Hoshizaki KM-630MAH, KM-630MWH, KM-630MRH service manual Setting Time

Page 23

2) Defrost Timer

No adjustment is required under normal use, as the Defrost Timer is adjusted to the suitable position. However, if necessary when all the ice formed on the Evaporator does not fall into the bin in the harvest cycle, adjust the Defrost Timer to longer setting by adjusting the Dip Switch (No. 1 & 2) on the Controller Board.

SETTING

 

TIME

Dip Switch

Dip Switch

 

No. 1

 

No. 2

 

OFF

 

OFF

60 seconds

ON

 

OFF

90 seconds

OFF

 

ON

120 seconds

ON

 

ON

180 seconds

3) Drain Timer

The Drain Timer is factory-adjusted, and no adjustment is required.

SETTING

 

TIME

Dip Switch

Dip Switch

 

 

No. 3

No. 4

T1

T2

OFF

OFF

10 seconds

150 seconds

ON

OFF

10 seconds

180 seconds

OFF

ON

10 seconds

120 seconds

ON

ON

20 seconds

180 seconds

T1: Time to drain the Water Tank

T2: Time to restrain defrost completion

4) Drain Counter

CAUTION

Do not adjust the Drain Counter, or the Evaporator may freeze up.

The Drain Counter is factory-adjusted to drain the Water Tank every 10 cycles, and no adjustment is required. However, where water quality is bad and the icemaker needs a pump drain more often, the Drain Counter can be adjusted as shown in the table below:

23

Image 23
Contents KM-630MAH KM-630MWH KM-630MRH Hoshizaki AMERICA, INC Contents Maintenance Water TEMP. F Specifications KM-630MAH2a. KM-630MWH Serial #L00001D M20270B 2b. KM-630MWH Serial #M20301E KM-630MRH URC-6F Condenser UnitSpecifications KM-630MAH II. General Information ConstructionKM-630MWH KM-630MRH Controller Board Features of Control Products E Controller BoardController Board SOLID-STATE ControlPage Freeze Cycle Beep every 3 sec. = High Evaporator Temperature 127 FMinute Fill Cycle Harvest CycleControl Products HOS-001A Board Important Water Valve opening is limited to 6 minutes Sequence 1st Cycle2nd Cycle and after with pump drain 2nd Cycle and after with no pump drain For Models with Thermostat Controls and AdjustmentsPage Setting Time Models with Thermostat Checking the Controller Board Models with Mechanical BIN ControlExplanation of Operation Proximity SwitchMechanical BIN Control Troubleshooting Mechanical BIN Control only KM-630MAH KM-630MWH KM-630MRH Wiring Diagrams Page B1 KM-630MRH with auxiliary codes L-0, M-0, M-1 B2 KM-630MRH with auxiliary codes M-2 and after Timing Chart Page 157 Performance DataPressure Drop of Cooling Water Line B1 KM-630MWH Serial #L00001D M20270BB2 KM-630MWH Serial #M20301E 603 Problem Possible Cause Remedy IV. Service Diagnosis 1. no ICE ProductionController Board Problem Possible Cause Remedy Thermistor Evaporator is Frozen UPOthers LOW ICE ProductionAbnormal ICE Evacuation and Recharge R-404A Removal and Replacement of ComponentsService for Refrigerant Lines Refrigerant RecoveryBrazing Removal and Replacement of Compressor Important Page Removal and Replacement of Expansion Valve Removal and Replacement of DrierRemoval and Replacement of HOT GAS Valve and Line Valve Page Removal and Replacement of Evaporator Important Page Adjustment of Water Regulating Valve WATER-COOLED Model only Page Removal and Replacement of Thermistor Caution Removal and Replacement of FAN Motor Removal and Replacement of Pump Motor Removal and Replacement of Water ValveRemoval and Replacement of Spray Tubes Preparing the Icemaker for Long Storage VI. Cleaning and Maintenance InstructionsPage Cleaning and Sanitizing Procedures Cleaning Procedure Page Sanitizing Procedure Maintenance