Carrier 19XR, XRV specifications Initial START-UP, Refrigerant HFC-134a Charge

Page 64

CHILLER EQUALIZATION WITH PUMPOUT UNIT — The following steps describe how to equalize refrigerant pres- sure on an isolated 19XR chiller using the pumpout unit.

1.Access the terminate lockout function on the CONTROL TEST screen.

2.IMPORTANT: Turn on the chilled water and con- denser water pumps to prevent freezing.

3.Open valve 4 on the pumpout unit and open valves 1a and 1b on the chiller cooler and condenser, Fig. 29 and 30. Slowly open valve 2 on the pumpout unit to equalize the pressure. This process takes approximately 15 minutes.

4.Once the pressures have equalized, the discharge isola- tion valve, cooler isolation valve, optional hot gas bypass isolation valve, and the refrigerant isolation valve can be opened. Close valves 1a and 1b, and all pumpout unit valves.

Whenever turning the discharge isolation valve, be sure to reattach the valve locking device. This prevents the valve from opening or closing during service work or during chiller operation.

The full refrigerant charge on the 19XR will vary with chill- er components and design conditions, as indicated on the job data specifications. An approximate charge may be determined by adding the condenser charge to the cooler charge as listed in Table 10.

Always operate the condenser and chilled water pumps whenever charging, transferring, or removing refrigerant from the chiller.

Use the CONTROL TEST terminate lockout function to monitor conditions and start the pumps.

If the chiller has been shipped with a holding charge, the refrigerant is added through the pumpout charging connection (Fig. 29 and 30, valve 1b). First evacuate the nitrogen holding charge from the chiller vessels. Charge the refrigerant as a gas until the system pressure exceeds 35 psig (141 kPa) for HFC-134a. After the chiller is beyond this pressure the refrig- erant should be charged as a liquid until all the recommended refrigerant charge has been added. The charging valve (Fig. 29 and 30, valve 7) can be used to charge liquid to the cooler if the cooler isolation valve (11) is present and is closed. Do not charge liquid through the linear float to the condenser.

TRIMMING REFRIGERANT CHARGE — The 19XR is shipped with the correct charge for the design duty of the chill- er. Trimming the charge can best be accomplished when the design load is available. To trim the charge, check the tempera- ture difference between the leaving chilled water temperature and cooler refrigerant temperature at full load design condi- tions. If necessary, add or remove refrigerant to bring the temperature difference to design conditions or minimum differential.

Table 10 lists the 19XR chiller refrigerant charges for each cooler and condenser code. Total refrigerant charge is the sum of the cooler and condenser charge.

Table 10 — Refrigerant (HFC-134a) Charge

COOLER

REFRIGERANT

CONDENSER

REFRIGERANT

CHARGE

CHARGE

CODE

 

 

CODE

 

 

lb

kg

lb

kg

 

 

10

290

132

10

200

91

11

310

141

11

200

91

12

330

150

12

200

91

15

320

145

15

250

113

16

340

154

16

250

113

17

370

168

17

250

113

20

345

157

20

225

102

21

385

175

21

225

102

22

435

197

22

225

102

30

350

159

30

260

118

31

420

190

31

260

118

32

490

222

32

260

118

35

400

181

35

310

141

36

480

218

36

310

141

37

550

250

37

310

141

40

560

254

40

280

127

41

630

286

41

280

127

42

690

313

42

280

127

45

640

290

45

330

150

46

720

327

46

330

150

47

790

358

47

330

150

50

750

340

50

400

181

51

840

381

51

400

181

52

900

408

52

400

181

55

870

395

55

490

222

56

940

426

56

490

222

57

980

445

57

490

222

60

940

426

60

420

190

61

980

445

61

420

190

62

1020

463

62

420

190

65

1020

463

65

510

231

66

1060

481

66

510

231

67

1090

494

67

510

231

70

1220

553

70

780

354

71

1340

608

71

780

354

72

1440

653

72

780

354

75

1365

619

75

925

420

76

1505

683

76

925

420

77

1625

737

77

925

420

80

1500

680

80

720

327

81

1620

735

81

720

327

82

1730

785

82

720

327

85

1690

766

85

860

390

86

1820

825

86

860

390

87

1940

880

87

860

390

INITIAL START-UP

Preparation — Before starting the chiller, verify:

1.Power is on to the main starter, oil pump relay, tower fan starter, oil heater relay, and the chiller control panel.

2.Cooling tower water is at proper level and at-or-below design entering temperature.

3.Chiller is charged with refrigerant and all refrigerant and oil valves are in their proper operating positions.

4.Oil is at the proper level in the reservoir sight glasses.

5.Oil reservoir temperature is above 140 F (60 C) or above refrigerant temperature plus 50° F (28° C).

6.Valves in the evaporator and condenser water circuits are open.

