Carrier 19XR, XRV specifications Parameter

Page 56

NOTE: Because a schedule is integral to the chiller control sequence, the chiller will not start until the time and date have been set.

CHANGE CVC/ICVC CONFIGURATION IF NECES- SARY — From the SERVICE table, access the CVC/ICVC CONFIGU-RATION screen. From there, view or modify the CVC/ICVC CCN address, change to English or SI units, and change the password. If there is more than one chiller at the jobsite, change the CVC/ICVC address on each chiller so that each chiller has its own address. Note and record the new address. Change the screen to SI units as required, and change the password if desired.

TO CHANGE THE PASSWORD — The password may be changed from the CVC/ICVC CONFIGURATION screen.

1.Press the MENU and SERVICE softkeys. Enter the current password and highlight CVC/ICVC CONFIGU-

RATION. Press the SELECT softkey. Only the last 5 entries on the CVC/ICVC CONFIG screen can be changed: BUS #, ADDRESS #, BAUD RATE, US IMP/ METRIC, and PASSWORD.

2.Use the ENTER softkey to scroll to PASSWORD. The first digit of the password is highlighted on the screen.

3.To change the digit, press the INCREASE or DECREASE softkey. When the desired digit is seen, press the ENTER softkey.

4.The next digit is highlighted. Change it, and the third and fourth digits in the same way the first was changed.

5.After the last digit is changed, the CVC/ICVC goes to the

BUS parameter. Press the EXIT softkey to leave that screen and return to the SERVICE menu.

Be sure to remember the password. Retain a copy for future reference. Without the password, access to the SERVICE menu will not be possible unless the CVC/ ICVC_PSWD menu on the STATUS screen is accessed by a Carrier representative.

TO CHANGE THE CVC/ICVC DISPLAY FROM ENGLISH TO METRIC UNITS — By default, the CVC/ ICVC displays information in English units. To change to met- ric units, access the CVC/ICVC CONFIGURATION screen:

1.Press the MENU and SERVICE softkeys. Enter the password and highlight CVC/ICVC CONFIGURATION. Press the SELECT softkey.

2.Use the ENTER softkey to scroll to US IMP/METRIC.

3.Press the softkey that corresponds to the units desired for display on the CVC/ICVC (e.g., US or METRIC).

CHANGE LANGUAGE (ICVC Only) — By default, the ICVC displays information in English. To change to another Language, access the ICVC CONFIGURATION screen:

1.Press the MENU and SERVICE softkeys. Enter the password and highlight ICVC CONFIGURATION. Press the SELECT softkey.

2.Use the ENTER softkey to scroll to LID LANGUAGE.

3.Press the INCREASE or DECREASE softkey until the

desired language is displayed. Press ENTER to confirm desired language.

MODIFY CONTROLLER IDENTIFICATION IF NECES- SARY — The CVC/ICVC module address can be changed from the CVC/ICVC CONFIGURATION screen. Change this

address for each chiller if there is more than one chiller at the jobsite. Write the new address on the CVC/ICVC module for future reference.

INPUT EQUIPMENT SERVICE PARAMETERS IF NEC- ESSARY — The EQUIPMENT SERVICE table has six service tables.

Configure SERVICE Tables — Access the SERVICE tables, shown in Table 2, to modify or view job site parameters:

PARAMETER

TABLE

Starter Type

ISM_CONF — Select 0 for full voltage, 1 for

 

reduced voltage, or 2 for solid state/variable fre-

 

quency drive.

Motor Rated Line

ISM_CONF — Motor rated voltage from chiller

Voltage

information nameplate.

Volt Transformer

ISM_CONF — Enter ratio (reduced to a ratio to

Ratio

1) of power transformer wired to terminal J3 of

 

ISM. If no transformer is used enter 1.

Motor Rated

ISM_CONF — Per chiller identification name-

Load Amps

plate data.

Motor Locked

ISM_CONF — Per chiller identification name-

Rotor Trip

plate data. Enter locked rotor delta amps (LR

 

AMPS D-).

