Regency G36D Pilot Adjustment, High Elevation, GAS Line Installation, GAS Pipe Pressure Testing

Page 23

INSTALLATION

G36D-NG1 System Data

For 0 to 4500 feet altitude

Burner Inlet Orifice Sizes: #42

Max. Input Rating

26,000

Btu/h

Min. Input Rating

13,100

Btu/h

Supply Pressure

min.5.0" w.c.

Manifold Pressure

 

 

(High)

3.8"+/- 0.2"w.c.

Log Set: Ceramic fi bre, 7 per set.

Vent System: Simpson Dura-Vent Direct Vent System or UltraGlow® Direct Vent System (Flex)

always best to consult with your local authorities and the CAN/CGA B149 installation code.

For USA installations follow local codes and/or the current National Fuel Gas Code, ANSI Z223.1.

When using copper or fl ex connectors use only approved fi ttings. Always provide a union so that gas lines can be easily disconnected for servicing. Flare nuts for copper lines and fl ex connectors are usually considered to meet this requirement.

Important: Always check for gas leaks with a soap and water solution or gas leak detector. Do not use open flame for leak testing.

The manifold pressure is controlled by a regulator built into the gas control, and should be checked at the pressure test point.

Note: To properly check gas pressure, both inlet and manifold pressures should be checked using the valve pressure ports on the valve.

1)

Make sure the valve is in the "OFF"

 

position.

2)

Loosen the "IN" and/or "OUT" pressure

 

tap(s), turning counterclockwise with a

 

1/8" wide fl at screwdriver.

3)

Attach manometer to "IN" and/or "OUT"

 

pressure tap(s) using a 5/16" ID hose.

G36D-LP1 System Data

For 0 to 4500 feet altitude

 

Burner Inlet Orifice Sizes:

#53

Max. Input Rating

26,000

Btu/h

Min. Input Rating

13,800

Btu/h

Supply Pressure

min.12.0" w.c.

Manifold Pressure

 

 

(High)

11"+/- 0.2" w.c.

Log Set: Ceramic fi bre, 7 per set.

Vent System: Simpson Dura-Vent Direct Vent System or UltraGlow® Direct Vent System (Flex)

PILOT ADJUSTMENT

Periodically check the pilot flames. Correct flame pattern has three strong blue flames: 1 flowing around the thermopile, 1 around the thermocouple and 1 flowing across the burner (it does not have to be touching the burner).

Note: If you have an incorrect flame pattern, contact your Regency® dealer for further instructions.

4)

Light the pilot and turn the valve to "ON"

 

position.

5)

The pressure check should be carried out

 

with the unit burning and the setting should

 

be within the limits specifi ed on the safety

 

label.

6)

When fi nished reading manometer, turn

 

off the gas valve, disconnect the hose and

 

tighten the screw (clockwise) with a 1/8"

 

fl at screwdriver. Note: Screw should be

 

snug, but do not over tighten.

S.I.T. VALVE DESCRIPTION

1)

Gas on/off knob

2)

Manual high/low adjustment

3)

Pilot Adjustment

4)

Thermocouple Connection - option

5)

Outlet Pressure Tap

6)

Inlet Pressure Tap

HIGH ELEVATION

 

Incorrect flame pattern will have small,

This unit is approved in Canada for altitude 0

probably yellow flames, not coming into

proper contact with the rear burner or

to 4500 ft. (CAN1 2.17-M91) with the orifi ce

thermopile or thermocouple.

supplied.

 

7)

Pilot Outlet

8)

Main Gas Outlet

9)

ve TC Connection

GAS LINE

INSTALLATION

The gas line can be brought through either the right or the left side of the appliance. The gas valve is situated on the right hand side of the unit and the gas inlet is on the right hand side of the valve.

Note: If the gas line is being installed from the left side, be sure to leave room to accommodate servicing of the fan.

The gas line connection may be made of rigid pipe, copper pipe or an approved fl ex connector. (If you are using rigid pipe, ensure that the valve can be removed for servicing.) Since some municipalities have additional local codes it is

GAS PIPE PRESSURE

TESTING

The appliance must be isolated from the gas supply piping system by closing its individual manual shut-off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig. (3.45 kPa). Disconnect piping from valve at pressures over 1/2 psig.

UltraGlow® G36D Zero Clearance Direct Vent Gas Fireplace

23

Image 23
Contents 12/18/05 G36D Zero Clearance Direct Vent Gas FireplaceTo the New Owner Information for MOBILE/MANUFACTURED Homes After First SaleTable of Contents Certified for/Certifiée pour Canada and U.S.A Safety LabelCopy of Safety Decal for G36D-NG1 300Before YOU Start InstallationInstallation Checklist Important Message Save These InstructionsManufactured Mobile Home Additional Requirements G36D Unit DimensionsDiagram Locating Your GAS StoveFraming Finishing ClearancesMantel LEG Clearances Combustible Mantels Top Facing Support Side Nailing Strips Unit Assembly Prior to InstallationTop Standoff Assembly Venting IntroductionVertical Termination Area where terminal is not permitedExterior Vent LocationsVenting Secure Vent Rigid Pipe Venting Components ListAlternate Rigid Pipe Venting SystemsUltraGlow Direct Vent System Flex Rigid Pipe Venting Arrangements Horizontal TerminationsInstallation Rigid Pipe Venting Arrangements Vertical Terminations Installation Flex Liner Vertical Termination With CO-LINEAR Flex SystemRequired Parts DescriptionVenting Arrangements Vertical Terminations Snorkel Terminations Diagram 3aI g h t Achieved Continue to assemble pipe lengths Firestop spacer must be installedDiagram Roof Pitch Ceiling to the positionFor UltraGlow Direct Vent System Flex Installation ProceduresOffset Chart High Elevation Pilot AdjustmentGAS Line Installation GAS Pipe Pressure TestingDC Sparker Kit Contains Qty Installation of LPG Conversion KitLPG Conversion Kit Contains QtyPiezo Ignitor Ignitor WireSparker Ignitor Wire Ground Wire from KitChain Install the 1/2 bushing to the heat shieldHeat Shield 02-53 02-51 02-54 LOG SET Installation02-75 02-55 02-52 Front Brackets 5th Grate TabLog indentation Rear Grate TabPlace embers in these 3 locations On the burner tray Install fl ush glass as per instructions in manualOptional Flush Trim Standard Flush DoorFlush Louvers Wall Thermostat Remote ControlWall Switch Thermostat Wire TableDo not cut the ground terminal off under any circumstances Wiring DiagramOpen the bottom louver door Installing the Optional FANTo Remove the Fan Operating Instructions Normal Operating Sounds of GAS Appliances Maintenance InstructionsCopy of the Lighting Plate Instructions Maintenance Removing Valve Installing ValveG36D Main Assembly Pilot Assembly Gasket Parts ListG36D Flush Front Assembly UltraGlow G36D Zero Clearance Direct Vent Gas Fireplace UltraGlow G36D Zero Clearance Direct Vent Gas Fireplace Exclusions WarrantyConditions Register your UltraGlow online at