AC INVERTER PROGRAMMING INSTRUCTIONS
The WFC Series AC Inverters come wired for external use and must be installed for use in a side panel control (See WIRING DIAGRAMS). Refer to owners manual for complete instructions and explanations. Manual used for the following was FORM 1094.
After installation is complete the inverter must be reprogrammed to Cleveland's modifications of the factory settings. All modifications are achieved in Access Level 2.
1.Turn agitator power on. The top four LED indicators will illuminate momentarily - wait for the three green LED's to go out before proceeding.
2.Press the PROGram and SHIFT keys simultaneously to reach Access Level 2. The display display will now read:
3.Use the UP/DOWN arrow keys to select the program parameter for change.
4.Press the SHIFT key. The program number will blink indicating that that the data value may be changed.
5.Use the UP/DOWN arrow keys to select the new data code.
6.Press the ENTER key. The display will indicate **STORED** for one second, then revert to the normal parameter display.
7.Press the PROGram key to exit the programming mode or the UP/DOWN keys to select an new parameter for change.
PROGRAM CODE SUMMARY:
# | Name | Description | Data Range | Factory Setting | Units | Access Level | Customer Setting |
01 | MODEL | Model Number | Note 1 | 1 |
| ||
|
|
|
|
|
|
|
|
02 | RVLVL | Software Revision | Note 1 | 2 |
| ||
|
|
|
|
|
|
|
|
03 | IRAT | Rated Current | Note 1 | A | 2 |
| |
|
|
|
|
|
|
|
|
05 | SERNO | Serial Number | 2 |
| |||
|
|
|
|
|
|
|
|
06 | REP | Repair Date | 2 |
| |||
|
|
|
|
|
|
|
|
07 | FLT3 | Last Fault | 1 |
| |||
|
|
|
|
|
|
|
|
08 | FLT2 | 2nd Fault | 2 |
| |||
|
|
|
|
|
|
|
|
09 | FLT1 | 1st Fault | 2 |
| |||
|
|
|
|
|
|
|
|
12 | FOUT | Output Frequency | Hz | 1 |
| ||
|
|
|
|
|
|
|
|
13 | VOUT | Output Voltage | % | 1 |
| ||
|
|
|
|
|
|
|
|
14 | IOUT | Output Current | A | 1 |
| ||
|
|
|
|
|
|
|
|
15 | LOAD | Drive Load | % | 1 |
| ||
|
|
|
|
|
|
|
|
16 | TORQ | Load Torque | % | 1 |
| ||
|
|
|
|
|
|
|
|
17 | TEMP | Inverter Temp | C | 1 |
| ||
|
|
|
|
|
|
|
|
18 | TIME1 | Total Run Time | h | 2 |
| ||
|
|
|
|
|
|
|
|
19 | TIME2 | Power On Hours | h | 2 |
| ||
|
|
|
|
|
|
|
|
21 | MODE | Input Mode | 0 | 1 | 4 | ||
|
|
|
|
|
|
|
|
24 | FSEL | Reference Select | 0 | 2 |
| ||
|
|
|
|
|
|
|
|
27 | TLSEL | Torque Limit Select | 0 | 2 |
| ||
|
|
|
|
|
|
|
|
31 | FMIN | Min. Frequency | 0 | Hz | 1 | 14 | |
|
|
|
|
|
|
|
|
32 | FMAX | Max. Frequency | 60 | Hz | 1 | 70 | |
|
|
|
|
|
|
|
|
33 | F2 | Preset Speed #2 - Jog | 5 | Hz | 1 |
| |
|
|
|
|
|
|
|
|
34 | F3 | Preset Speed #3 | 20 | Hz | 2 |
| |
|
|
|
|
|
|
|
|
35 | F4 | Preset Speed #4 | 40 | Hz | 2 |
| |
|
|
|
|
|
|
|
|
36 | F5 | Preset Speed #5 | 60 | Hz | 2 |
| |
|
|
|
|
|
|
|
|
37 | F6 | Preset Speed #6 | 0 | Hz | 2 |
| |
|
|
|
|
|
|
|
|
38 | F7 | Preset Speed #7 | 0 | Hz | 2 |
| |
|
|
|
|
|
|
|
|
39 | FTL | Min. Frequency in Torque Limit | 10 | Hz | 2 |
| |
|
|
|
|
|
|
|
|
41 | RSEL | Ramp Selector | 0 | 2 |
|
42 ACC1 | Acceleration Time #1 | 3 | s | 1 | 9 |