Sierra Monitor Corporation HRG015-W, HRG010-W Piping, „ Pipe diameter, „ How to install piping

Page 35

HRX-OM-J049-A

Chapter 3 Transport and Installation

3.2.6Piping

Only expert engineers or personnel who have adequate knowledge of and experiences with piping installation are allowed to install piping. Potential fluid leakage or stagnant fluid may occur if disregarded.

zInstall piping properly. Failure to conduct proper piping installation may result in the entry of supplied and drained water into the inside of the building, which may cause the work area and equipment to get wet.

zKeep facility water pressure below 0.5MPa.

zMake sure the locations of IN and OUT ports for circulating fluid supply. The reverse connection inhibits proper operation of the unit.

zMake sure no entry of dust and foreign materials into the water circuit during piping installation.

zHold the piping connected port with a pipe wrench when tightening the pipe. Excessive force will damage the port and cause leaks if disregarded.

zHold the piping connected port with a pipe wrench when tightening piping.

„Pipe diameter

Table 3-5 Pipe diameter

 

Pipe

 

 

Diameter

 

 

Recommended

 

 

 

 

HRG010-W

 

HRG015-W

 

 

tightening torque

 

 

 

 

 

 

 

 

 

 

Facility water IN

 

Rc1/2

 

 

Rc3/4

 

28 to 30N·m

 

Facility water OUT

 

Rc1/2

 

 

Rc3/4

 

28 to 30N·m

 

Auto supply port

 

 

Rc1/2

 

28 to 30N·m

 

Circulating fluid OUT

 

 

Rc3/4

 

28 to 30N·m

 

Circulating fluid RETURN

 

 

Rc3/4

 

28 to 30N·m

 

Port for overflow

 

 

Rc1/2

 

28 to 30N·m

 

Port for drain in tank

 

 

Rc1/2

 

28 to 30N·m

„How to install piping

1. Hold the piping connected port with a specific wrench and tighten the pipe.

Pipe coupling hole

Sealant

[Tips]

Fig. 3-12 Tightening of Pipe

 

Install a valve at the drain port to facilitate the replacing and draining of the circulating fluid from the tank described in chapter 6 “Unit Maintenance”. (The valve needs to be prepared separately.)

HRG010-W HRG015-W

3.2 Installation

1st edition : Aug. 2006

3-13

Rev. A: May. 2007

Image 35
Contents Water-refrigerated Thermo cooler To the Customers Table of Contents Chapter Documents Error Message and TroubleshootingChapter Unit Maintenance Startup and ShutdownTOC-3 TOC-4 Before Using this Unit Safety Instructions„ Minor injury Level of riskDefinitions of Serious injury and Minor injury „ Serious injurySymbols „ High voltage hazards „ High temperature hazardsHazard Warning Label Classification of risksType of hazard warning labels Location of hazard warning label Model labelSafety Precautions Safety Measures„ For system operation „ For system transportation, installation and removalProtective equipment „ For handling circulating fluidThermo Cooler OFF Emergency MeasuresDisposition of Waste Recovery of refrigerant and compressor oilSystem disposal Material Safety Data Sheet MsdsCirculating fluid disposal Safety Instructions Appearance Appearance and Each Section1 HRG010-W Name of Each SectionName of Each Section HRG015-W 2 HRG015-WName Function Control panelTransport Transport and InstallationForklift Insertion Position and Unit Lifting Transporting with forklift and unit lifting„ HRG010-W-A / HRG015-W-A caster-mounted option Transporting with casterInstallation conditions InstallationInstallation location Recommended Installation Location Installation location and maintenance work area„ Procedure for Installation InstallationHRG010-W-A / HRG015-W-A Caster-mounted Option HRG010-W HRG015-W Electrical wiring„ Power supply cable and Gfci breaker Removal of Front Panel „ How to conduct wiringHRG015-W „ Electrical wiring diagram11 Communication Cable Wiring Specifications„ Pipe diameter „ How to install pipingPiping Name Qty „ Recommended piping installationName Size HRG010-W HRG015-W Open the supply valve laid with pipes Supply of circulating fluid„ Disconnection of power supply cable Reinstallation of unitPre-check Startup and ShutdownPreparation for startup Power supplySetting of circulating fluid temperature Additional water supply „ TS switch pump manual operation switchStopping the unit Unit Startup and ShutdownStarting the unit „ Bypass valve Check at startup„ Bypass relieving valve piping set Error Message Error Message TroubleshootingSee 5.3 Alarm Reset for error recovery Troubleshooting„ Error check Alarm Reset Alarm Lamp OFFUndo the screws 6 pcs. to remove the front panel Location of Reset Switch RS Yellow Button „ When the alarm lamp goes out by performing steps 1. to„ Power error check Recovery from Power Failure Power Lamp onUndo the screws 6 pcs. to remove the front panel Switch off the earth leakage breaker once Substances Facility water Circulating fluid spec Spec Unit MaintenanceControl of Water Quality Inspection and Cleaning Inspection method Daily inspectionInspection item Biannual inspection „ Replacement of circulating fluid„ Cleaning of facility water Quarterly inspection„ Antifreeze function automatic pump operation Check during wintertime„ Antifreeze of circulating fluid Part number Qty Remarks ConsumablesLong-term Storage Documents Standard SpecificationsHRG010-W HRG015-W „ Communication Optional Specifications„ Caster „ Gfci breaker2 HRG010-W-A, HRG015-W-A Outline Dimensions1 HRG010-W, HRG015-W Electric CircuitElectric Circuit HRG010-W-BC, HRG015-W-BC 2 HRG010-W-BC, HRG015-W-BC„ HRG010-W, HRG015-W Flow ChartIN/OUT Thermo Cooler HRG010-W / WRG015-W Daily Inspection SheetProduct Warranty