3.4.3 The control panel

The control panel (5) is based upon a schematic drawing of the system where a number of control lamps will show the status of the system and possible faults.

The control lamps have been divided into three categories:

Green indicating a coupled unit (valve, C3K)

Yellow indicating an activated sensor (pressure switch, flow, level)

Red indicating a serious fault (leakage, over heating, etc.)

In normal conditions only the green and the yellow control lamps will glow.

If a serious fault arises the relevant red control lamp will start flashing and at the same time the system will stop operating completely. Status from the other lamps is retained so the condition at the moment of the fault is visible.

If a red control lamp flashes the system can usually not be re-started until the fault has been corrected unless a motor pump unit is disengaged because of a too high temperature or a too high power consumption. The plant can be restarted by following the procedure described in section 3.4.2 as the steering will disconnect the defective motor. Thus the actual control lamp will glow contantly (cf. the section on “3.10 Trouble-shooting and correction”).

The meaning of the control panel and the individual control lamps appears from Fig. 2 below.

Fig. 2

 

 

RED: Flashes at illegal sensor combination [water inlet will stop]

YELLOW: Temperature adjustment

RED:

Flashes at a water temperature in tank above 80°C [system will stop]

 

connected

RED:

Flashes at lack of water

Glows if the regulation is

 

 

temporarily disconnected

 

YELLOW: Glows when high water level has been achieved

because of an insufficient

 

[water inlet will stop]

water supply.

 

YELLOW: Glows when low water level has been achieved

 

 

 

[water inlet will start]

GREEN:

Cold inlet

 

 

GREEN:

Hot inlet

 

 

 

 

 

YELLOW: Glows when water is recirculated

 

 

 

GREEN: Glows when relief valve is closed [normal operat.]

 

 

 

YELLOW: Glows at normal working pressure [high pressure]

 

 

 

YELLOW: Glows when line pressure exceeds 25 bar.

RED: *) Flashes if the temp. in motor no. 1 is excessive or the oil level low [system will stop]

*) Glows constantly when starting the plant with a defective motor pump unit

RED: *) Flashes if the current cons. on pump no. 1 is excessive [system will stop]

GREEN: Glows when pump no. 1 is in operation

RED: Flashes in case of leakage on internal high pressure hose [system will stop]

RED: Flashes in case of leakage on external pipe line [system will stop]

42

Image 42
Contents Deltabooster Deltabooster How to use the Deltabooster Product Description Layout of systemPage Deltabooster switchboard Model survey and main functionsC3K pumps Line Pressure Selection of systemNumber of Pumps Selection of Spray LanceTechnical data Identification of model2 C3K pump Control systemWater tank ClassificaDimensions, weight and total performance per system No. of pumps Model 44C3Location of the Deltabooster Installation requirements for water connection Differential pressure of solenoid valve measured in barInstallation requirements for mains power connection Deltabooster control systemMax 125 a Pipe system Location of pipelines/general instructionsTypes of pipes standards Rørledningskomponenter TuyauteriePipingComponents Fittings, standardsRohrleitungskomponenten-Elements Dimension Bezeichnung DesignationBezeichnung Designationdimension Rohrhalterung tuyauSupportRohrleitungskomponenten-Elements Kobber CopperDimensioning of pipe systems Page Pressure Drop ExamplesExample 50 m 40 m 70 m BarPressure Example 60 m30 m 10 m M 80 m DropExample 20 m 40 m 30 m 60 m 30 m 15 m 80 m Ring systemBar 10 bar Bends/hose connections Temperature compensationMounting requirements and hints CompensationFixation AT Corners and TEE Connectors Mounting of Pipe LINES/GENERAL InstructionsMounting in Connection Socket RemountingOutlet points and accessories Outlet StationAccessories Detachable foam injectorMultipressure spray lance system Bar black nozzle protectionBar grey nozzle protection Location Sketch Mounting base Connection of inlet water Control of filter in water tankFilter Page Start Starting up/runningOil control Venting of pumpsAdjustment of line pressure Venting of pipe systemDo not Interfere with this Setting How to use the DeltaboosterSafety Save these instructions for laterModel survey Functional diagram Main / emergency switch Control switch / starting switch and stopping switchInstrument panel Control panel Setting and reading of Deltabooster Setting of water temperature On 50CConnection and disconnection of C3K pumps Both should be on for the operation of a single plantReading of hour meters Starting up/running in cf. Fig Page Multipressure spray lance system Operation after starting up outlet points and equipment Operation after starting upAdmixture of detergents After useGeneral guidelines for the dosage of detergents Water filter MaintenanceService intervals/oil change CouplingsTrouble-shooting and possible correction Problem Possible cause CorrectionPortugal 7309021