Rosemount 3051N
Reference Manual
Table
Symptom | Corrective Actions |
|
|
Milliamp Reading Is Zero | • | Check if power polarity is reversed. |
| • Verify voltage across terminals (should be 10 to 55 V dc). | |
| • Check for bad diode in terminal block. | |
|
|
|
Transmitter Not Communicating with | • | Check power supply voltage at transmitter (minimum 10.5 V). |
HART Communicator | • Verify calibration settings (4 and 20 mA points) | |
| ||
| • Check load resistance (250 Ω minimum). | |
| • Check if unit is addressed properly. | |
|
|
|
Milliamp Reading Is Low or High | • | Check pressure variable reading for saturation. |
| • Check if output in alarm condition. | |
| • Verify 4 and 20 mA range points. | |
| • Perform | |
|
|
|
No Response to Changes in | • | Check test equipment. |
Applied Pressure | • Check impulse piping for blockage. | |
| ||
| • Check disabled span adjustment. | |
| • Check if output in alarm condition. | |
|
|
|
Pressure Variable Reading Is | • | Check impulse piping for blockage. |
Low or High | • | Check test equipment. |
| ||
| • Perform full sensor trim. | |
|
|
|
Pressure Variable Reading Is Erratic | • | Check impulse piping for blockage. |
| • | Check damping. |
| • Check for EMF interference. |