Switch Nos. 9 and 10:
Used for adjustment of Freeze Timer. The Freeze Timer determines maximum freeze cycle time. Upon termination of Freeze Timer, machine initiates the harvest cycle. After 2 consecutive timer terminations, machine will shut down, possibly indicating a problem.
1) Defrost Control
A thermistor (Semiconductor) is used for a defrost control sensor. The resistance varies depending on the Suction Line temperatures. The Thermistor detects the temperature of the Evaporator outlet to start the Defrost Timer. No adjustment is required. If necessary, check for resistance between Thermistor leads, and visually check the Thermistor mounting, located on the Suction Line next to the Evaporator outlet.
Temperature (°F) | Resistance (kΩ ) |
0 | 14.401 |
10 | 10.613 |
32 | 6.000 |
50 | 3.871 |
70 | 2.474 |
90 | 1.633 |
Check a thermistor for resistance by using the following procedures.
(i)Disconnect the connector K3 on the board.
(ii)Remove the Thermistor. See “V. 11. REMOVAL AND REPLACEMENT OF THERMISTOR.”
(iii)Immerse the Thermistor sensor portion in a glass containing ice and water for 2 or 3 minutes.
(iv)Check for a resistance between Thermistor leads.
Normal reading is within 3.5 to 7 kΩ . Replace the Thermistor if it exceeds the normal reading.
22