NOTE: If the pumps are not automatic, ensure water is circulating properly.

Do not permit water or brine that is warmer than 110 F (43 C) to flow through the cooler or condenser. Refrigerant overpressure may discharge through the relief valves and result in the loss of refrigerant charge.

7.Access the CONTROL TEST screen. Scroll down on the TERMINATE LOCKOUT option. Press the SELECT (to enable the chiller to start) and answer YES to reset unit to operating mode. The chiller is locked out at the factory in order to prevent accidental start-up.

64

Image 64
Contents Start-Up, Operation, and Maintenance Instructions Safety ConsiderationsContents Contents Introduction Abbreviations and ExplanationsChiller Familiarization 19XR IdentificationTypical 19XR Components Refrigeration Cycle Motor and Lubricating OIL Cooling CycleVFD Cooling Cycle Lubrication CycleStarting Equipment Unit-Mounted Solid-State Starter OptionalControls Unit-Mounted Wye-Delta Starter OptionalDefinitions Variable Frequency Drive VFD 19XR Controls and Sensor Locations Major PIC II Components Panel Locations PIC II Component Panel LocationControl Panel CVC/ICVC Operation and Menus Fig Example of Status Screen 19XR Chiller Display Menu Structure CVC/ICVC 19XR Service Menu Structure Time and Date Example of Time Schedule Operation Screen Example of Set Point Screen Example 1 Chiller Display Default Screen CVC/ICVC Display DataExample 2 Maintstat Display Screen Description Status Units PointExample 3 Startup Display Screen Startup Description Status Units PointExample 4 Compress Display Screen Example 5 Heatex Display ScreenExample 6 Power Display Screen Example 7 Ismstat Display ScreenMenu Setpoint Select Description Status Units Point Default Example 8 CVC/ICVCPSWD Display ScreenCVC Icvc Description Status Units Point Example 9 Setpoint Display ScreenControl Algorithm Status Override Description Units Point Example 11 Override Display ScreenExample 12 Llmaint Display Screen Example 14 Wsmdefme Display Screen Example 13 Ismhist Display ScreenControl Algorithm Status Wsmdefme Description Units Point ISM Starter Config Data Ismconf Description Status Units Point DefaultExample 15 Netopt Display Screen Example 16 Ismconf Display ScreenSpare ALERT/ALARM Enable Example 18 SETUP1 Display ScreenExample 17 Options Display Screen Example 20 Leadlag Display Screen Example 19 SETUP2 Display ScreenLAG=2, STANDBY=3 Description Status Units Point Default Reset TypeExample 21 Rampdem Display Screen Example 22 Tempctl Display ScreenNormal Control mode occurs when Active Delta T Surge Prevention Mode occurs when Active Delta TMode IGV VFD PIC II System FunctionsPage Protective Safety Limits and Control Settings Page Capacity Overrides Evaporator Freeze Protection Icvc only a Page Surge Protection Fixed Speed Chiller Head Pressure Reference OutputPage Page Point Example of Attach to Network Device Screen Example of Holiday Period Screen Default CVC/ICVC screen, press the Menu START-UP/SHUTDOWNRecycle Sequence Fig Local Start-Up Local start-up or a manual start-up isEntering Condenser Water temperature plus 3 F -1.6C Job Data Required Before Initial START-UPEquipment Required 19XR Leak Test Procedures Page Page HFC-134a Pressure Temperature C HFC-134a Pressure Temperature FTemperature Pressure Inspect Wiring Perform dehydration as followsManufacturer Cable no Check StarterWhite G Software Configuration Parameter Benshaw RediStart Micro Menu Items Verify VFD Configuration and Change Parameters if Necessary Description Setting VFD Title Setting ParameterDescription Settings Press Status Press Compress Press Select Press Menu Press Status Press Compress Press SelectEstimated Minimum Load Conditions Load Surge Prevention Occurs TOO Soon Occurs TOO LateCCM Temperature Thermistors Control Test Menu Functions Charge Refrigerant into ChillerTests to be Devices Tested Performed Initial START-UP Refrigerant HFC-134a ChargeCheck Motor Rotation Dry Run to Test Start-Up SequenceCheck Oil Pressure and Compressor Stop Operating Instructions Operator DutiesTo Start the Chiller To Stop the ChillerPumpout and Refrigerant Transfer Procedures Operating the Optional Pumpout UnitDate Cooler Condenser Compressor TimeBearing FLATurn off pumpout condenser water Valve ConditionChillers with Isolation Valves General Maintenance Test After Service, Repair, or Major Leak IfWeekly Maintenance Guide Vane Actuator LinkageScheduled Maintenance Check Safety and Operating Controls MonthlyCompressor Bearing and Gear Maintenance Inspect the Heat Exchanger Tubes and Flow DevicesOrdering Replacement Chiller Parts When Optional Pumpout System ControlsTroubleshooting Guide Checking Pressure TransducersLlmaint HeatexOccdefcm Terminate Pumpdown Mode Shutdown in ProgressICE Build Ready to StartPrestart AlertAutorestart in Progress Running Temp ControlFault RUN CapacityLimited SensorProtective Failure toStart StopLoss CommunicationPotential FREEZE-UPSensor Alert LOW OIL PressureAutorestart PendingPressure Alert RecycleOption Sensor DiffuserThermistor Temperature F vs. Resistance/Voltage Drop DropThermistor Temperature C vs. Resistance/Voltage Drop Temperature PIC ResistancePower is connected to Plug J1 on each module Control ModulesIntegrated Starter Module Fig Chiller Control Module CCM FigReplacing Defective Processor Modules Integratedstartermodule Measure SCR Pairs Recorded Being Between CheckedHeat Exchanger Data English Number of Tubes English CodeHeat Exchanger Data SI Number of Tubes CodeCompressor Weights 19XR Additional Data for Marine Waterboxes19XR Motor Weights Standard and High Efficiency Motors English Motor19XR Waterbox Cover Weights English lb 19XR Waterbox Cover Weights SI kg Optional Pumpout System Electrical Data Additional Miscellaneous WeightsMotor Voltage Code Compressor Assembly Torques Description TorqueView B High Speed Shaft 19XR Compressor Clearances Compressor Code100 Allen-Bradley Wye-Delta Unit-Mounted Starter101 102 ISM103 Temp104 105 106 Power Panel Wiring Schematic 107Cutler-Hammer Wye Delta Unit Mounted Starter Sizes 3-5DP 108Cutler-Hammer Wye Delta Unit Mounted Starter Size 6DP 109Ground Fault Phase Current Option Separate Metering Option111 112 AUX113 FU Fuse114 115 VFDTypical Variable Frequency Drive VFD Wiring Schematic 116117 118 119 120 121 122 Index Index Remove and use for job file JOB Data RequiredInspect Wiring and Record Electrical Data Ratings CL-240 to 100 10 to60.0 15 toCL-4 200 to 460105 to 115 85 to30 to 50 to20 to Psi CL-6150 to 90 to125 125 to90 to 100 65 toAmp 250 CL-8 25 to CL-950 to 145 CL-100000 to 02000000 to 0200 CL-11002 Power Module Dependent Selected motor 100% amps 004 To H.022 Job Sheet 60 for 60 Hz and 50 for 50 Hz028 10 to Job Sheet 60 for 60 Hz and 50 for 50 Hz 000 100 to Selected line voltageCL-13 CCN Local Reset CL-14Page Incurring obligations
Related manuals
Manual 40 pages 46.08 Kb

