Reference Manual
Rosemount 3051N
FUNCTIONAL
SPECIFICATIONS
Service | Liquid, gas, or vapor |
Output | |
| on HART® protocol |
Power Supply | Load Limitations |
| Maximum loop resistance is determined by the voltage level of the |
| external power supply, as described by: |
| Max. Loop Resistance = 43.5 (Power Supply Voltage – 10.5) ohms |
Load (ohms)
1935 |
|
|
|
|
|
|
|
1500 |
|
|
|
|
|
|
|
|
|
|
|
|
| ||
1000 |
|
|
|
|
| Design | |
|
|
|
|
|
| ||
500 |
|
|
|
|
| Region | |
0 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
10.5 | 20 | 30 | 40 | 55 |
|
| Voltage (V dc) |
|
|
| Communication requires a minimum loop resistance of 250 ohms. |
Temperature Limits | Ambient | |
| 0 to 185 | °F |
| with meter option: | |
| 0 to 175 | °F |
| Process(1) (2) (3) | |
| 0 to 250 | °F |
| 0 to 300 | °F |
Storage
0 to 212 °F
0 to 185 °F
(1)Process temperatures above 185 °F (85 °C) require derating the ambient temperature limits by 1.5 °F per degree above 185 °F.
(2)220 °F (104 °C) limit in vacuum service; 130 °F (54 °C) for pressures below 0.5 psia
(3)EPR