Regency G36D installation manual Operating Instructions

Page 34

OPERATING INSTRUCTIONS

OPERATING

INSTRUCTIONS

1)Read and understand these instructions before operating this appliance.

2)Check to see that all wiring is correct and enclosed to prevent possible shock.

3)Check to ensure there are no gas leaks.

4)Make sure the glass in the door frame is properly positioned. Never operate the appliance with the glass removed.

5)Verify that the venting and cap are unobstructed.

6)Ensure that the brick panels are installed.

7)Verify log placement. If the pilot cannot be seen when lighting the unit, the logs have been incorrectly positioned.

8)The unit should never be turned off, and on again without a minimum of a 60 second wait.

2)Turn gas control knob so indicator points to "OFF" position and allow 5 minutes for any gas in the combustion chamber to escape.

3)Turn gas control knob counterclockwise so indicator points to the "PILOT" position. Depress the gas control knob fully. Depress the igniter button several times until the pilot lights.After approximately one minute, release the gas control knob. The pilot fl ame should continue to burn. If the pilot does not remain lit, repeat operation allowing a longer period before releasing gas control knob.

4)When the pilot stays lit, turn the gas knob further counterclockwise to the "ON" position.

5)Use the wall switch, thermostat or remote control to turn on the unit.

6)Rotate the fl ame height regulator to adjust the fl ame height higher or lower.

SHUTDOWN

PROCEDURE

1)Use the wall switch, thermostat or remote control to turn off the main burner.

2)Turn the main gas control clockwise to the "OFF" position to turn off the pilot.

3)Turn off all electric power to appliance if service is to be performed.

DO NOT BURN THE APPLIANCE WITHOUT THE GLASS FRONT IN PLACE.

During the first few fires, a white film may develop on the glass front as part of the curing process. The glass should be cleaned or the film will bake on and become very difficult to remove. Use a non-abrasive cleaner and NEVER clean the glass while it is hot.

AERATION

ADJUSTMENT

The air shutter can be adjusted by moving the adjusting wire up or down. The wire is accessed through the bottom louver opening. Open the air shutter for a blue fl ame or close for a yellower

ame. The burner aeration is factory set but may need adjusting due to either the local gas supply or altitude.

Minimum Air Shutter Opening:

3/16" Natural Gas

1/2" Propane

CAUTION: Carbon will be produced if air shutter is closed too much.

Note: Any damage due to carboning resulting from improperly setting the aeration controls is NOT covered under warranty.

Note: Aeration Adjustment should only be performed by an authorized Regency® Installer at the time of installation or service.

LIGHTING

PROCEDURE

IMPORTANT

To ignite or reignite the pilot, you must first release the ten- sion springs below the door.

Only when the pilot holds, without pressure being applied to the control knob, reapply the tension springs to the door. The unit must not be operated with the tension springs unattached.

IMPORTANT Gas cock knob cannot be turned from "PILOT" to "OFF" unless it is partially depressed.

1)Turn burner OFF using "ON/OFF" switch.

FIRST FIRE

The fi rst fi re in your fi replace is part of the paint curing process. To ensure that the paint is properly cured, it is recommended that you burn your fi replace for at least four (4) hours the fi rst time before you use it with the fan on.

When fi rst operated, the unit will release an odour caused by the curing of the paint, the burning off of any oils remaining from manufacturing. Smoke detectors in the house may go off at this time. Open a few windows to ventilate the room for a couple of hours.

The glass panel may require cleaning after the

unit has cooled down. DO NOTATTEMPT

TO CLEAN THE GLASS WHILE IT IS HOT.

Note: When the glass is cold and the appliance is lit, it may cause condensation and fog the glass. This condensation is normal and will disappear in a few minutes as the glass heats up.

Adjustment Wire: push to close or

pull to open aeration cap.

Closed - Tall yellow

Open - Short Blue

34

UltraGlow® G36D Zero Clearance Direct Vent Gas Fireplace

Image 34
Contents G36D Zero Clearance Direct Vent Gas Fireplace 12/18/05Information for MOBILE/MANUFACTURED Homes After First Sale To the New OwnerTable of Contents 300 Safety LabelCopy of Safety Decal for G36D-NG1 Certified for/Certifiée pour Canada and U.S.AImportant Message Save These Instructions InstallationInstallation Checklist Before YOU StartLocating Your GAS Stove G36D Unit DimensionsDiagram Manufactured Mobile Home Additional RequirementsMantel LEG Clearances ClearancesFraming Finishing Combustible Mantels Venting Introduction Unit Assembly Prior to InstallationTop Standoff Assembly Top Facing Support Side Nailing StripsLocations Area where terminal is not permitedExterior Vent Vertical TerminationVenting Rigid Pipe Venting Components List Secure VentRigid Pipe Venting Systems AlternateRigid Pipe Venting Arrangements Horizontal Terminations UltraGlow Direct Vent System FlexInstallation Rigid Pipe Venting Arrangements Vertical Terminations Installation Description Vertical Termination With CO-LINEAR Flex SystemRequired Parts Flex LinerVenting Arrangements Vertical Terminations I g h t Achieved Diagram 3aSnorkel Terminations Ceiling to the position Firestop spacer must be installedDiagram Roof Pitch Continue to assemble pipe lengthsOffset Chart Installation ProceduresFor UltraGlow Direct Vent System Flex GAS Pipe Pressure Testing Pilot AdjustmentGAS Line Installation High ElevationQty Installation of LPG Conversion KitLPG Conversion Kit Contains DC Sparker Kit Contains QtyGround Wire from Kit Ignitor WireSparker Ignitor Wire Piezo IgnitorHeat Shield Install the 1/2 bushing to the heat shieldChain 02-75 02-55 02-52 LOG SET Installation02-53 02-51 02-54 Rear Grate Tab 5th Grate TabLog indentation Front BracketsInstall fl ush glass as per instructions in manual Place embers in these 3 locations On the burner trayFlush Louvers Standard Flush DoorOptional Flush Trim Thermostat Wire Table Remote ControlWall Switch Wall ThermostatWiring Diagram Do not cut the ground terminal off under any circumstancesTo Remove the Fan Installing the Optional FANOpen the bottom louver door Operating Instructions Copy of the Lighting Plate Instructions Maintenance InstructionsNormal Operating Sounds of GAS Appliances Maintenance Installing Valve Removing ValveG36D Main Assembly Parts List Pilot Assembly GasketG36D Flush Front Assembly UltraGlow G36D Zero Clearance Direct Vent Gas Fireplace UltraGlow G36D Zero Clearance Direct Vent Gas Fireplace Conditions WarrantyExclusions Register your UltraGlow online at