Hoshizaki 73168 service manual Service Menu Chart

Page 22

b) Service Menu Chart

Service

 

Setting Range

 

Factory Default

Menu

Item and Details

Cabinet

 

Rail

Cabinet

 

Rail

F0

Defrost Interval

1 to 12 hours in

 

N/A

6

 

N/A

 

• The cabinet uses a time initiated

1 hour increments.

 

 

 

 

 

 

 

 

 

 

 

 

 

heated defrost.

 

 

 

 

 

 

 

• The change in the defrost

 

 

 

 

 

 

 

interval setting will take effect

 

 

 

 

 

 

 

immediately. The next defrost

 

 

 

 

 

 

 

will take place after the newly

 

 

 

 

 

 

 

set time interval has elapsed.

 

 

 

 

 

 

 

• Initiating a manual defrost on the

 

 

 

 

 

 

 

cabinet will restart the defrost

 

 

 

 

 

 

 

timer.

 

 

 

 

 

 

F1

Defrost Termination Temperature

41 to 68°F

 

N/A

49°F (9.4°C)

 

N/A

 

Do not adjust. For

(5 to 20°C)

 

 

 

 

 

 

recommendations, contact

in 1 degree

 

 

 

 

 

 

Hoshizaki Technical Support.

increments

 

 

 

 

 

F2

Setpoint Temperature Differential

Both the + and - values can be

Comp on

 

Comp on

 

Use "SET" button to scroll through

adjusted between 0 to 6.3°F in

0°F (0°C)

 

0°F (0°C)

 

all 4 settings.

increments of .9°F

 

at setpoint

 

at setpoint

 

• You cannot set both + and - to

(0 to 3.5°C in increments of .5°C)

 

 

 

 

(decimal not displayed)

 

Comp off

 

Comp off

 

0.0.

 

 

 

 

 

 

-3.6°F (-2°C)

-3.6°F (-2°C)

 

• Negative value indicated by LED

 

 

 

 

 

 

 

below setpoint

 

below setpoint

 

to left of number.

 

 

 

 

 

 

F3

High Temperature Alarm Delay

0 to 3 hours in 1 hour increments

 

2

 

Time: See "III.A. Alarm Signals."

 

 

 

 

 

 

F4

Low Temperature Alarm Delay

0 or 1 hour

 

 

1

 

Time: See "III.A. Alarm Signals."

 

 

 

 

 

 

F5

Temperature Display

Fahrenheit or Celsius

 

°F

F6

Alarm History: maximum 8 alarms.

Alarms displayed newest to oldest.

N/A

 

 

When "--" appears, you have

 

 

 

 

No reset for alarm history

reached the end of the alarm

 

 

 

 

available.

history.

 

 

 

 

F7

Compressor Run Time (%):

N/A

 

N/A

 

Displays compressor run time

 

 

 

 

 

 

 

percentage between the 2 most

 

 

 

 

 

 

 

recent defrosts.

 

 

 

 

 

 

F8

Not Used

N/A

 

N/A

F9

Rail Cooling Switch:

0=rail fans on continuously (same

N/A

 

2

 

"LOW" Rail Fan Adjustment (rail

as "NORMAL" position)

 

 

 

 

 

section only)

1=rail fans on 15 sec.

 

 

 

 

 

 

rail fans off 90 sec.

 

 

 

 

 

 

2=rail fans on 1 sec.

 

 

 

 

 

 

rail fans off 90 sec.

 

 

 

 

FA

High Condenser Temperature

Adjustable between 140 to 167°F

140°F (60°C)

Do not

Alarm Setting (clogged filter):

(60 to 75°C).

 

(1 not displayed)

adjust

For recommendations, contact

 

 

 

 

 

 

 

Hoshizaki Technical Support.

 

 

 

 

 

 

Fb

Audible Control

N/A

 

N/A

22

Image 22
Contents Superior Degree Reliability Number Issued Revised Hoshizaki AMERICA, INC Contents Page Page Indicates important information about the use and care Important Safety InformationSerious injury UnitSpecifications Nameplate Ratings DimensionsII. General Information Construction Power Switch ON, Rail Cooling Switch Normal or LOW Power Switch ON, Rail Cooling Switch OFFSequence of Operation Cool Down Restart Cabinet DefrostCabinet Defrost Power Switch ON, Rail Cooling Switch OFF Rail DefrostPower Switch ON, Rail Cooling Switch OFF Cabinet OperationPower Switch ON, Rail Cooling Switch Normal or LOW Position Rail CoolingCabinet and Rail Cooling Control Board Control Board LocationFront Rear Control Board LayoutService Menu LED Display and Service Lock-OutAlarm Signal Compressor Short Cycle ProtectionSwitch Settings Controls and AdjustmentsTemperature Display Energy Saving Mode Temperature SetpointCabinet Defrost Temperature Correction Factor Service Menu Service Menu AccessService Menu Chart Control Board Check Procedure Alarm SignalsControl Board Replacement Perimeter Heater Thermistor CheckCompressor Protector III. Service Diagnosis Alarm SignalsAlarm Priority Problem Reset, Corrections, and Adjustments High Temperature Alarm E1 Reset OptionsLow Temperature Alarm E2 Cabinet Defrost Alarm E3 High Condenser Temperature Alarm clogged filter E7 Possible Causes Defrost Thermistor cabinet Malfunction Alarm E85a. Secondary Defrost Thermistor Rail, not used Condenser Thermistor Malfunction Alarm E9 Control Board Alarms EA and ED Service ChartNo Operation Cabinet Cooling Problem Possible Cause Remedy Rail Cooling Cabinet Defrost Other Service for Refrigerant Lines IV. Removal and Replacement of ComponentsRefrigerant Recovery Brazing Evacuation and Recharge R-404APage Removal and Replacement of Refrigeration System Cartridge Refrigerant Recovery ProcedurePage Refrigeration System Pump‑Down Procedure Page Defrost Thermistor Rail Thermistor Removal and Replacement of Compressor Removal and Replacement of Cabinet Evaporator Removal and Replacement of Expansion Valve Removal and Replacement of Liquid Line Valve Removal and Replacement of Condenser Cabinet Thermistor Removal and Replacement of Thermistors and ThermostatDefrost Thermistor Defrost Thermostat Rail ThermistorRemoval and Replacement of Defrost Heater Condenser Thermistor clogged filterRemoval and Replacement of Fan Motors Cabinet Fan MotorCondenser Fan Motor Rail Fan MotorRemoval and Replacement of Door Gasket Door Re-Hinging and Drawer ConversionCleaning and Maintenance Instructions Work SurfaceCabinet Interior Rail and Rail CoverExterior Door/Drawer GasketsRail Condensate Pan MaintenancePower Supply Connection Air FilterShutdown and Long Storage Refrigeration Circuit VI. Technical Information HPR100A-DWiring Diagrams HPR46A-D2a. HPR72A-D Auxiliary Code U-5 and Earlier 2b. HPR72A-D Auxiliary Code U-6 and Later Awaiting Data