Table of Contents
DCA-100SSJU — OUTPUT TERMINAL PANEL OVERVIEW
Voltage Selector Switch- 3 Phase 240/139V Position The following are additional voltages available when the voltage selector switch is in the 3 phase 240/139V position. (See Figure 31 below.)
FIGURE 32. Voltage
Regulator Knob located
on the control panel
Single Phase: 240V, 220V, or 208 Volt
The following connection, with the voltage selector switch locked into the 3 phase 240/139V position (See Figure 31), can offer SINGLE PHASE power at 240V, 220V, or 208V.
After hooking up the hard wires to the lugs as shown in figure 34 below, 240V will be the voltage with the Voltage Regulator Knob turned toward maximum. 220 volt will be reached when the Voltage Regulator Knob is turned down, and 208 volt when the Voltage Regulator Knob is toward the lowest setting (See Figure 32).
FIGURE 31. Voltage Selector Switch 240/139V Three Phase | FIGURE 34. Hard Wire Hookup for Single Phase 240V, 220V, |
Position | or 208V |
3 Phase, 240V, 220V, or 208 Volt
The following connection, with the voltage selector switch locked into the 3 phase 240/139V position (See Figure 31), can offer THREE PHASE power at 270V, 220V, or 208V.
After hooking up the hard wires to the lugs as shown in figure 33 below, 240V will be the voltage with the Voltage Regulator Knob turned toward maximum. 220 volt will be reached when the Voltage Regulator Knob is turned down, and 208 volt when the Voltage Regulator Knob is toward the lowest setting (See Figure 32).
Single Phase: 139V, 127V, or 120V
The following connection, with the voltage selector switch locked into the 3 phase 240/139V position (See Figure 31), can offer SINGLE PHASE power at 139V, 127V, or 120V.
After hooking up the hard wires to the lugs as shown in figure 35 below, 139V will be the voltage with the Voltage Regulator Knob turned toward maximum. 127 volt will be reached when the Voltage Regulator Knob is turned down, and 120 volt when the Voltage Regulator Knob is toward the lowest setting (See Figure 32).
FIGURE 33. Hard Wire Hookup for Three Phase 240V, 220V, | FIGURE 35. Hard Wire Hookup for Single Phase 139V, 127V, | |
or 208V | ||
or 120V | ||
|
PAGE 40 —