Carrier XRV, 19XR specifications Dry Run to Test Start-Up Sequence, Check Motor Rotation

Page 65

Dry Run to Test Start-Up Sequence

For electro-mechanical starters.

1.Disengage the main motor disconnect (CB1) on the start- er front panel. This should only disconnect the motor power. Power to the controls, oil pump, and starter con- trol circuit should still be energized.

2.Observe the default screen on the CVC/ICVC: the status message in the upper left-hand corner reads, “Manually Stopped,” Press the CCN or LOCAL softkey to start. If the chiller controls do not go into a start mode (“Unoc- cupied Mode” is displayed) go to the SCHEDULE screen and override the schedule or change the occupied time. Press the LOCAL softkey to begin the start-up sequences.

3.View the STARTUP display screen and verify the chilled water and condenser water pumps have energized.

4.Verify the oil pump has started and is pressurizing the lubrication system. After the oil pump has run about 11 seconds, the starter energizes (COMPRESSOR START CONTACT is closed) and goes through its start-up sequence.

5.Check the main contactor (1M) for proper operation.

6.The PIC II eventually shows an alarm for motors amps not sensed. Reset this alarm and continue with the initial start-up.

For Benshaw Inc. solid-state starters:

1.Close the main motor disconnect (CB1). Voltage will be applied to the compressor motor but the SCRs will not fire (compressor motor will not rotate). Enter MENU 4 in the Benshaw RediStart MICRO™ Menu structure at the Benshaw display (see Input Service Configurations, Change The Benshaw RediStart MICRO Software Con- figuration page 57). Select Dry Run Mode and scroll to YES.

2.Follow steps 2 through 4 for the electro-mechanical start- ers. When the Ramp Time is set for less than 10 seconds COMPRESSOR RUN CONTACT will close.

3.The PIC II eventually shows an alarm for motors amps not sensed. Reset this alarm and enter MENU 4 in the Benshaw display. Select Dry Run Mode and scroll to NO. Continue with the initial start-up.

Check Motor Rotation

1.Engage the oil pump circuit breaker (CB3) located inside the right hand side of the starter panel.

2.Then engage the control power circuit breaker (CB2) lo- cated in the same section of the starter cabinet.

3.Finally close the main motor disconnect (CB1) on the front of the starter panel.

4.The ISM mounted in the electro-mechanical starters checks for proper phase rotation as soon as power is applied to the starter and the PIC II controls power up. Solid-state starters have phase protection and do not per- mit a start if the phase rotation is not correct.

5.An alarm message will appear on the CVC/ICVC if the phase rotation is incorrect. If this occurs reverse any 2 of the 3 incoming power leads to the starter and reapply power. The motor is now ready for a rotation check.

6.After the default screen status message states ‘Ready to Start’ press the LOCAL softkey. The PIC II control per- forms start-up checks.

7.When the starter is energized and the motor begins to turn, check for clockwise motor rotation (Fig. 33).

Fig. 33 — Correct Motor Rotation

Do not check motor rotation during coastdown. Rotation may have reversed during equalization of vessel pressures.

Check Oil Pressure and Compressor Stop

1.When the motor is at full speed, note the differential oil pressure reading on the CVC/ICVC default screen. It should be between 18 and 30 psid (124 to 206 kPad).

2.Press the Stop button and listen for any unusual sounds from the compressor as it coasts to a stop.

To Prevent Accidental Start-UpA chiller STOP override setting may be entered to prevent accidental start-up during service or whenever necessary. Access the MAINSTAT

screen and using the NEXT or PREVIOUS softkeys, high- light the CHILLER START/STOP parameter. Override the cur-

rent START value by pressing the SELECT softkey. Press the STOP softkey followed by the ENTER softkey. The word SUPVSR! displays on the CVC/ICVC indicating the override is in place.

To restart the chiller the STOP override setting must be re- moved. Access the MAINSTAT screen and using NEXT or PREVIOUS softkeys highlight CHILLER START/STOP. The

3 softkeys that appear represent 3 choices:

START — forces the chiller ON

STOP — forces the chiller OFF

RELEASE — puts the chiller under remote or schedule control.

To return the chiller to normal control, press the

RELEASE softkey followed by the ENTER softkey. For more information, see Local Start-Up, page 46.

The default CVC/ICVC screen message line indicates which command is in effect.

Check Chiller Operating Condition — Check to be sure that chiller temperatures, pressures, water flows, and oil and refrigerant levels indicate the system is functioning properly.

Instruct the Customer Operator — Ensure the op- erator(s) understand all operating and maintenance procedures. Point out the various chiller parts and explain their function as part of the complete system.