Starter LRA

ISM_CONF — Enter value from nameplate in

Rating

starter cabinet

 

Allen -Bradley this appears as “max locked rotor

 

current @100% nom. voltage.”

 

Benshaw Starters: value is entered as 9999.

Motor Current

ISM_CONF — Enter ratio (reduced to a ratio to

CT Ratio

1) of current transformers wired to terminal J4 of

 

ISM. For Benshaw Inc. RediStart MICRO™

 

Starters set to 100.

Ground Fault

ISM_CONF — Enter 0 if no ground fault CTs are

Current

wired to terminal J5 of ISM. Enter 1 if ground

Transformers

fault CTs are used.

Ground Fault

ISM_CONF — Enter ratio (reduced to a ratio to

CT Ratio

1) of ground fault CT.

Single Cycle

ISM_CONF — ENABLE if motor protection

Dropout

required from drop in line voltage within one

 

cycle.

Line Frequency

ISM_CONF — Enter YES for 60 Hz or NO for 50

 

Hz.

Line Frequency

ISM_CONF — ENABLE if motor

Faulting

protection required for drop in line

 

frequency.

Surge Limiting or

OPTIONS — Enter 1 if HGBP is installed.

Hot Gas Bypass

 

Option

 

Minimum Load

OPTIONS — Per Chiller Requisition (DT1, DP2)

Points (T1, P1)

if available or per job data — See modify load

 

points section.

Full (Maximum)

OPTIONS — Per Chiller Requisition (DT2, DP2)

Load Points (T2, P2)

if available or per job data — See modify load

 

points section. For VFD units refer to table

 

located in control panel.

Chilled Medium

SETUP1 — Enter water or brine.

Evaporator

SETUP1 — Usually 3° F (1.7° C) below design

Refrigerant

refrigerant temperature.

Trippoint

 

Evaporator Flow

SETUP1 — Per Chiller Requisition if available or

Delta P Cutout

enter 50% of design pressure drop to 0.5 psi (3.4

 

kPa).*

Condenser Flow

SETUP1 — Per Chiller Requisition if available or

Delta P Cutout

enter 50% of design pressure drop to 0.5 psi (3.4

 

kPa).*

Diffuser Option

SETUP2 — ENABLE for 4 and 5 size compres-

(Compressors with Split

sor. See model number nomenclature.

Ring Diffusers)

 

Diffuser Full Span

SETUP2 — Enter diffuser actuator full span mA

mA Rating

rating for 4 and 5 size compressor. Value is

(Compressors with Split

located on label on side of diffuser actuator

Ring Diffusers)

motor.

Motor Rated

RAMP_DEM — Enter value from chiller requisi-

Kilowatts

tion form (product data submittal) if kilowatt ramp

 

demand is enabled.

*With variable flow systems this point may be configured to the lower end of the range.

NOTE: Other parameters: Screens are normally left at the default settings; they may be changed by the operator as required. The time and persistence set- tings on the ISM_CONF table can be adjusted to increase or decrease the sen- sitivity to a fault condition. Increasing time or persistence decreases sensitivity. Decreasing time or persistence increases sensitivity to the fault condition.

