Hoshizaki 73168 service manual High Condenser Temperature Alarm clogged filter E7

Page 30

4. High Condenser Temperature Alarm (clogged filter) (E7)

The unit is equipped with a condenser air filter to protect the condenser from dirt, grease, etc. The condenser air filter promotes clean condenser surfaces and efficient operation and should be checked twice monthly and cleaned when necessary. The unit is also equipped with a condenser thermistor to determine if the condenser or condenser air filter is excessively dirty. If the condenser thermistor detects a temperature that exceeds the preset temperature value (136.4°F (58°C)) for over 2 minutes, "E7" will be displayed.

CAUTION

Failure to take action when this alarm activates could result in damage to the compressor.

Reset Options

After cleaning the filter, the alarm will automatically reset once the temperature at the condenser outlet drops below 136.4°F (58°C).

Possible Causes (for further details see "III.B. Service Chart")

The condenser or condenser air filter is dirty.

The condenser fan motor is not functioning.

Note: If the power is turned off and then back on while the alarm signal is displayed, the alarm may be reset even if the condenser or condenser air filter has not been cleaned. However, the alarm will repeat once the compressor discharge temperature reaches 136.4°F (58°C).

 

E7 Alarm Timer Start

2 min

 

 

High

 

E7 Alarm

 

 

Reset

E7 Alarm Temp.

 

 

136.4°F (58°C)

 

 

 

 

E7 Alarm

Low

Temperature Display

E7 Alternating

 

 

 

with Temperature

30

Image 30
Contents Superior Degree Reliability Number Issued Revised Hoshizaki AMERICA, INC Contents Page Page Indicates important information about the use and care Important Safety InformationSerious injury UnitSpecifications Nameplate Ratings DimensionsII. General Information Construction Power Switch ON, Rail Cooling Switch OFF Power Switch ON, Rail Cooling Switch Normal or LOWSequence of Operation Cool Down Restart Cabinet DefrostCabinet Defrost Power Switch ON, Rail Cooling Switch OFF Rail DefrostPower Switch ON, Rail Cooling Switch OFF Cabinet OperationPower Switch ON, Rail Cooling Switch Normal or LOW Position Rail CoolingCabinet and Rail Cooling Control Board Control Board LocationFront Rear Control Board LayoutService Menu LED Display and Service Lock-OutAlarm Signal Compressor Short Cycle ProtectionControls and Adjustments Switch SettingsTemperature Display Temperature Setpoint Energy Saving ModeCabinet Defrost Temperature Correction Factor Service Menu Service Menu AccessService Menu Chart Alarm Signals Control Board Check ProcedureControl Board Replacement Thermistor Check Perimeter HeaterCompressor Protector III. Service Diagnosis Alarm SignalsAlarm Priority Problem Reset, Corrections, and Adjustments High Temperature Alarm E1 Reset OptionsLow Temperature Alarm E2 Cabinet Defrost Alarm E3 High Condenser Temperature Alarm clogged filter E7 Defrost Thermistor cabinet Malfunction Alarm E8 Possible Causes5a. Secondary Defrost Thermistor Rail, not used Condenser Thermistor Malfunction Alarm E9 Service Chart Control Board Alarms EA and EDNo Operation Cabinet Cooling Problem Possible Cause Remedy Rail Cooling Cabinet Defrost Other IV. Removal and Replacement of Components Service for Refrigerant LinesRefrigerant Recovery Brazing Evacuation and Recharge R-404APage Removal and Replacement of Refrigeration System Cartridge Refrigerant Recovery ProcedurePage Refrigeration System Pump‑Down Procedure Page Defrost Thermistor Rail Thermistor Removal and Replacement of Compressor Removal and Replacement of Cabinet Evaporator Removal and Replacement of Expansion Valve Removal and Replacement of Liquid Line Valve Removal and Replacement of Condenser Removal and Replacement of Thermistors and Thermostat Cabinet ThermistorDefrost Thermistor Defrost Thermostat Rail ThermistorRemoval and Replacement of Defrost Heater Condenser Thermistor clogged filterRemoval and Replacement of Fan Motors Cabinet Fan MotorCondenser Fan Motor Rail Fan MotorRemoval and Replacement of Door Gasket Door Re-Hinging and Drawer ConversionCleaning and Maintenance Instructions Work SurfaceCabinet Interior Rail and Rail CoverExterior Door/Drawer GasketsRail Condensate Pan MaintenancePower Supply Connection Air FilterShutdown and Long Storage Refrigeration Circuit VI. Technical Information HPR100A-DWiring Diagrams HPR46A-D2a. HPR72A-D Auxiliary Code U-5 and Earlier 2b. HPR72A-D Auxiliary Code U-6 and Later Awaiting Data