Reference Manual
Rosemount 3051N
FIGURE 2-5. Square Root Output Transition Point.
Full Scale Output |
|
|
Full Scale | ||
(mA dc) |
| Flow (%) |
|
| |
|
|
|
Sq. Root |
Curve |
Transition Point |
Linear Section |
Sq. Root Curve
Transition
Point
Slope=42
Slope=1
Rerange | The Range Values command sets the 4 and 20 mA points (lower and upper |
| range values). Setting the range values to the limits of expected readings |
| maximizes transmitter performance. In practice, you may reset the transmitter |
| range values as often as necessary to reflect changing process conditions. |
| You may use one of three methods to rerange the transmitter. Each method is |
| unique; examine all three closely before deciding which method to use. |
Rerange with a
Communicator Only
HART Comm. | 1, 2, 3, 1, 1 |
|
|
Reranging using only the communicator changes the values of the analog 4 and 20 mA points independently without a pressure input.
NOTE
Changing the lower or upper range point results in similar changes to the span.
To rerange using only the communicator, enter the