COOLER-CONDENSER — Float chamber, relief valves, re- frigerant charging valve, temperature sensor locations, pressure transducer locations, Schrader fittings, waterboxes and tubes, and vents and drains.

65

Image 65
Contents Safety Considerations Start-Up, Operation, and Maintenance InstructionsContents Contents Abbreviations and Explanations Introduction19XR Identification Chiller FamiliarizationTypical 19XR Components Motor and Lubricating OIL Cooling Cycle Refrigeration CycleLubrication Cycle VFD Cooling CycleUnit-Mounted Solid-State Starter Optional Starting EquipmentDefinitions Unit-Mounted Wye-Delta Starter OptionalControls Variable Frequency Drive VFD 19XR Controls and Sensor Locations PIC II Component Panel Location Major PIC II Components Panel LocationsControl Panel CVC/ICVC Operation and Menus Fig Example of Status Screen 19XR Chiller Display Menu Structure CVC/ICVC 19XR Service Menu Structure Time and Date Example of Time Schedule Operation Screen Example of Set Point Screen CVC/ICVC Display Data Example 1 Chiller Display Default ScreenDescription Status Units Point Example 2 Maintstat Display ScreenExample 3 Startup Display Screen Startup Description Status Units PointExample 5 Heatex Display Screen Example 4 Compress Display ScreenExample 7 Ismstat Display Screen Example 6 Power Display ScreenExample 8 CVC/ICVCPSWD Display Screen Menu Setpoint Select Description Status Units Point DefaultCVC Icvc Description Status Units Point Example 9 Setpoint Display ScreenExample 12 Llmaint Display Screen Example 11 Override Display ScreenControl Algorithm Status Override Description Units Point Control Algorithm Status Wsmdefme Description Units Point Example 13 Ismhist Display ScreenExample 14 Wsmdefme Display Screen Ismconf Description Status Units Point Default ISM Starter Config DataExample 15 Netopt Display Screen Example 16 Ismconf Display ScreenExample 17 Options Display Screen Example 18 SETUP1 Display ScreenSpare ALERT/ALARM Enable LAG=2, STANDBY=3 Example 19 SETUP2 Display ScreenExample 20 Leadlag Display Screen Reset Type Description Status Units Point DefaultExample 21 Rampdem Display Screen Example 22 Tempctl Display ScreenSurge Prevention Mode occurs when Active Delta T Normal Control mode occurs when Active Delta TMode IGV VFD PIC II System FunctionsPage Protective Safety Limits and Control Settings Page Capacity Overrides Evaporator Freeze Protection Icvc only a Page Head Pressure Reference Output Surge Protection Fixed Speed ChillerPage Page Point Example of Attach to Network Device Screen Example of Holiday Period Screen START-UP/SHUTDOWN Default CVC/ICVC screen, press the MenuRecycle Sequence Fig Local Start-Up Local start-up or a manual start-up isEntering Condenser Water temperature plus 3 F -1.6C Equipment Required Before Initial START-UPJob Data Required 19XR Leak Test Procedures Page Page Temperature Pressure HFC-134a Pressure Temperature FHFC-134a Pressure Temperature C Perform dehydration as follows Inspect WiringWhite G Check StarterManufacturer Cable no Software Configuration Parameter Benshaw RediStart Micro Menu Items Verify VFD Configuration and Change Parameters if Necessary Description Settings VFD Title Setting ParameterDescription Setting Press Menu Press Status Press Compress Press Select Press Status Press Compress Press SelectLoad Surge Prevention Occurs TOO Soon Occurs TOO Late Estimated Minimum Load ConditionsCCM Temperature Thermistors Tests to be Devices Tested Performed Charge Refrigerant into ChillerControl Test Menu Functions Refrigerant HFC-134a Charge Initial START-UPCheck Oil Pressure and Compressor Stop Dry Run to Test Start-Up SequenceCheck Motor Rotation Operator Duties Operating InstructionsTo Start the Chiller To Stop the ChillerOperating the Optional Pumpout Unit Pumpout and Refrigerant Transfer ProceduresTime Date Cooler Condenser CompressorBearing FLAValve Condition Turn off pumpout condenser waterChillers with Isolation Valves Test After Service, Repair, or Major Leak If General MaintenanceGuide Vane Actuator Linkage Weekly MaintenanceCheck Safety and Operating Controls Monthly Scheduled MaintenanceInspect the Heat Exchanger Tubes and Flow Devices Compressor Bearing and Gear MaintenanceOptional Pumpout System Controls Ordering Replacement Chiller Parts WhenChecking Pressure Transducers Troubleshooting GuideOccdefcm HeatexLlmaint Shutdown in Progress Terminate Pumpdown ModeICE Build Ready to StartAlert PrestartAutorestart in Progress Running Temp ControlRUN Capacity FaultLimited SensorFailure to ProtectiveStart StopCommunication LossPotential FREEZE-UPLOW OIL Pressure Sensor AlertAutorestart PendingRecycle Pressure AlertOption Sensor DiffuserDrop Thermistor Temperature F vs. Resistance/Voltage DropTemperature PIC Resistance Thermistor Temperature C vs. Resistance/Voltage DropControl Modules Power is connected to Plug J1 on each moduleReplacing Defective Processor Modules Chiller Control Module CCM FigIntegrated Starter Module Fig Integratedstartermodule Checked Measure SCR Pairs Recorded Being BetweenNumber of Tubes English Code Heat Exchanger Data EnglishNumber of Tubes Code Heat Exchanger Data SI19XR Additional Data for Marine Waterboxes Compressor WeightsEnglish Motor 19XR Motor Weights Standard and High Efficiency Motors19XR Waterbox Cover Weights English lb 19XR Waterbox Cover Weights SI kg Motor Voltage Code Additional Miscellaneous WeightsOptional Pumpout System Electrical Data Description Torque Compressor Assembly TorquesCompressor Code View B High Speed Shaft 19XR Compressor ClearancesAllen-Bradley Wye-Delta Unit-Mounted Starter 100101 ISM 102Temp 103104 105 106 107 Power Panel Wiring Schematic108 Cutler-Hammer Wye Delta Unit Mounted Starter Sizes 3-5DP109 Cutler-Hammer Wye Delta Unit Mounted Starter Size 6DPSeparate Metering Option Ground Fault Phase Current Option111 AUX 112FU Fuse 113114 VFD 115116 Typical Variable Frequency Drive VFD Wiring Schematic117 118 119 120 121 122 Index Index JOB Data Required Remove and use for job fileCL-2 Inspect Wiring and Record Electrical Data Ratings10 to 40 to 10060.0 15 toCL-4 460 200 to105 to 115 85 to50 to 30 to20 to Psi CL-690 to 150 to125 125 toAmp 250 CL-8 65 to90 to 100 CL-9 25 toCL-10 50 to 1450200 0000 to0000 to 0200 CL-11004 To H.022 Job Sheet 60 for 60 Hz and 50 for 50 Hz 002 Power Module Dependent Selected motor 100% amps028 10 to Job Sheet 60 for 60 Hz and 50 for 50 Hz 000 100 to Selected line voltageCL-13 CL-14 CCN Local ResetPage Incurring obligations
Related manuals
Manual 40 pages 46.08 Kb

