Regency G36D installation manual Installation

Page 15

INSTALLATION

RIGID PIPE VENTING ARRANGEMENTS - HORIZONTAL TERMINATIONS

UltraGlow® DIRECT VENT SYSTEM (FLEX)

(Propane & Natural Gas)

The diagram below shows examples of horizontal termination arrangements using two 90o elbows (two 45o elbows equal one 90o elbow).

Note: 1) A maximum of two 90o elbows are permitted.

2)A minimum of 6 ft. (1.8m) vertical from base of unit is required if two 90o elbows are used.

3)Minimum distance between elbows is 2 ft. (0.6m).

4)Determine the permitted range of horizontal termination arrangements by using chart in the "Rigid Pepi Venting Arrangements - Vertical Termination" section and deducting 3 ft. (0.9m) from the maximum horizontal distance for the second 90o elbow.

If length "B" is increased, length "A" must be decreased by a corresponding amount.

All Rigid Pipe Systems

4" inner diameter

6-5/8" outer diameter

UltraGlow® Flex Vent 4" inner diameter

6-7/8" inner diameter

A vent guard should be used whenever the termination is lower than the specifi ed minimum or as per local codes.

Maintain clearances to combustibles as listed in the "Clearances," "Locating Your Gas Stoves," "Combustible Mantels," "Framing and Finishing," & "Hearth Requirement" sections.

Horizontal vent must be supported every 3 feet.

UltraGlow® G36D Zero Clearance Direct Vent Gas Fireplace

15

Image 15
Contents 12/18/05 G36D Zero Clearance Direct Vent Gas FireplaceTo the New Owner Information for MOBILE/MANUFACTURED Homes After First SaleTable of Contents Certified for/Certifiée pour Canada and U.S.A Safety LabelCopy of Safety Decal for G36D-NG1 300Before YOU Start InstallationInstallation Checklist Important Message Save These InstructionsManufactured Mobile Home Additional Requirements G36D Unit DimensionsDiagram Locating Your GAS StoveClearances Mantel LEG ClearancesFraming Finishing Combustible Mantels Top Facing Support Side Nailing Strips Unit Assembly Prior to InstallationTop Standoff Assembly Venting IntroductionVertical Termination Area where terminal is not permitedExterior Vent LocationsVenting Secure Vent Rigid Pipe Venting Components ListAlternate Rigid Pipe Venting SystemsUltraGlow Direct Vent System Flex Rigid Pipe Venting Arrangements Horizontal TerminationsInstallation Rigid Pipe Venting Arrangements Vertical Terminations Installation Flex Liner Vertical Termination With CO-LINEAR Flex SystemRequired Parts DescriptionVenting Arrangements Vertical Terminations Diagram 3a I g h t AchievedSnorkel Terminations Continue to assemble pipe lengths Firestop spacer must be installedDiagram Roof Pitch Ceiling to the positionInstallation Procedures Offset ChartFor UltraGlow Direct Vent System Flex High Elevation Pilot AdjustmentGAS Line Installation GAS Pipe Pressure TestingDC Sparker Kit Contains Qty Installation of LPG Conversion KitLPG Conversion Kit Contains QtyPiezo Ignitor Ignitor WireSparker Ignitor Wire Ground Wire from KitInstall the 1/2 bushing to the heat shield Heat ShieldChain LOG SET Installation 02-75 02-55 02-5202-53 02-51 02-54 Front Brackets 5th Grate TabLog indentation Rear Grate TabPlace embers in these 3 locations On the burner tray Install fl ush glass as per instructions in manualStandard Flush Door Flush LouversOptional Flush Trim Wall Thermostat Remote ControlWall Switch Thermostat Wire TableDo not cut the ground terminal off under any circumstances Wiring DiagramInstalling the Optional FAN To Remove the FanOpen the bottom louver door Operating Instructions Maintenance Instructions Copy of the Lighting Plate InstructionsNormal Operating Sounds of GAS Appliances Maintenance Removing Valve Installing ValveG36D Main Assembly Pilot Assembly Gasket Parts ListG36D Flush Front Assembly UltraGlow G36D Zero Clearance Direct Vent Gas Fireplace UltraGlow G36D Zero Clearance Direct Vent Gas Fireplace Warranty ConditionsExclusions Register your UltraGlow online at