9.ADJUSTMENT OF WATER REGULATING VALVE - WATER-COOLED MODEL ONLY

The Water Regulating Valve (also called “WATER REGULATOR”) is factory-adjusted. No adjustment is required under normal use. Adjust the Water Regulator, if necessary, using the following procedures.

1)Attach a pressure gauge to the high-side line of the system. Or prepare a thermometer to check for the condenser drain temperature.

2)Rotate the adjustment screw by using a flat blade screwdriver, so that the pressure gauge shows the temperature specified in the table, 5 minutes after a freeze cycle or icemaking process starts. When the pressure exceeds 270 PSIG, or the condenser drain temperature exceeds the temperature range, rotate the adjustment screw counterclockwise. See Fig. 1.

3)Check that the pressure or the condenser drain temperature holds a stable setting.

Fig. 1

55

Image 55
Contents KM-630MAH KM-630MWH KM-630MRH Hoshizaki AMERICA, INC Contents Maintenance Water TEMP. F Specifications KM-630MAH2a. KM-630MWH Serial #L00001D M20270B 2b. KM-630MWH Serial #M20301E KM-630MRH URC-6F Condenser UnitSpecifications KM-630MAH II. General Information ConstructionKM-630MWH KM-630MRH Controller Board Features of Control Products E Controller BoardController Board SOLID-STATE ControlPage Freeze Cycle Beep every 3 sec. = High Evaporator Temperature 127 FMinute Fill Cycle Harvest CycleControl Products HOS-001A Board Important Water Valve opening is limited to 6 minutes Sequence 1st Cycle2nd Cycle and after with pump drain 2nd Cycle and after with no pump drain For Models with Thermostat Controls and AdjustmentsPage Setting Time Models with Thermostat Checking the Controller Board Models with Mechanical BIN ControlMechanical BIN Control Proximity SwitchExplanation of Operation Troubleshooting Mechanical BIN Control only KM-630MAH KM-630MWH KM-630MRH Wiring Diagrams Page B1 KM-630MRH with auxiliary codes L-0, M-0, M-1 B2 KM-630MRH with auxiliary codes M-2 and after Timing Chart Page 157 Performance DataPressure Drop of Cooling Water Line B1 KM-630MWH Serial #L00001D M20270BB2 KM-630MWH Serial #M20301E 603 Problem Possible Cause Remedy IV. Service Diagnosis 1. no ICE ProductionController Board Problem Possible Cause Remedy Thermistor Evaporator is Frozen UPAbnormal ICE LOW ICE ProductionOthers Evacuation and Recharge R-404A Removal and Replacement of ComponentsService for Refrigerant Lines Refrigerant RecoveryBrazing Removal and Replacement of Compressor Important Page Removal and Replacement of Expansion Valve Removal and Replacement of DrierRemoval and Replacement of HOT GAS Valve and Line Valve Page Removal and Replacement of Evaporator Important Page Adjustment of Water Regulating Valve WATER-COOLED Model only Page Removal and Replacement of Thermistor Caution Removal and Replacement of FAN Motor Removal and Replacement of Pump Motor Removal and Replacement of Water ValveRemoval and Replacement of Spray Tubes Preparing the Icemaker for Long Storage VI. Cleaning and Maintenance InstructionsPage Cleaning and Sanitizing Procedures Cleaning Procedure Page Sanitizing Procedure Maintenance