10.REMOVAL AND REPLACEMENT OF CONDENSING PRESSURE REGULATOR (C.P.R.) - REMOTE AIR-COOLED MODEL ONLY

IMPORTANT

Always install a new Drier every time the sealed refrigeration system is opened. Do not replace the Drier until after all other repair or replacement has been made.

1)Turn off the power supply.

2)Remove the panels from the remote condenser unit.

3)Recover the refrigerant and store it in an approved container.

4)Before heating, break off the stub on the dome to release the dome charge.

5)Disconnect the C.P.R. using brazing equipment.

6)Install the new C.P.R. Use nitrogen gas at the pressure of 3 - 4 PSIG when brazing the C.P.R.

WARNING

Always protect the C.P.R. body by using a damp cloth to prevent the C.P.R. from overheating. Do not braze with the C.P.R. body exceeding 250° F.

7)Install the new Drier in the icemaker.

8)Check for leaks using nitrogen gas (140 PSIG) and soap bubbles.

9)Evacuate the system and charge it with refrigerant. See the Charge Label in the machine compartment in the icemaker.

10)Replace the panels in their correct positions.

11)Turn on the power supply.

56

Image 56
Contents KM-630MAH KM-630MWH KM-630MRH Hoshizaki AMERICA, INC Contents Maintenance Specifications KM-630MAH Water TEMP. F2a. KM-630MWH Serial #L00001D M20270B 2b. KM-630MWH Serial #M20301E KM-630MRH Condenser Unit URC-6FSpecifications II. General Information Construction KM-630MAHKM-630MWH KM-630MRH Features of Control Products E Controller Board Controller BoardSOLID-STATE Control Controller BoardPage Beep every 3 sec. = High Evaporator Temperature 127 F Minute Fill CycleHarvest Cycle Freeze CycleControl Products HOS-001A Board Sequence 1st Cycle Important Water Valve opening is limited to 6 minutes2nd Cycle and after with pump drain 2nd Cycle and after with no pump drain Controls and Adjustments For Models with ThermostatPage Setting Time Models with Thermostat Models with Mechanical BIN Control Checking the Controller BoardExplanation of Operation Proximity SwitchMechanical BIN Control Troubleshooting Mechanical BIN Control only KM-630MAH KM-630MWH KM-630MRH Wiring Diagrams Page B1 KM-630MRH with auxiliary codes L-0, M-0, M-1 B2 KM-630MRH with auxiliary codes M-2 and after Timing Chart Page Performance Data 157B1 KM-630MWH Serial #L00001D M20270B Pressure Drop of Cooling Water LineB2 KM-630MWH Serial #M20301E 603 IV. Service Diagnosis 1. no ICE Production Problem Possible Cause RemedyController Board Problem Possible Cause Remedy Evaporator is Frozen UP ThermistorOthers LOW ICE ProductionAbnormal ICE Removal and Replacement of Components Service for Refrigerant LinesRefrigerant Recovery Evacuation and Recharge R-404ABrazing Removal and Replacement of Compressor Important Page Removal and Replacement of Drier Removal and Replacement of Expansion ValveRemoval and Replacement of HOT GAS Valve and Line Valve Page Removal and Replacement of Evaporator Important Page Adjustment of Water Regulating Valve WATER-COOLED Model only Page Removal and Replacement of Thermistor Caution Removal and Replacement of FAN Motor Removal and Replacement of Water Valve Removal and Replacement of Pump MotorRemoval and Replacement of Spray Tubes VI. Cleaning and Maintenance Instructions Preparing the Icemaker for Long StoragePage Cleaning and Sanitizing Procedures Cleaning Procedure Page Sanitizing Procedure Maintenance