24" Adj. Pipe | |||
|
| |||
Vertical |
| 6" + 12" | ||
|
| 9" + 9" | ||
Terminal |
| 6" + 9" | ||
|
| |||
Storm Collar |
|
|
| |
(Part # 953) | Vinyl Siding |
|
| |
| Standoff (Optional) |
| Alternate | |
Flashing | (Part #950) |
| Horizontal Ter- | |
943 or 943S |
|
| mination Caps | |
Ceiling Firestop |
| Horizontal |
| |
(Part # 963) |
| Termination Cap |
|
(Part#
| Wall Thimble |
| (Part # 942) |
Pipe Length | Adj.Pipe Length |
| |
| 11" - |
| 90o Elbow |
24" Pipe Length
WARNING:
Do not combine venting components from different venting systems.
However use of the the AstroCapTM and FPI Riser is acceptable with all systems.
Rigid Pipe Adaptor
(Part# 510-994)
When using Rigid Vent piping other than Simpson
This product has been evaluated by Intertek for using a Rigid Pipe Adaptor in conjunction with
The FPI AstroCapTM and FPI Riser Vent terminal are certifi ed for installations using FPI venting systems as well as Simpson
UltraGlow® G36D Zero Clearance Direct Vent Gas Fireplace | 13 |