Carrier XRV, 19XR specifications VFD Title Setting Parameter, Description Settings

Page 59

VFD Cooling System Leak Inspection

1.Check for leaks on the refrigerant cooling flange connec- tions to the VFD enclosure.

2.Check for leaks on all tubing internal to the VFD enclo- sure, the tubing flair connection to the VFD module and the TXV valve.

3.Verify that the VFD refrigerant cooling system TXV valve control bulb is securely inserted into the VFD drive module heat sink.

Power Up Verification

1.Inspect control wiring inside the VFD and verify the in- tegrity of the connections between the integrated starter module (ISM) and the VFD module.

2.Close the control power switch in the VFD enclosure.

3.Close the oil pump power switch inside the VFD enclosure.

4.Verify the VFD disconnect switch is in the open position.

5.Close and latch the doors of the VFD enclosure.

6.Apply power to the VFD enclosure. Remove lock outs and close all disconnects.

7.Verify that the CVC/ICVC display powers up and goes to the default screen.

8.Close the VFD disconnect switch.

9.Verify the following actions during the VFD start-up self test:

The display shows SELF and all LEDs are illumi- nated for 5 to 6 seconds.

The display reads a 0 after the diagnosis is complete.

If Err is displayed a fault has been detected. Perform manual reset by establishing a reset through the small hole under the VFD Keypad. If this does not correct the fault contact your Carrier representative.

If AR with a counting down number is displayed wait for the number to count to 0 and the display should then revert to a 0. If the counter starts over at 30 contact Carrier representative.

Configure VFD Parameters — The VFD controller must have job specific parameters set as defined by the component name- plates and labels. The parameters come preset by the factory, but must be verified prior to start-up by accessing the PRO- GRAM MODE of the VFD controller keypad. For information on how to access the VFD keypad see page 58.

Press the PROGRAM softkey to access the parameter screen to modify or view the following job specific parameters:.

VFD

TITLE

SETTING

PARAMETER

 

 

P.004

Maximum

Line Frequency selected. Per

 

Speed

Compressor Nameplate.

P.006

Password

107

P.028

Speed

60 for 60 Hz selection and

 

Display

50 for 50 Hz selection

 

Scaling

 

H.000

Motor

Compressor nameplate voltage.

 

Voltage

 

H.001

Frequency

Line Frequency selected. Per

 

 

Compressor Nameplate.

H.002

Motor

Compressor nameplate amps.

 

Amps

 

H.021

Line

VFD nameplate voltage.

 

Voltage

 

H.022

Over

69 for 60 Hz selection and

 

Frequency

57 for 50 Hz selection.

 

Limit

 

Configure Chiller Visual Controller Parameter — The chiller controller must have its job specific parameters set as defined by the job sheet or installed nameplates. Below are the job spe- cific parameters that must be set:

To access the ISM_CONF screen:

1.Press ENTER .

2.Press SERVICE .

3.Enter the password 1111.

4.Select ISM (CONFIG STARTER DATA)

5.Scroll down and select the ISM_CONF DATA screen to modify or view the ISM parameters:

DESCRIPTION

SETTING

STARTER TYPE

2

(2 = SS/VFD)

 

MOTOR RATED

VFD Nameplate Voltage.

LINE VOLTAGE

 

MOTOR RATED

VFD Nameplate Chiller Rated Load

LOAD AMPS

Amps

MOTOR LOCKED

Compressor Nameplate

ROTOR TRIP

 

STARTER LRA RATING

600 for VFD

 

part #19XVR0414XXX

 

700 for VFD

 

part #19XVR0500XXX

 

900 for VFD

 

part #19XVR0643XXX

MOTOR CURRENT

163

CT RATIO:1

120 (414A)

3 GRND FAULT CT?

NO

(1=NO)

 

FREQUENCY-60HZ

NO for 50 Hz selection

(NO=50)

YES for 60 Hz selection

6.Press to the SAVE softkey to save changes.

7.Press the EXIT softkey to and exit the ISM Configura- tion Screen.

VFD Enable Configuration — To access the parameters:

1.Press MENU .

2.Press SERVICE .

3.Select EQUIPMENT SERVICE.

4.Scroll down and select SETUP2.

5.Verify the following parameters:

VFD OPTION

ENABLED

VFD CURRENT LIMIT

COMPRESSOR NAMEPLATE AMPS

Configure Surge Parameters

1.Press MENU .

2.Press SERVICE .

