Reference Manual
Rosemount 3051N
FIGURE 6-1. Exploded View of the Rosemount 3051N with Optional LCD Meter.
Installing the Meter
a.Select 5 CM xfer fnct. Enter the transmitter transfer function for the meter. Select sq root to display flow units. The custom meter transfer function is independent of the analog output transfer function.
8.Select SEND (F2) to upload the configuration to the transmitter.
Interconnecting Pins
Jumpers (Top and Bottom)
LCD Meter
Extended
Cover
For transmitters ordered with the LCD meter, the meter is shipped installed. Installing the meter on an existing Rosemount 3051N transmitter requires a small instrument screwdriver and the meter kit (when the kit is made available by Rosemount Nuclear Instruments, Inc.).
To maintain the Rosemount 3051N qualification status, any piece parts for the Rosemount 3051N (if available) must be supplied by RNII.
The meter kit includes:
•one LCD meter assembly
•one extended cover with
•two nylon standoffs
•two captive screws
•one
Use the following procedure and Figure
1.IF the transmitter is installed in a loop, THEN secure the loop and disconnect power.
2. Remove the transmitter cover opposite the field terminal side. Do not remove the instrument covers in explosive environments when the circuit is alive.
3.Remove the failure mode and alarm jumpers from the electronics module and insert them in their new positions above and below the meter readout on the meter assembly.
See “Safety Messages” in Section 6 for warning information.