DCA-100SSJU — OUTPUTTERMINAL PANEL OVERVIEW
Output Terminal Panel Available Voltages
A wide range of voltages are available to supply load to many different applications. Voltages may be selected by using the voltage selector switch and how you hookup your hard wire connection to the generator. To obtain some of the voltages listed, fine adjustment with the Voltage Regulator on the control panel is necessary. See the table below (Table 8) for a list of available voltages the generator is able to supply.
Table 8. Available Voltages
MODEL | DCA100SSJU |
|
|
|
| ||
|
|
|
|
|
|
| |
3 PHASE VOLTAGE | 208 VOLT | 220 VOLT | 240 VOLT | 416 VOLT | 440 VOLT | 480 VOLT | |
(SWITCHABLE) | |||||||
|
|
|
|
|
| ||
|
|
|
|
|
|
| |
SINGLE PHASE | 120 VOLT | 127 VOLT | 139 VOLT | 240 VOLT | 254 VOLT | 277 VOLT | |
(SWITCHABLE) | |||||||
|
|
|
|
|
| ||
|
|
|
|
|
|
|
Voltage Selector Switch
The voltage selector switch is located above the UVWO Hard Wire Hookup Panel. It has been provided for ease of voltage selection.
CAUTION :
NEVER switch Voltage Selector Switch position while the engine is engaged.
Voltage Selector Switch Locking Button
The voltage selector switch has a locking button to protect the generator and generator load from being switched while the engine is running. To lock the Voltage Selector Switch, press in the red button located on the Voltage Selector Switch, and use a pad lock to hold it into this position. (See figure 17, page 37)
Over Current Relay
An over current relay is connected to the circuit breaker. In an over current situation, both the circuit breaker and the over current relay may trip. If the circuit breaker can not be reset, the reset button on the over current relay must be pressed. The over current relay is located in the control box.
Maximum Amps
The following table show the maximum amps the entire generator can provide. Do not exceed the maximum amps listed. (See Table 9 below.)
Table 9. Maximum Amps
Model: | DCA100SSJU | |
|
| |
Rated | Maximum Amps | |
Voltage | ||
| ||
|
| |
Single Phase | 222.2 amps (4 wire) | |
120 Volt | ||
| ||
|
| |
Single Phase | 111.1 amps (4 wire) | |
240 Volt | ||
| ||
|
| |
Three Phase | 241 amps | |
240 Volt | ||
| ||
|
| |
Three Phase | 120 amps | |
480 Volt | ||
| ||
|
|
Receptacle Use
When the UVWO terminals are providing power, the receptacle power available decrease. Do not exceed receptacle power available listed on Table 10.
Table 10. Receptacle Use
|
| Receptacle | |
Power in Use | Power | ||
|
| Available | |
|
|
| |
| 240/120V | Duplex | |
240/480V | Single Phase | ||
NEMA | |||
or Twist | |||
| Lock CS6369 | ||
|
| ||
|
|
| |
KVA | KW | KW | |
|
|
| |
100 | 57.7 | 0 | |
|
|
| |
95.8 | 56.5 | 1.2 | |
|
|
| |
91.7 | 55.3 | 2.4 | |
|
|
| |
87.5 | 54.1 | 3.6 | |
|
|
| |
83.4 | 52.9 | 4.8 | |
|
|
|