3.Select EQUIPMENT SERVICE and OPTIONS to verify the following:

DESCRIPTION

SETTINGS

SURGE/HGBP

Surge parameter label

DELTA T1

 

SURGE/HGBP

Surge parameter label

DELTA P1

 

SURGE/HGBP

Surge parameter label

DELTA T2

 

SURGE/HGBP

Surge parameter label

DELTA P2

 

VFD CONTROL VERFICATION (Non-Running) — In order to verify and, if necessary, tune the speed control signal of the chiller controller to the VFD (ISM terminal J8 1-2 labeled 4-20 mA OUT VFD) and the speed feedback signal from the VFD to the chiller controller (ISM terminal J6 1-2 labeled VFD HZ), follow the steps below.

Set TARGET VFD SPEED to 0%.

1. Press MENU .

59

Image 59
Contents Safety Considerations Start-Up, Operation, and Maintenance InstructionsContents Contents Abbreviations and Explanations Introduction19XR Identification Chiller FamiliarizationTypical 19XR Components Motor and Lubricating OIL Cooling Cycle Refrigeration CycleLubrication Cycle VFD Cooling CycleUnit-Mounted Solid-State Starter Optional Starting EquipmentDefinitions Unit-Mounted Wye-Delta Starter OptionalControls Variable Frequency Drive VFD 19XR Controls and Sensor Locations PIC II Component Panel Location Major PIC II Components Panel LocationsControl Panel CVC/ICVC Operation and Menus Fig Example of Status Screen 19XR Chiller Display Menu Structure CVC/ICVC 19XR Service Menu Structure Time and Date Example of Time Schedule Operation Screen Example of Set Point Screen CVC/ICVC Display Data Example 1 Chiller Display Default ScreenStartup Description Status Units Point Example 2 Maintstat Display ScreenDescription Status Units Point Example 3 Startup Display ScreenExample 5 Heatex Display Screen Example 4 Compress Display ScreenExample 7 Ismstat Display Screen Example 6 Power Display ScreenExample 9 Setpoint Display Screen Menu Setpoint Select Description Status Units Point DefaultExample 8 CVC/ICVCPSWD Display Screen CVC Icvc Description Status Units PointExample 12 Llmaint Display Screen Example 11 Override Display ScreenControl Algorithm Status Override Description Units Point Control Algorithm Status Wsmdefme Description Units Point Example 13 Ismhist Display ScreenExample 14 Wsmdefme Display Screen Example 16 Ismconf Display Screen ISM Starter Config DataIsmconf Description Status Units Point Default Example 15 Netopt Display ScreenExample 17 Options Display Screen Example 18 SETUP1 Display ScreenSpare ALERT/ALARM Enable LAG=2, STANDBY=3 Example 19 SETUP2 Display ScreenExample 20 Leadlag Display Screen Example 22 Tempctl Display Screen Description Status Units Point DefaultReset Type Example 21 Rampdem Display ScreenPIC II System Functions Normal Control mode occurs when Active Delta TSurge Prevention Mode occurs when Active Delta T Mode IGV VFDPage Protective Safety Limits and Control Settings Page Capacity Overrides Evaporator Freeze Protection Icvc only a Page Head Pressure Reference Output Surge Protection Fixed Speed ChillerPage Page Point Example of Attach to Network Device Screen Example of Holiday Period Screen Local Start-Up Local start-up or a manual start-up is Default CVC/ICVC screen, press the MenuSTART-UP/SHUTDOWN Recycle Sequence FigEntering Condenser Water temperature plus 3 F -1.6C Equipment Required Before Initial START-UPJob Data Required 19XR Leak Test Procedures Page Page Temperature Pressure HFC-134a Pressure Temperature FHFC-134a Pressure Temperature C Perform dehydration as follows Inspect WiringWhite G Check StarterManufacturer Cable no Software Configuration Parameter Benshaw RediStart Micro Menu Items Verify VFD Configuration and Change Parameters if Necessary Description Settings VFD Title Setting ParameterDescription Setting Press Menu Press Status Press Compress Press Select Press Status Press Compress Press SelectLoad Surge Prevention Occurs TOO Soon Occurs TOO Late Estimated Minimum Load ConditionsCCM Temperature Thermistors Tests to be Devices Tested Performed Charge Refrigerant into ChillerControl Test Menu Functions Refrigerant HFC-134a Charge Initial START-UPCheck Oil Pressure and Compressor Stop Dry Run to Test Start-Up SequenceCheck Motor Rotation To Stop the Chiller Operating InstructionsOperator Duties To Start the ChillerOperating the Optional Pumpout Unit Pumpout and Refrigerant Transfer ProceduresFLA Date Cooler Condenser CompressorTime BearingValve Condition Turn off pumpout condenser waterChillers with Isolation Valves Test After Service, Repair, or Major Leak If General MaintenanceGuide Vane Actuator Linkage Weekly MaintenanceCheck Safety and Operating Controls Monthly Scheduled MaintenanceInspect the Heat Exchanger Tubes and Flow Devices Compressor Bearing and Gear MaintenanceOptional Pumpout System Controls Ordering Replacement Chiller Parts WhenChecking Pressure Transducers Troubleshooting GuideOccdefcm HeatexLlmaint Ready to Start Terminate Pumpdown ModeShutdown in Progress ICE BuildRunning Temp Control PrestartAlert Autorestart in ProgressSensor FaultRUN Capacity LimitedStop ProtectiveFailure to StartFREEZE-UP LossCommunication PotentialPending Sensor AlertLOW OIL Pressure AutorestartDiffuser Pressure AlertRecycle Option SensorDrop Thermistor Temperature F vs. Resistance/Voltage DropTemperature PIC Resistance Thermistor Temperature C vs. Resistance/Voltage DropControl Modules Power is connected to Plug J1 on each moduleReplacing Defective Processor Modules Chiller Control Module CCM FigIntegrated Starter Module Fig Integratedstartermodule Checked Measure SCR Pairs Recorded Being BetweenNumber of Tubes English Code Heat Exchanger Data EnglishNumber of Tubes Code Heat Exchanger Data SI19XR Additional Data for Marine Waterboxes Compressor WeightsEnglish Motor 19XR Motor Weights Standard and High Efficiency Motors19XR Waterbox Cover Weights English lb 19XR Waterbox Cover Weights SI kg Motor Voltage Code Additional Miscellaneous WeightsOptional Pumpout System Electrical Data Description Torque Compressor Assembly TorquesCompressor Code View B High Speed Shaft 19XR Compressor ClearancesAllen-Bradley Wye-Delta Unit-Mounted Starter 100101 ISM 102Temp 103104 105 106 107 Power Panel Wiring Schematic108 Cutler-Hammer Wye Delta Unit Mounted Starter Sizes 3-5DP109 Cutler-Hammer Wye Delta Unit Mounted Starter Size 6DPSeparate Metering Option Ground Fault Phase Current Option111 AUX 112FU Fuse 113114 VFD 115116 Typical Variable Frequency Drive VFD Wiring Schematic117 118 119 120 121 122 Index Index JOB Data Required Remove and use for job fileCL-2 Inspect Wiring and Record Electrical Data Ratings15 to 40 to 10010 to 60.0CL-4 85 to 200 to460 105 to 115CL-6 30 to50 to 20 to Psi125 to 150 to90 to 125Amp 250 CL-8 65 to90 to 100 CL-9 25 toCL-10 50 to 145CL-11 0000 to0200 0000 to 0200000 100 to Selected line voltage 002 Power Module Dependent Selected motor 100% amps004 To H.022 Job Sheet 60 for 60 Hz and 50 for 50 Hz 028 10 to Job Sheet 60 for 60 Hz and 50 for 50 HzCL-13 CL-14 CCN Local ResetPage Incurring obligations
Related manuals
Manual 40 pages 46.08 Kb