19XR, XRV specifications

The Carrier 19XR and 19XRV chillers are sophisticated cooling solutions that represent the forefront of HVAC technology. Designed for large commercial and industrial applications, these chillers provide exceptional performance, energy efficiency, and reliability, making them ideal for a variety of environments ranging from hospitals to manufacturing facilities.

One of the most significant features of the Carrier 19XR and 19XRV chillers is their advanced scroll compressor technology. These units employ a tandem scroll design that enhances efficiency while minimizing operational noise. This makes them ideal for urban environments where noise restrictions may be in place. Moreover, the compressors are equipped with variable speed drive options in the 19XRV model, which allows for greater energy savings by adjusting cooling output based on real-time demand.

In addition to their advanced compressors, the 19XR and 19XRV units incorporate the Carrier GreenChoice refrigerant, which has a lower global warming potential compared to traditional refrigerants. This innovative choice not only meets regulatory requirements but also contributes to sustainability goals, making these chillers a responsible choice for environmentally conscious organizations.

The units are engineered with a robust heat exchanger design, which enhances heat transfer efficiency and overall system performance. This ensures optimal operation even in extreme conditions. They feature a microprocessor-based control system that allows for precise monitoring and control of the chiller’s performance, enabling operators to make real-time adjustments to maximize energy efficiency.

The Carrier 19XR and 19XRV chillers also prioritize serviceability. The design incorporates easy access to key components, simplifying maintenance procedures and reducing downtime. This focus on maintainability extends the lifespan of the equipment, leading to lower lifecycle costs.

In terms of connectivity, these chillers are equipped with advanced Building Management System (BMS) integration capabilities. This allows for seamless monitoring and control of the chillers using a centralized platform, facilitating energy management and operational optimization.

Overall, the Carrier 19XR and 19XRV chillers stand out in the market for their blend of cutting-edge technology, energy efficiency, and user-friendly features. They are engineered to meet the demanding needs of modern commercial and industrial applications, making them a preferred choice for facility managers seeking reliable cooling solutions.