Hoshizaki 73168 service manual Operation, Power Switch ON, Rail Cooling Switch OFF Cabinet

Page 12
Stage 1:
5-minute Comp delay timer

Power Switch "ON," Rail Cooling Switch "OFF"

1. Cabinet

C.

Cycle Steps

1.Startup

2-minute

Comp delay timer starts

6-hour DT starts

 

2. Cool Down

 

3. Cool Down Achieved

 

4. Cabinet Defrost

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

From 5 below

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2-minute Comp

 

 

 

 

 

 

 

 

 

 

DTh in control

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

delay timer starts

 

to

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CTh reaches

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CTh warms setpoint

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3.6°F (2°C)

 

 

• 6 hour DT expires, then

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

or more

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

resets

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

below setpoint

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

100-minute defrost

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CTh in control

 

 

 

 

 

 

 

 

 

 

 

 

termination timer starts

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cooling

Sequence of

 

Operation

Initial startup begins here

To 5 below

12

CabFM energized

CabFM energized

CabFM energized

CLLV energized

CLLV energized

CLLV energized

CLLV energized

DH energized

PH energized

Comp energized

PH energized

CabFM de-energized

 

ConFM energized

Comp de-energized

Comp de-energized

 

PH energized

ConFM de-energized

ConFM de-energized

 

 

 

PH de-energized

From 4 above

5.Cabinet Cool Down Defrost Recovery (defrost terminated)

DTh reaches 49°F (9.4°C) or

100-minute defrost termination timer expires or DTst temperature reaches 120°F±5°F (49°C±3°C)

Stage 2:

5-minute CabFM and

PH delay timer

To 2 above

CLLV energized

CabFM and PH

CabFM energized

DH de-energized

energize for 10 sec.

CLLV energized

CabFM de-energized

CLLV energized

Comp energized

Comp de-energized

Comp energized

ConFM energized

ConFM de-energized

ConFM energized

PH energized

PH de-energized

 

 

Legend: CabFM-cabinet fan motor Comp-compressorConFM-condenser fan motor CLLV-cabinet liquid line valve CTh-cabinet thermistor DH-defrost heater DT-defrost timer DTh-defrost thermistor DTst-defrost thermostat PH-perimeter heater

Image 12
Contents Superior Degree Reliability Number Issued Revised Hoshizaki AMERICA, INC Contents Page Page Important Safety Information Serious injuryIndicates important information about the use and care UnitSpecifications Nameplate Ratings DimensionsII. General Information Construction Power Switch ON, Rail Cooling Switch OFF Power Switch ON, Rail Cooling Switch Normal or LOWSequence of Operation Cool Down Restart Cabinet DefrostCabinet Defrost Power Switch ON, Rail Cooling Switch OFF Rail DefrostPower Switch ON, Rail Cooling Switch OFF Cabinet OperationPower Switch ON, Rail Cooling Switch Normal or LOW Position Rail CoolingCabinet and Rail Cooling Control Board Control Board LocationFront Rear Control Board LayoutLED Display and Service Lock-Out Alarm SignalService Menu Compressor Short Cycle ProtectionControls and Adjustments Switch SettingsTemperature Display Temperature Setpoint Energy Saving ModeCabinet Defrost Temperature Correction Factor Service Menu Service Menu AccessService Menu Chart Alarm Signals Control Board Check ProcedureControl Board Replacement Thermistor Check Perimeter HeaterCompressor Protector III. Service Diagnosis Alarm SignalsAlarm Priority Problem Reset, Corrections, and Adjustments High Temperature Alarm E1 Reset OptionsLow Temperature Alarm E2 Cabinet Defrost Alarm E3 High Condenser Temperature Alarm clogged filter E7 Defrost Thermistor cabinet Malfunction Alarm E8 Possible Causes5a. Secondary Defrost Thermistor Rail, not used Condenser Thermistor Malfunction Alarm E9 Service Chart Control Board Alarms EA and EDNo Operation Cabinet Cooling Problem Possible Cause Remedy Rail Cooling Cabinet Defrost Other IV. Removal and Replacement of Components Service for Refrigerant LinesRefrigerant Recovery Brazing Evacuation and Recharge R-404APage Removal and Replacement of Refrigeration System Cartridge Refrigerant Recovery ProcedurePage Refrigeration System Pump‑Down Procedure Page Defrost Thermistor Rail Thermistor Removal and Replacement of Compressor Removal and Replacement of Cabinet Evaporator Removal and Replacement of Expansion Valve Removal and Replacement of Liquid Line Valve Removal and Replacement of Condenser Removal and Replacement of Thermistors and Thermostat Cabinet ThermistorDefrost Thermistor Defrost Thermostat Rail ThermistorRemoval and Replacement of Defrost Heater Condenser Thermistor clogged filterRemoval and Replacement of Fan Motors Cabinet Fan MotorCondenser Fan Motor Rail Fan MotorRemoval and Replacement of Door Gasket Door Re-Hinging and Drawer ConversionCleaning and Maintenance Instructions Work SurfaceRail and Rail Cover ExteriorCabinet Interior Door/Drawer GasketsMaintenance Power Supply ConnectionRail Condensate Pan Air FilterShutdown and Long Storage Refrigeration Circuit VI. Technical Information HPR100A-DWiring Diagrams HPR46A-D2a. HPR72A-D Auxiliary Code U-5 and Earlier 2b. HPR72A-D Auxiliary Code U-6 and Later Awaiting Data