56

Image 56
Contents Start-Up, Operation, and Maintenance Instructions Safety ConsiderationsContents Contents Introduction Abbreviations and ExplanationsChiller Familiarization 19XR IdentificationTypical 19XR Components Refrigeration Cycle Motor and Lubricating OIL Cooling CycleVFD Cooling Cycle Lubrication CycleStarting Equipment Unit-Mounted Solid-State Starter OptionalDefinitions Unit-Mounted Wye-Delta Starter OptionalControls Variable Frequency Drive VFD 19XR Controls and Sensor Locations Major PIC II Components Panel Locations PIC II Component Panel LocationControl Panel CVC/ICVC Operation and Menus Fig Example of Status Screen 19XR Chiller Display Menu Structure CVC/ICVC 19XR Service Menu Structure Time and Date Example of Time Schedule Operation Screen Example of Set Point Screen Example 1 Chiller Display Default Screen CVC/ICVC Display DataExample 2 Maintstat Display Screen Description Status Units PointExample 3 Startup Display Screen Startup Description Status Units PointExample 4 Compress Display Screen Example 5 Heatex Display ScreenExample 6 Power Display Screen Example 7 Ismstat Display ScreenMenu Setpoint Select Description Status Units Point Default Example 8 CVC/ICVCPSWD Display ScreenCVC Icvc Description Status Units Point Example 9 Setpoint Display ScreenExample 12 Llmaint Display Screen Example 11 Override Display ScreenControl Algorithm Status Override Description Units Point Control Algorithm Status Wsmdefme Description Units Point Example 13 Ismhist Display ScreenExample 14 Wsmdefme Display Screen ISM Starter Config Data Ismconf Description Status Units Point DefaultExample 15 Netopt Display Screen Example 16 Ismconf Display ScreenExample 17 Options Display Screen Example 18 SETUP1 Display ScreenSpare ALERT/ALARM Enable LAG=2, STANDBY=3 Example 19 SETUP2 Display ScreenExample 20 Leadlag Display Screen Description Status Units Point Default Reset TypeExample 21 Rampdem Display Screen Example 22 Tempctl Display ScreenNormal Control mode occurs when Active Delta T Surge Prevention Mode occurs when Active Delta TMode IGV VFD PIC II System FunctionsPage Protective Safety Limits and Control Settings Page Capacity Overrides Evaporator Freeze Protection Icvc only a Page Surge Protection Fixed Speed Chiller Head Pressure Reference OutputPage Page Point Example of Attach to Network Device Screen Example of Holiday Period Screen Default CVC/ICVC screen, press the Menu START-UP/SHUTDOWNRecycle Sequence Fig Local Start-Up Local start-up or a manual start-up isEntering Condenser Water temperature plus 3 F -1.6C Equipment Required Before Initial START-UPJob Data Required 19XR Leak Test Procedures Page Page Temperature Pressure HFC-134a Pressure Temperature FHFC-134a Pressure Temperature C Inspect Wiring Perform dehydration as followsWhite G Check StarterManufacturer Cable no Software Configuration Parameter Benshaw RediStart Micro Menu Items Verify VFD Configuration and Change Parameters if Necessary Description Settings VFD Title Setting ParameterDescription Setting Press Status Press Compress Press Select Press Menu Press Status Press Compress Press SelectEstimated Minimum Load Conditions Load Surge Prevention Occurs TOO Soon Occurs TOO LateCCM Temperature Thermistors Tests to be Devices Tested Performed Charge Refrigerant into ChillerControl Test Menu Functions Initial START-UP Refrigerant HFC-134a ChargeCheck Oil Pressure and Compressor Stop Dry Run to Test Start-Up SequenceCheck Motor Rotation Operating Instructions Operator DutiesTo Start the Chiller To Stop the ChillerPumpout and Refrigerant Transfer Procedures Operating the Optional Pumpout UnitDate Cooler Condenser Compressor TimeBearing FLATurn off pumpout condenser water Valve ConditionChillers with Isolation Valves General Maintenance Test After Service, Repair, or Major Leak IfWeekly Maintenance Guide Vane Actuator LinkageScheduled Maintenance Check Safety and Operating Controls MonthlyCompressor Bearing and Gear Maintenance Inspect the Heat Exchanger Tubes and Flow DevicesOrdering Replacement Chiller Parts When Optional Pumpout System ControlsTroubleshooting Guide Checking Pressure TransducersOccdefcm HeatexLlmaint Terminate Pumpdown Mode Shutdown in ProgressICE Build Ready to StartPrestart AlertAutorestart in Progress Running Temp ControlFault RUN CapacityLimited SensorProtective Failure toStart StopLoss CommunicationPotential FREEZE-UPSensor Alert LOW OIL PressureAutorestart PendingPressure Alert RecycleOption Sensor DiffuserThermistor Temperature F vs. Resistance/Voltage Drop DropThermistor Temperature C vs. Resistance/Voltage Drop Temperature PIC ResistancePower is connected to Plug J1 on each module Control ModulesReplacing Defective Processor Modules Chiller Control Module CCM FigIntegrated Starter Module Fig Integratedstartermodule Measure SCR Pairs Recorded Being Between CheckedHeat Exchanger Data English Number of Tubes English CodeHeat Exchanger Data SI Number of Tubes CodeCompressor Weights 19XR Additional Data for Marine Waterboxes19XR Motor Weights Standard and High Efficiency Motors English Motor19XR Waterbox Cover Weights English lb 19XR Waterbox Cover Weights SI kg Motor Voltage Code Additional Miscellaneous WeightsOptional Pumpout System Electrical Data Compressor Assembly Torques Description TorqueView B High Speed Shaft 19XR Compressor Clearances Compressor Code100 Allen-Bradley Wye-Delta Unit-Mounted Starter101 102 ISM103 Temp104 105 106 Power Panel Wiring Schematic 107Cutler-Hammer Wye Delta Unit Mounted Starter Sizes 3-5DP 108Cutler-Hammer Wye Delta Unit Mounted Starter Size 6DP 109Ground Fault Phase Current Option Separate Metering Option111 112 AUX113 FU Fuse114 115 VFDTypical Variable Frequency Drive VFD Wiring Schematic 116117 118 119 120 121 122 Index Index Remove and use for job file JOB Data RequiredInspect Wiring and Record Electrical Data Ratings CL-240 to 100 10 to60.0 15 toCL-4 200 to 460105 to 115 85 to30 to 50 to20 to Psi CL-6150 to 90 to125 125 toAmp 250 CL-8 65 to90 to 100 25 to CL-950 to 145 CL-100000 to 02000000 to 0200 CL-11002 Power Module Dependent Selected motor 100% amps 004 To H.022 Job Sheet 60 for 60 Hz and 50 for 50 Hz028 10 to Job Sheet 60 for 60 Hz and 50 for 50 Hz 000 100 to Selected line voltageCL-13 CCN Local Reset CL-14Page Incurring obligations
Related manuals
Manual 40 pages 46.08 Kb

