1.7.6 Mounting requirements and hints

Temperature compensation

When hot water (max. 75°C) is used in the system due regard should be paid to thermal expan- sion of the pipes when mounting the system. When raising the temperature from10°C to 75°C the system will expand some 0.7 mm/m. In order to allow for this expansion long straight lines should be fitted with compensators in the form of U-bends or hose connections.The pipe system should not be fixed too close to any corners and close to Tee connectors at outlet points.

U-bends/hose connections

At a max. temperature on the system of 75°C a compensator should be fitted at 20 m intervals if there are no elbows on the line. If the pipe may expand at one end compensators may be left out if the pipe is not fixed at the Tee connectors at the same time. Compensation for 15 and 22 should be in the form of hose connections or as U-bends on the pipe. Use hose connec- tions for 30.

COMPENSATION

Pipe

Hose no.

Hose no. stainless

L (mm)

L min (mm)

R min (mm)

15

6300453

6301191

350

450

40

22

6300453/6300454*

6301191/6202161*

350/480

550

55

30

6300454

6202161

480

 

 

*If the pipe line carries more than the water volume from 3 pumps 6300454 respectively 6202161 hoses should be fitted.

26

Image 26
Contents Deltabooster Deltabooster How to use the Deltabooster Product Description Layout of systemPage Deltabooster switchboard Model survey and main functionsC3K pumps Line Pressure Selection of systemNumber of Pumps Selection of Spray LanceTechnical data Identification of model2 C3K pump Control systemWater tank ClassificaDimensions, weight and total performance per system No. of pumps Model 44C3Location of the Deltabooster Installation requirements for water connection Differential pressure of solenoid valve measured in barMax 125 a Installation requirements for mains power connectionDeltabooster control system Types of pipes standards Pipe systemLocation of pipelines/general instructions Rørledningskomponenter TuyauteriePipingComponents Fittings, standardsRohrleitungskomponenten-Elements Dimension Bezeichnung DesignationBezeichnung Designationdimension Rohrhalterung tuyauSupportRohrleitungskomponenten-Elements Kobber CopperDimensioning of pipe systems Page Pressure Drop ExamplesExample 50 m 40 m 70 m BarPressure Example 60 m30 m 10 m M 80 m DropBar 10 bar Example 20 m 40 m 30 m 60 m 30 m 15 m 80 mRing system Bends/hose connections Temperature compensationMounting requirements and hints CompensationFixation AT Corners and TEE Connectors Mounting of Pipe LINES/GENERAL InstructionsMounting in Connection Socket RemountingOutlet points and accessories Outlet StationAccessories Detachable foam injectorBar grey nozzle protection Multipressure spray lance systemBar black nozzle protection Location Sketch Mounting base Filter Connection of inlet waterControl of filter in water tank Page Start Starting up/runningOil control Venting of pumpsAdjustment of line pressure Venting of pipe systemDo not Interfere with this Setting How to use the DeltaboosterSafety Save these instructions for laterModel survey Functional diagram Instrument panel Main / emergency switchControl switch / starting switch and stopping switch Control panel Setting and reading of Deltabooster Setting of water temperature On 50CConnection and disconnection of C3K pumps Both should be on for the operation of a single plantReading of hour meters Starting up/running in cf. Fig Page Multipressure spray lance system Operation after starting up outlet points and equipment Operation after starting upAdmixture of detergents After useGeneral guidelines for the dosage of detergents Water filter MaintenanceService intervals/oil change CouplingsTrouble-shooting and possible correction Problem Possible cause CorrectionPortugal 7309021