Regency G36D installation manual Rigid Pipe Venting Arrangements Vertical Terminations, Diagram

Page 16

INSTALLATION

RIGID PIPE VENTING ARRANGEMENTS - VERTICAL TERMINATIONS

(Propane & Natural Gas)

The G36D is approved for a maximum 23 ft. (7.0m) vertical, with a maximum 12 ft. (3.7m) horizontal offset using two 90o elbows (two 45o elbows equal one 90o elbow) with Rigid Pipe vent systems for Propane and Natural Gas, as per diagram 1.

The G36D is approved for a maximum 37 ft. (11.3m) straight vertical, including a maximum 20" (0.5m) horizontal offset using two 90o elbow (two 45o elbows equal one 90o elbow) with Rigid Pipe vent systems for Propane and Natural Gas, as per diagram 2.

Vent must be supported at offsets

Maintain clearances as listed in the"Clearances" section.

Firestops are required at each floor level and whenever passing through a wall.

Note: Must use optional rigid pipe adaptor when using rigid vent systems (Part # 510-994).

Note: UltraGlow® Direct Vent System (Flex) is only approved for horizontal terminations.

Diagram 1

Diagram 2

16

UltraGlow® G36D Zero Clearance Direct Vent Gas Fireplace

Image 16
Contents G36D Zero Clearance Direct Vent Gas Fireplace 12/18/05Information for MOBILE/MANUFACTURED Homes After First Sale To the New OwnerTable of Contents Safety Label Copy of Safety Decal for G36D-NG1300 Certified for/Certifiée pour Canada and U.S.AInstallation Installation ChecklistImportant Message Save These Instructions Before YOU StartG36D Unit Dimensions DiagramLocating Your GAS Stove Manufactured Mobile Home Additional RequirementsMantel LEG Clearances ClearancesFraming Finishing Combustible Mantels Unit Assembly Prior to Installation Top Standoff AssemblyVenting Introduction Top Facing Support Side Nailing StripsArea where terminal is not permited Exterior VentLocations Vertical TerminationVenting Rigid Pipe Venting Components List Secure VentRigid Pipe Venting Systems AlternateRigid Pipe Venting Arrangements Horizontal Terminations UltraGlow Direct Vent System FlexInstallation Rigid Pipe Venting Arrangements Vertical Terminations Installation Vertical Termination With CO-LINEAR Flex System Required PartsDescription Flex LinerVenting Arrangements Vertical Terminations I g h t Achieved Diagram 3aSnorkel Terminations Firestop spacer must be installed Diagram Roof PitchCeiling to the position Continue to assemble pipe lengthsOffset Chart Installation ProceduresFor UltraGlow Direct Vent System Flex Pilot Adjustment GAS Line InstallationGAS Pipe Pressure Testing High ElevationInstallation of LPG Conversion Kit LPG Conversion Kit ContainsQty DC Sparker Kit Contains QtyIgnitor Wire Sparker Ignitor WireGround Wire from Kit Piezo IgnitorHeat Shield Install the 1/2 bushing to the heat shieldChain 02-75 02-55 02-52 LOG SET Installation02-53 02-51 02-54 5th Grate Tab Log indentationRear Grate Tab Front BracketsInstall fl ush glass as per instructions in manual Place embers in these 3 locations On the burner trayFlush Louvers Standard Flush DoorOptional Flush Trim Remote Control Wall SwitchThermostat Wire Table Wall ThermostatWiring Diagram Do not cut the ground terminal off under any circumstancesTo Remove the Fan Installing the Optional FANOpen the bottom louver door Operating Instructions Copy of the Lighting Plate Instructions Maintenance InstructionsNormal Operating Sounds of GAS Appliances Maintenance Installing Valve Removing ValveG36D Main Assembly Parts List Pilot Assembly GasketG36D Flush Front Assembly UltraGlow G36D Zero Clearance Direct Vent Gas Fireplace UltraGlow G36D Zero Clearance Direct Vent Gas Fireplace Conditions WarrantyExclusions Register your UltraGlow online at