1.7.4 Dimensioning of pipe systems

The below diagram shows the current pressure drop graphs meant for the dimensioning of pipe systems used in connection with the DELTABOOSTER plant.

The diagram illustrates two vertical divisions for

 

 

 

II) electro galvanized steel pipes

15x2 mm

-

22x2.5 mm -

30x4 mm

I) stainless steel pipes

15x1.5 mm

-

22x2 mm

- 30x3 mm

The pressure drop per metre of pipe at a given water volume may be read from the fol- lowing pressure drop graph.

Water volume [l/min]

When dimensioning the system be careful that the maximum pressure drop at the remotest outlet point does not exceed 15 bar at full load.

The pressure drop in elbows and branches is of minor importance in relation to the pressure drop in the pipes.

21

Image 21
Contents Deltabooster Deltabooster How to use the Deltabooster Layout of system Product DescriptionPage Model survey and main functions Deltabooster switchboardC3K pumps Number of Pumps Selection of systemLine Pressure Selection of Spray LanceIdentification of model Technical dataWater tank Control system2 C3K pump ClassificaNo. of pumps Model 44C3 Dimensions, weight and total performance per systemLocation of the Deltabooster Differential pressure of solenoid valve measured in bar Installation requirements for water connectionInstallation requirements for mains power connection Deltabooster control systemMax 125 a Pipe system Location of pipelines/general instructionsTypes of pipes standards PipingComponents TuyauterieRørledningskomponenter Fittings, standardsRohrleitungskomponenten-Elements Bezeichnung Designation DimensionRohrhalterung tuyauSupport Bezeichnung DesignationdimensionKobber Copper Rohrleitungskomponenten-ElementsDimensioning of pipe systems Page Example 50 m 40 m 70 m ExamplesPressure Drop Bar30 m 10 m M 80 m Example 60 mPressure DropExample 20 m 40 m 30 m 60 m 30 m 15 m 80 m Ring systemBar 10 bar Mounting requirements and hints Temperature compensationBends/hose connections CompensationMounting of Pipe LINES/GENERAL Instructions Fixation AT Corners and TEE ConnectorsRemounting Mounting in Connection SocketOutlet Station Outlet points and accessoriesDetachable foam injector AccessoriesMultipressure spray lance system Bar black nozzle protectionBar grey nozzle protection Location Sketch Mounting base Connection of inlet water Control of filter in water tankFilter Page Oil control Starting up/runningStart Venting of pumpsVenting of pipe system Adjustment of line pressureSafety How to use the DeltaboosterDo not Interfere with this Setting Save these instructions for laterModel survey Functional diagram Main / emergency switch Control switch / starting switch and stopping switchInstrument panel Control panel Setting and reading of Deltabooster On 50C Setting of water temperatureBoth should be on for the operation of a single plant Connection and disconnection of C3K pumpsReading of hour meters Starting up/running in cf. Fig Page Multipressure spray lance system Operation after starting up Operation after starting up outlet points and equipmentAfter use Admixture of detergentsGeneral guidelines for the dosage of detergents Service intervals/oil change MaintenanceWater filter CouplingsProblem Possible cause Correction Trouble-shooting and possible correctionPortugal 7309021