Electrical Requirements

For 24 kW Models:35 Pound Electric

 

Terminal Block

 

Recommended

 

Recommended

Serial Plate

Current

Breaker

Minimum

Connections

Fuse or Breaker

Voltage

(Amps)

Poles

Conductor Size

Required

Rating (Amps)

 

 

 

[AWG (mm2)]

208V/60Hz/1ph

L1, L2, Neutral,

122

175

2

2/0 (67.5)

and ground

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

240V/60Hz/1ph

L1, L2, Neutral,

107

150

2

1/0 (53.5)

and ground

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

200V/60Hz/1ph

L1, Neutral,

122

175

1

2/0 (67.5)

and ground

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

200V/50Hz/1ph

L1, Neutral,

119

150

1

1/0 (53.5)

and ground

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

230-240V/50Hz/

L1, Neutral,

108

150

1

1/0 (53.5)

1ph

and ground

 

 

 

 

 

 

 

 

 

 

200-208V/60Hz/

L1, L2, L3,

71

90*

3

3 (26.7)

3ph

and ground

 

 

 

 

 

 

 

 

 

 

200V/50Hz/3ph

L1, L2, L3,

65

90*

3

3 (26.7)

and ground

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

230-240V/50Hz/

L1, L2, L3,

62

80*

3

4 (21.2)

3ph

and ground

 

 

 

 

 

 

 

 

 

 

240V/60Hz/3ph

L1, L2, L3,

62

80*

3

4 (21.2)

and ground

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

380V/50Hz/3ph

L1, L2, L3,

38

50*

3

6 (13.3)

and ground

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

400-415V/50Hz/

L1, L2, L3,

35

45*

3

8 (8.37)

3ph

and ground

 

 

 

 

 

 

 

 

 

 

460-480V/60Hz/

L1, L2, L3,

31

40*

3

8 (8.37)

3ph

and ground

 

 

 

 

 

 

 

 

 

 

*3 Phase machines should not have fuses, breakers only.

Table 13

56