Page 28

2. Low Temperature Alarm (E2)

If the cabinet or rail temperature drops below the setpoint temperature by 9°F (5°C) or more for more than y hours, "E2" is displayed. The default value of y is "1" (1 hour). The value of y can be changed under "F4" on the service menu. (0=No delay; 1=1 hour)

Note:

The low temperature alarm timer starts once the cabinet temperature drops 9°F

(5°C) below the setpoint temperature.

The low temperature alarm feature operates even during defrost.

Reset Options

The alarm will automatically reset once the area temperature reaches the upper setpoint temperature differential.

Possible Causes (for further details see "III.B. Service Chart")

Ambient temperature is low.

Trouble with the cabinet thermistor (black).

Liquid line valve open.

Evaporator fans not operating.

Power On

Setpoint Temperature and

Upper Setpoint Differential 0°F (0°C)

Lower Setpoint Temperature

Differential -3.6°F (2°C)

E2 Alarm Temperature

9°F (5°C) below setpoint temp.

E2 Alarm Timer under 1 hour

E2 Alarm

Timer Reset

Temperature Display

E2 Alarm Reset

E2 Alarm

E2 Alarm Timer over 1 hour

E2

Blinking

28

Image 28
Contents Superior Degree Reliability Number Issued Revised Hoshizaki AMERICA, INC Contents Page Page Important Safety Information Serious injuryIndicates important information about the use and care UnitSpecifications Nameplate Ratings DimensionsII. General Information Construction Power Switch ON, Rail Cooling Switch Normal or LOW Power Switch ON, Rail Cooling Switch OFFSequence of Operation Cool Down Restart Cabinet DefrostCabinet Defrost Power Switch ON, Rail Cooling Switch OFF Rail DefrostPower Switch ON, Rail Cooling Switch OFF Cabinet OperationPower Switch ON, Rail Cooling Switch Normal or LOW Position Rail CoolingCabinet and Rail Cooling Control Board Control Board LocationFront Rear Control Board LayoutLED Display and Service Lock-Out Alarm SignalService Menu Compressor Short Cycle ProtectionSwitch Settings Controls and AdjustmentsTemperature Display Energy Saving Mode Temperature SetpointCabinet Defrost Temperature Correction Factor Service Menu Service Menu AccessService Menu Chart Control Board Check Procedure Alarm SignalsControl Board Replacement Perimeter Heater Thermistor CheckCompressor Protector III. Service Diagnosis Alarm SignalsAlarm Priority Problem Reset, Corrections, and Adjustments High Temperature Alarm E1 Reset OptionsLow Temperature Alarm E2 Cabinet Defrost Alarm E3 High Condenser Temperature Alarm clogged filter E7 Possible Causes Defrost Thermistor cabinet Malfunction Alarm E85a. Secondary Defrost Thermistor Rail, not used Condenser Thermistor Malfunction Alarm E9 Control Board Alarms EA and ED Service ChartNo Operation Cabinet Cooling Problem Possible Cause Remedy Rail Cooling Cabinet Defrost Other Service for Refrigerant Lines IV. Removal and Replacement of ComponentsRefrigerant Recovery Brazing Evacuation and Recharge R-404APage Removal and Replacement of Refrigeration System Cartridge Refrigerant Recovery ProcedurePage Refrigeration System Pump‑Down Procedure Page Defrost Thermistor Rail Thermistor Removal and Replacement of Compressor Removal and Replacement of Cabinet Evaporator Removal and Replacement of Expansion Valve Removal and Replacement of Liquid Line Valve Removal and Replacement of Condenser Cabinet Thermistor Removal and Replacement of Thermistors and ThermostatDefrost Thermistor Defrost Thermostat Rail ThermistorRemoval and Replacement of Defrost Heater Condenser Thermistor clogged filterRemoval and Replacement of Fan Motors Cabinet Fan MotorCondenser Fan Motor Rail Fan MotorRemoval and Replacement of Door Gasket Door Re-Hinging and Drawer ConversionCleaning and Maintenance Instructions Work SurfaceRail and Rail Cover ExteriorCabinet Interior Door/Drawer GasketsMaintenance Power Supply ConnectionRail Condensate Pan Air FilterShutdown and Long Storage Refrigeration Circuit VI. Technical Information HPR100A-DWiring Diagrams HPR46A-D2a. HPR72A-D Auxiliary Code U-5 and Earlier 2b. HPR72A-D Auxiliary Code U-6 and Later Awaiting Data