19XR, XRV specifications

The Carrier 19XR and 19XRV chillers are sophisticated cooling solutions that represent the forefront of HVAC technology. Designed for large commercial and industrial applications, these chillers provide exceptional performance, energy efficiency, and reliability, making them ideal for a variety of environments ranging from hospitals to manufacturing facilities.

One of the most significant features of the Carrier 19XR and 19XRV chillers is their advanced scroll compressor technology. These units employ a tandem scroll design that enhances efficiency while minimizing operational noise. This makes them ideal for urban environments where noise restrictions may be in place. Moreover, the compressors are equipped with variable speed drive options in the 19XRV model, which allows for greater energy savings by adjusting cooling output based on real-time demand.

In addition to their advanced compressors, the 19XR and 19XRV units incorporate the Carrier GreenChoice refrigerant, which has a lower global warming potential compared to traditional refrigerants. This innovative choice not only meets regulatory requirements but also contributes to sustainability goals, making these chillers a responsible choice for environmentally conscious organizations.

The units are engineered with a robust heat exchanger design, which enhances heat transfer efficiency and overall system performance. This ensures optimal operation even in extreme conditions. They feature a microprocessor-based control system that allows for precise monitoring and control of the chiller’s performance, enabling operators to make real-time adjustments to maximize energy efficiency.

The Carrier 19XR and 19XRV chillers also prioritize serviceability. The design incorporates easy access to key components, simplifying maintenance procedures and reducing downtime. This focus on maintainability extends the lifespan of the equipment, leading to lower lifecycle costs.

In terms of connectivity, these chillers are equipped with advanced Building Management System (BMS) integration capabilities. This allows for seamless monitoring and control of the chillers using a centralized platform, facilitating energy management and operational optimization.

Overall, the Carrier 19XR and 19XRV chillers stand out in the market for their blend of cutting-edge technology, energy efficiency, and user-friendly features. They are engineered to meet the demanding needs of modern commercial and industrial applications, making them a preferred choice for facility managers seeking reliable cooling solutions.