Rosemount 3051N
Reference Manual
FIGURE 2-1. Electronics Board.
ELECTRONICS BOARD
OFF
ON
HI
LO
Alarm
Security
FIGURE 2-2. Rosemount 3051N with Optional LCD Meter.
COMMISSIONING THE ROSEMOUNT 3051N WITH A
NOTE
Security jumper not installed = Not Write Protected.
Alarm jumper not installed = High Alarm.
Commissioning consists of testing the transmitter and verifying transmitter configuration data. You may commission Rosemount 3051N transmitters either before or after installation. Commissioning the transmitter on the bench before installation using a