Command Syntax

INITiate[:IMMediate]

 

 

INITiate:CONTinuous <bool>

Parameters

For INIT[:IMM]

(None)

 

For INIT:CONT

0 1 OFF ON

*RST Value

OFF

 

Examples

INIT INIT:CONT 1 INIT:CONT ON

Query Syntax

For INIT[:IMM]

(None)

 

For INIT:CONT

INITiate:CONTinuous?

Returned Parameters

0 1

 

Related Commands

ABOR CURR:TRIG

TRIG *TRG VOLT:TRIG

List Subsystem

This subsystem controls the generation of parameter lists that sequence the power module output through values of voltage and current. Two subsystem commands specify lists of output voltages (LIST:VOLT), and currents (LIST:CURR). A count command (LIST:COUN) determines how many times the power module sequences through a list before that list is completed. A dwell command (LIST:DWEL) specifies the time interval that each value (point) of a list is to remain in effect. A step command (LIST:STEP) determines if a trigger causes a list to advance only to its next point or to sequence through all of its points.

Each list can have from 1 to 20 points. Normally, voltage, current, and dwell lists must have the same number of points, or an error is generated when the first list point is triggered. The exception is a list consisting of only one point. Such a list is treated as if it had the same number of points as the other lists, with all the points having the same value as the one specified point.

Note

All list subsystem commands (as well as CURR:MODE LIST and VOLT:MODE LIST) are implied

 

ABORt commands.

 

 

LIST:COUN

This command sets the number of times that the list is executed before it is completed. The command accepts parameters in the range 1 through 9.9E37, but any number greater than 65534 is interpreted as INFinity. Use INF if you wish to execute a list indefinitely.

Command Syntax

[SOURce]:LIST:COUNt <NRf+>

Parameters

1 to 9.9E37 INFinity

*RST Value

1

 

Examples

LIST:COUN 3

LIST:COUN INF

Query Syntax

[SOURce]:LIST:COUNt?

Returned Parameters

<NR3>

 

Related Commands

CURR:MODE LIST:CURR LIST:DWEL LIST:STEP

 

LIST:VOLT

VOLT:MODE

LIST:CURR

This command specifies the output current points in a list. The current points are given in the command parameters, which are separated by commas. Up to 20 points may be entered and the output current values specified by the points will be generated in the same order as they were entered.

Command Syntax

[SOURce]:LIST:CURRent <NRf+> {,<NRf+>}

Parameters

See Table 3-2

Default Suffix

A

Examples

LIST:CURR 2.5,3.0,3.5 LIST:CURR MAX,2.5,MIN

Query Syntax

(None)

Related Commands

CURR:MODE LIST:CURR:POIN? LIST:DWEL

Language Dictionary 37