INSTALLATION

RIGID PIPE VENTING ARRANGEMENTS - HORIZONTAL TERMINATIONS

UltraGlow® DIRECT VENT SYSTEM (FLEX)

(Propane & Natural Gas)

The diagram shows all allowable combinations of vertical runs with horizontal terminations, using one 90o elbow (two 45o elbows equal one 90o elbow).

Note: Must use optional rigid pipe adaptor (Part # 510-994) when using rigid vent systems.

All Rigid Pipe Systems

4" inner diameter

6-5/8" outer diameter

UltraGlow® Flex Vent 4" inner diameter

6-7/8" inner diameter

A vent guard should be used whenever the termination is lower than the specifi ed minimum or as per local codes.

Note: UltraGlow® Direct Vent System (Flex) is only approved for horizontal terminations.

Maintain clearances to combustibles as listed in the "Clearances," "Mantel Leg Clearances," "Framing and Finishing," & "Combustible Mantels" sections.

Horizontal vent must be supported every 3 feet.

Firestops are required at each floor level and whenever passing through a wall.

14

UltraGlow® G36D Zero Clearance Direct Vent Gas Fireplace

Image 14
Contents G36D Zero Clearance Direct Vent Gas Fireplace 12/18/05Information for MOBILE/MANUFACTURED Homes After First Sale To the New OwnerTable of Contents 300 Safety LabelCopy of Safety Decal for G36D-NG1 Certified for/Certifiée pour Canada and U.S.AImportant Message Save These Instructions InstallationInstallation Checklist Before YOU StartLocating Your GAS Stove G36D Unit DimensionsDiagram Manufactured Mobile Home Additional RequirementsFraming Finishing ClearancesMantel LEG Clearances Combustible Mantels Venting Introduction Unit Assembly Prior to InstallationTop Standoff Assembly Top Facing Support Side Nailing StripsLocations Area where terminal is not permitedExterior Vent Vertical TerminationVenting Rigid Pipe Venting Components List Secure VentRigid Pipe Venting Systems AlternateRigid Pipe Venting Arrangements Horizontal Terminations UltraGlow Direct Vent System FlexInstallation Rigid Pipe Venting Arrangements Vertical Terminations Installation Description Vertical Termination With CO-LINEAR Flex SystemRequired Parts Flex LinerVenting Arrangements Vertical Terminations Snorkel Terminations Diagram 3aI g h t Achieved Ceiling to the position Firestop spacer must be installedDiagram Roof Pitch Continue to assemble pipe lengthsFor UltraGlow Direct Vent System Flex Installation ProceduresOffset Chart GAS Pipe Pressure Testing Pilot AdjustmentGAS Line Installation High ElevationQty Installation of LPG Conversion KitLPG Conversion Kit Contains DC Sparker Kit Contains QtyGround Wire from Kit Ignitor WireSparker Ignitor Wire Piezo IgnitorChain Install the 1/2 bushing to the heat shieldHeat Shield 02-53 02-51 02-54 LOG SET Installation02-75 02-55 02-52 Rear Grate Tab 5th Grate TabLog indentation Front BracketsInstall fl ush glass as per instructions in manual Place embers in these 3 locations On the burner trayOptional Flush Trim Standard Flush DoorFlush Louvers Thermostat Wire Table Remote ControlWall Switch Wall ThermostatWiring Diagram Do not cut the ground terminal off under any circumstancesOpen the bottom louver door Installing the Optional FANTo Remove the Fan Operating Instructions Normal Operating Sounds of GAS Appliances Maintenance InstructionsCopy of the Lighting Plate Instructions Maintenance Installing Valve Removing ValveG36D Main Assembly Parts List Pilot Assembly GasketG36D Flush Front Assembly UltraGlow G36D Zero Clearance Direct Vent Gas Fireplace UltraGlow G36D Zero Clearance Direct Vent Gas Fireplace Exclusions WarrantyConditions Register your UltraGlow online at