Hoshizaki KM-630MWH, KM-630MRH, KM-630MAH service manual

Page 54

8.REMOVAL AND REPLACEMENT OF WATER REGULATING VALVE - WATER-COOLED MODEL ONLY

IMPORTANT

Always install a new Drier every time the sealed refrigeration system is opened. Do not replace the Drier until after all other repair or replacement has been made.

1)Turn off the power supply.

2)Close the Water Supply Line Shut-off Valve.

3)Remove the panels.

4)Recover the refrigerant and store it in an approved container.

5)Disconnect the Capillary Tube at the Condenser outlet using brazing equipment.

6)Disconnect the Flare-connections of the valve.

7)Remove the screws and the valve from the Bracket.

8)Install the new valve, and braze the Capillary Tube.

9)Install the new Drier.

10)Check for leaks using nitrogen gas (140 PSIG) and soap bubbles.

11)Evacuate the system, and charge it with refrigerant. See the Nameplate for the required refrigerant charge.

12)Connect the Flare-connections.

13)Open the Water Supply Line Shut-off Valve.

14)Check for water leaks.

15)Replace the panels in their correct positions.

16)Turn on the power supply.

54

Image 54
Contents KM-630MAH KM-630MWH KM-630MRH Hoshizaki AMERICA, INC Contents Maintenance Specifications KM-630MAH Water TEMP. F2a. KM-630MWH Serial #L00001D M20270B 2b. KM-630MWH Serial #M20301E KM-630MRH Condenser Unit URC-6FSpecifications II. General Information Construction KM-630MAHKM-630MWH KM-630MRH SOLID-STATE Control Features of Control Products E Controller BoardController Board Controller BoardPage Harvest Cycle Beep every 3 sec. = High Evaporator Temperature 127 FMinute Fill Cycle Freeze CycleControl Products HOS-001A Board Sequence 1st Cycle Important Water Valve opening is limited to 6 minutes2nd Cycle and after with pump drain 2nd Cycle and after with no pump drain Controls and Adjustments For Models with ThermostatPage Setting Time Models with Thermostat Models with Mechanical BIN Control Checking the Controller BoardProximity Switch Mechanical BIN ControlExplanation of Operation Troubleshooting Mechanical BIN Control only KM-630MAH KM-630MWH KM-630MRH Wiring Diagrams Page B1 KM-630MRH with auxiliary codes L-0, M-0, M-1 B2 KM-630MRH with auxiliary codes M-2 and after Timing Chart Page Performance Data 157B1 KM-630MWH Serial #L00001D M20270B Pressure Drop of Cooling Water LineB2 KM-630MWH Serial #M20301E 603 IV. Service Diagnosis 1. no ICE Production Problem Possible Cause RemedyController Board Problem Possible Cause Remedy Evaporator is Frozen UP ThermistorLOW ICE Production Abnormal ICEOthers Refrigerant Recovery Removal and Replacement of ComponentsService for Refrigerant Lines Evacuation and Recharge R-404ABrazing Removal and Replacement of Compressor Important Page Removal and Replacement of Drier Removal and Replacement of Expansion ValveRemoval and Replacement of HOT GAS Valve and Line Valve Page Removal and Replacement of Evaporator Important Page Adjustment of Water Regulating Valve WATER-COOLED Model only Page Removal and Replacement of Thermistor Caution Removal and Replacement of FAN Motor Removal and Replacement of Water Valve Removal and Replacement of Pump MotorRemoval and Replacement of Spray Tubes VI. Cleaning and Maintenance Instructions Preparing the Icemaker for Long StoragePage Cleaning and Sanitizing Procedures Cleaning Procedure Page Sanitizing Procedure Maintenance