2. Continue Adding Flue Components
Refer to Cinch Pipe and Termination Cap installation in- structions.
•Continue adding flue components, locking each succeed- ing component into place.
•Ensure that each succeeding flue component is secure- ly fitted and locked into the preceding component in the flue system. Securing pipe sections with a maximum of two screws is recommended.
•90° elbows may be installed and rotated to any point around the preceding component’s vertical axis. If an el- bow does not end up in a locked position with the pre- ceding component, attach with a minimum of two (2) sheet metal screws.
3.Install Support Brackets
Refer to Cinch Pipe and Termination Cap installation in- structions.
HEAT SHIELD
TRIM HEAT SHIELD IF TOO LONG, ADD TO SHIELD IF TOO SHORT
EXTERIOR
FIRESTOP
INTERIOR
FIRESTOP
Figure 20. Heat Shield, Interior & Exterior Firestops
For Vertical Runs - One ceiling firestop is REQUIRED at the hole in each ceiling through which the flue passes.
4. Install Firestops
For Horizontal Runs - Firestops are REQUIRED on both sides of a combustible wall through which the flue passes.
NOTE: Model
To install firestops for horizontal runs that pass through either interior or exterior walls:
• Cut a 10” x 12” (254mm X 305mm) hole through the wall.
NOTE: The center of the hole is one (1) inch (25.4mm) above the center of the horizontal flue pipe.
•Position the firestops on both sides of the hole previ- ously cut and secure the firestops with nails or screws.
To install firestops for vertical runs that pass through ceilings:
•Position a plumb bob directly over the center of the verti- cal flue component.
•Mark the ceiling to establish the centerpoint of the flue.
•Drill a hole or drive a nail through this centerpoint.
•Check the floor above for any obstructions, such as wir- ing or plumbing runs.
•Reposition the fireplace and flue system, if necessary, to accommodate the ceiling joists and/or obstructions.
•Cut an
• The heat shields of the firestops MUST BE placed to- | • Frame the hole with framing lumber the same size as the |
wards the top of the hole. | ceiling joists. |
• Continue the flue run through the firestops.
NOTE: There must be NO INSULATION or other | 10" (254mm) |
combustibles inside the framed firestop opening. | 10" (254mm) |
|
| 10" |
|
| CHIMNEY |
|
|
| HOLE | |
| INTERIOR |
|
|
|
| WALL SHIELD |
|
|
|
|
|
| NEW | EXISTING CEILING |
|
|
| JOISTS | |
|
|
| FRAMING | |
|
|
|
| |
|
|
| MEMBERS |
|
|
| 12" | CEILING |
|
|
|
|
| |
|
|
| Figure 21. Hole & New Framing Members | |
| Figure 19. 10" x 12" Hole and Flue Pipe |
|
|
|
28 | Heat & Glo • |
|