19XR, XRV specifications

The Carrier 19XR and 19XRV chillers are sophisticated cooling solutions that represent the forefront of HVAC technology. Designed for large commercial and industrial applications, these chillers provide exceptional performance, energy efficiency, and reliability, making them ideal for a variety of environments ranging from hospitals to manufacturing facilities.

One of the most significant features of the Carrier 19XR and 19XRV chillers is their advanced scroll compressor technology. These units employ a tandem scroll design that enhances efficiency while minimizing operational noise. This makes them ideal for urban environments where noise restrictions may be in place. Moreover, the compressors are equipped with variable speed drive options in the 19XRV model, which allows for greater energy savings by adjusting cooling output based on real-time demand.

In addition to their advanced compressors, the 19XR and 19XRV units incorporate the Carrier GreenChoice refrigerant, which has a lower global warming potential compared to traditional refrigerants. This innovative choice not only meets regulatory requirements but also contributes to sustainability goals, making these chillers a responsible choice for environmentally conscious organizations.

The units are engineered with a robust heat exchanger design, which enhances heat transfer efficiency and overall system performance. This ensures optimal operation even in extreme conditions. They feature a microprocessor-based control system that allows for precise monitoring and control of the chiller’s performance, enabling operators to make real-time adjustments to maximize energy efficiency.

The Carrier 19XR and 19XRV chillers also prioritize serviceability. The design incorporates easy access to key components, simplifying maintenance procedures and reducing downtime. This focus on maintainability extends the lifespan of the equipment, leading to lower lifecycle costs.

In terms of connectivity, these chillers are equipped with advanced Building Management System (BMS) integration capabilities. This allows for seamless monitoring and control of the chillers using a centralized platform, facilitating energy management and operational optimization.

Overall, the Carrier 19XR and 19XRV chillers stand out in the market for their blend of cutting-edge technology, energy efficiency, and user-friendly features. They are engineered to meet the demanding needs of modern commercial and industrial applications, making them a preferred choice for facility managers seeking reliable cooling solutions.