19XR, XRV specifications

The Carrier 19XR and 19XRV chillers are sophisticated cooling solutions that represent the forefront of HVAC technology. Designed for large commercial and industrial applications, these chillers provide exceptional performance, energy efficiency, and reliability, making them ideal for a variety of environments ranging from hospitals to manufacturing facilities.

One of the most significant features of the Carrier 19XR and 19XRV chillers is their advanced scroll compressor technology. These units employ a tandem scroll design that enhances efficiency while minimizing operational noise. This makes them ideal for urban environments where noise restrictions may be in place. Moreover, the compressors are equipped with variable speed drive options in the 19XRV model, which allows for greater energy savings by adjusting cooling output based on real-time demand.

In addition to their advanced compressors, the 19XR and 19XRV units incorporate the Carrier GreenChoice refrigerant, which has a lower global warming potential compared to traditional refrigerants. This innovative choice not only meets regulatory requirements but also contributes to sustainability goals, making these chillers a responsible choice for environmentally conscious organizations.

The units are engineered with a robust heat exchanger design, which enhances heat transfer efficiency and overall system performance. This ensures optimal operation even in extreme conditions. They feature a microprocessor-based control system that allows for precise monitoring and control of the chiller’s performance, enabling operators to make real-time adjustments to maximize energy efficiency.

The Carrier 19XR and 19XRV chillers also prioritize serviceability. The design incorporates easy access to key components, simplifying maintenance procedures and reducing downtime. This focus on maintainability extends the lifespan of the equipment, leading to lower lifecycle costs.

In terms of connectivity, these chillers are equipped with advanced Building Management System (BMS) integration capabilities. This allows for seamless monitoring and control of the chillers using a centralized platform, facilitating energy management and operational optimization.

Overall, the Carrier 19XR and 19XRV chillers stand out in the market for their blend of cutting-edge technology, energy efficiency, and user-friendly features. They are engineered to meet the demanding needs of modern commercial and industrial applications, making them a preferred choice for facility managers seeking reliable cooling solutions.