INSTALLATION
G36D-NG1 System Data
For 0 to 4500 feet altitude
Burner Inlet Orifice Sizes: #42
Max. Input Rating | 26,000 | Btu/h |
Min. Input Rating | 13,100 | Btu/h |
Supply Pressure | min.5.0" w.c. | |
Manifold Pressure |
|
|
(High) | 3.8"+/- 0.2"w.c. |
Log Set: Ceramic fi bre, 7 per set.
Vent System: Simpson
always best to consult with your local authorities and the CAN/CGA B149 installation code.
For USA installations follow local codes and/or the current National Fuel Gas Code, ANSI Z223.1.
When using copper or fl ex connectors use only approved fi ttings. Always provide a union so that gas lines can be easily disconnected for servicing. Flare nuts for copper lines and fl ex connectors are usually considered to meet this requirement.
Important: Always check for gas leaks with a soap and water solution or gas leak detector. Do not use open flame for leak testing.
The manifold pressure is controlled by a regulator built into the gas control, and should be checked at the pressure test point.
Note: To properly check gas pressure, both inlet and manifold pressures should be checked using the valve pressure ports on the valve.
1) | Make sure the valve is in the "OFF" |
| position. |
2) | Loosen the "IN" and/or "OUT" pressure |
| tap(s), turning counterclockwise with a |
| 1/8" wide fl at screwdriver. |
3) | Attach manometer to "IN" and/or "OUT" |
| pressure tap(s) using a 5/16" ID hose. |
G36D-LP1 System Data
For 0 to 4500 feet altitude |
| |
Burner Inlet Orifice Sizes: | #53 | |
Max. Input Rating | 26,000 | Btu/h |
Min. Input Rating | 13,800 | Btu/h |
Supply Pressure | min.12.0" w.c. | |
Manifold Pressure |
|
|
(High) | 11"+/- 0.2" w.c. |
Log Set: Ceramic fi bre, 7 per set.
Vent System: Simpson
PILOT ADJUSTMENT
Periodically check the pilot flames. Correct flame pattern has three strong blue flames: 1 flowing around the thermopile, 1 around the thermocouple and 1 flowing across the burner (it does not have to be touching the burner).
Note: If you have an incorrect flame pattern, contact your Regency® dealer for further instructions.
4) | Light the pilot and turn the valve to "ON" |
| position. |
5) | The pressure check should be carried out |
| with the unit burning and the setting should |
| be within the limits specifi ed on the safety |
| label. |
6) | When fi nished reading manometer, turn |
| off the gas valve, disconnect the hose and |
| tighten the screw (clockwise) with a 1/8" |
| fl at screwdriver. Note: Screw should be |
| snug, but do not over tighten. |
S.I.T. VALVE DESCRIPTION
1) | Gas on/off knob |
2) | Manual high/low adjustment |
3) | Pilot Adjustment |
4) | Thermocouple Connection - option |
5) | Outlet Pressure Tap |
6) | Inlet Pressure Tap |
HIGH ELEVATION
| Incorrect flame pattern will have small, | |
This unit is approved in Canada for altitude 0 | probably yellow flames, not coming into | |
proper contact with the rear burner or | ||
to 4500 ft. (CAN1 | ||
thermopile or thermocouple. | ||
supplied. | ||
|
7) | Pilot Outlet |
8) | Main Gas Outlet |
9) | ve TC Connection |
GAS LINE
INSTALLATION
The gas line can be brought through either the right or the left side of the appliance. The gas valve is situated on the right hand side of the unit and the gas inlet is on the right hand side of the valve.
Note: If the gas line is being installed from the left side, be sure to leave room to accommodate servicing of the fan.
The gas line connection may be made of rigid pipe, copper pipe or an approved fl ex connector. (If you are using rigid pipe, ensure that the valve can be removed for servicing.) Since some municipalities have additional local codes it is
GAS PIPE PRESSURE
TESTING
The appliance must be isolated from the gas supply piping system by closing its individual manual
UltraGlow® G36D Zero Clearance Direct Vent Gas Fireplace | 23 |