NOTE: Because a schedule is integral to the chiller control sequence, the chiller will not start until the time and date have been set.
CHANGE CVC/ICVC CONFIGURATION IF NECES- SARY — From the SERVICE table, access the CVC/ICVC CONFIGU-RATION screen. From there, view or modify the CVC/ICVC CCN address, change to English or SI units, and change the password. If there is more than one chiller at the jobsite, change the CVC/ICVC address on each chiller so that each chiller has its own address. Note and record the new address. Change the screen to SI units as required, and change the password if desired.
TO CHANGE THE PASSWORD — The password may be changed from the CVC/ICVC CONFIGURATION screen.
1.Press the MENU and SERVICE softkeys. Enter the current password and highlight CVC/ICVC CONFIGU-
RATION. Press the SELECT softkey. Only the last 5 entries on the CVC/ICVC CONFIG screen can be changed: BUS #, ADDRESS #, BAUD RATE, US IMP/ METRIC, and PASSWORD.
2.Use the ENTER softkey to scroll to PASSWORD. The first digit of the password is highlighted on the screen.
3.To change the digit, press the INCREASE or DECREASE softkey. When the desired digit is seen, press the ENTER softkey.
4.The next digit is highlighted. Change it, and the third and fourth digits in the same way the first was changed.
5.After the last digit is changed, the CVC/ICVC goes to the
BUS parameter. Press the EXIT softkey to leave that screen and return to the SERVICE menu.
Be sure to remember the password. Retain a copy for future reference. Without the password, access to the SERVICE menu will not be possible unless the CVC/ ICVC_PSWD menu on the STATUS screen is accessed by a Carrier representative.
TO CHANGE THE CVC/ICVC DISPLAY FROM ENGLISH TO METRIC UNITS — By default, the CVC/ ICVC displays information in English units. To change to met- ric units, access the CVC/ICVC CONFIGURATION screen:
1.Press the MENU and SERVICE softkeys. Enter the password and highlight CVC/ICVC CONFIGURATION. Press the SELECT softkey.
2.Use the ENTER softkey to scroll to US IMP/METRIC.
3.Press the softkey that corresponds to the units desired for display on the CVC/ICVC (e.g., US or METRIC).
CHANGE LANGUAGE (ICVC Only) — By default, the ICVC displays information in English. To change to another Language, access the ICVC CONFIGURATION screen:
1.Press the MENU and SERVICE softkeys. Enter the password and highlight ICVC CONFIGURATION. Press the SELECT softkey.
2.Use the ENTER softkey to scroll to LID LANGUAGE.
3.Press the INCREASE or DECREASE softkey until the
desired language is displayed. Press ENTER to confirm desired language.
MODIFY CONTROLLER IDENTIFICATION IF NECES- SARY — The CVC/ICVC module address can be changed from the CVC/ICVC CONFIGURATION screen. Change this
address for each chiller if there is more than one chiller at the jobsite. Write the new address on the CVC/ICVC module for future reference.
INPUT EQUIPMENT SERVICE PARAMETERS IF NEC- ESSARY — The EQUIPMENT SERVICE table has six service tables.
Configure SERVICE Tables — Access the SERVICE tables, shown in Table 2, to modify or view job site parameters:
PARAMETER | TABLE |
Starter Type | ISM_CONF — Select 0 for full voltage, 1 for |
| reduced voltage, or 2 for solid state/variable fre- |
| quency drive. |
Motor Rated Line | ISM_CONF — Motor rated voltage from chiller |
Voltage | information nameplate. |
Volt Transformer | ISM_CONF — Enter ratio (reduced to a ratio to |
Ratio | 1) of power transformer wired to terminal J3 of |
| ISM. If no transformer is used enter 1. |
Motor Rated | ISM_CONF — Per chiller identification name- |
Load Amps | plate data. |
Motor Locked | ISM_CONF — Per chiller identification name- |
Rotor Trip | plate data. Enter locked rotor delta amps (LR |
| AMPS D-). |
Starter LRA | ISM_CONF — Enter value from nameplate in |
Rating | starter cabinet |
| Allen -Bradley this appears as “max locked rotor |
| current @100% nom. voltage.” |
| Benshaw Starters: value is entered as 9999. |
Motor Current | ISM_CONF — Enter ratio (reduced to a ratio to |
CT Ratio | 1) of current transformers wired to terminal J4 of |
| ISM. For Benshaw Inc. RediStart MICRO™ |
| Starters set to 100. |
Ground Fault | ISM_CONF — Enter 0 if no ground fault CTs are |
Current | wired to terminal J5 of ISM. Enter 1 if ground |
Transformers | fault CTs are used. |
Ground Fault | ISM_CONF — Enter ratio (reduced to a ratio to |
CT Ratio | 1) of ground fault CT. |
Single Cycle | ISM_CONF — ENABLE if motor protection |
Dropout | required from drop in line voltage within one |
| cycle. |
Line Frequency | ISM_CONF — Enter YES for 60 Hz or NO for 50 |
| Hz. |
Line Frequency | ISM_CONF — ENABLE if motor |
Faulting | protection required for drop in line |
| frequency. |
Surge Limiting or | OPTIONS — Enter 1 if HGBP is installed. |
Hot Gas Bypass | |
Option | |
Minimum Load | OPTIONS — Per Chiller Requisition (DT1, DP2) |
Points (T1, P1) | if available or per job data — See modify load |
| points section. |
Full (Maximum) | OPTIONS — Per Chiller Requisition (DT2, DP2) |
Load Points (T2, P2) | if available or per job data — See modify load |
| points section. For VFD units refer to table |
| located in control panel. |
Chilled Medium | SETUP1 — Enter water or brine. |
Evaporator | SETUP1 — Usually 3° F (1.7° C) below design |
Refrigerant | refrigerant temperature. |
Trippoint | |
Evaporator Flow | SETUP1 — Per Chiller Requisition if available or |
Delta P Cutout | enter 50% of design pressure drop to 0.5 psi (3.4 |
| kPa).* |
Condenser Flow | SETUP1 — Per Chiller Requisition if available or |
Delta P Cutout | enter 50% of design pressure drop to 0.5 psi (3.4 |
| kPa).* |
Diffuser Option | SETUP2 — ENABLE for 4 and 5 size compres- |
(Compressors with Split | sor. See model number nomenclature. |
Ring Diffusers) | |
Diffuser Full Span | SETUP2 — Enter diffuser actuator full span mA |
mA Rating | rating for 4 and 5 size compressor. Value is |
(Compressors with Split | located on label on side of diffuser actuator |
Ring Diffusers) | motor. |
Motor Rated | RAMP_DEM — Enter value from chiller requisi- |
Kilowatts | tion form (product data submittal) if kilowatt ramp |
| demand is enabled. |
*With variable flow systems this point may be configured to the lower end of the range.
NOTE: Other parameters: Screens are normally left at the default settings; they may be changed by the operator as required. The time and persistence set- tings on the ISM_CONF table can be adjusted to increase or decrease the sen- sitivity to a fault condition. Increasing time or persistence decreases sensitivity. Decreasing time or persistence increases sensitivity to the fault condition.