gas connections
This gas appliance has been set to operate with either natural gas or propane as indicated on the identification name plate. Make certain the gas supply matches the nameplate information. Should conversion to the opposite fuel be desired, conversion parts must be ordered from the factory. Conversion must be completed by a qualified service person only. Always remember to reflect the conversion on the nameplate.
c a U t I o n
RESIDENTIAl GAS CONNECTIONSANDDanGer
CONNECTING TO THE WRONG GAS
SUPPLY COULD RESULT IN FIRE OR
AN EXPLOSION CAUSING SEVERE
INJURY AND PROPERTY DAMAGE.
gas specifications
| NATURAL GAS | PROPANE GAS |
195,000 Btu/hr. | 195,000 Btu/hr. |
INSTALLATION REQUIREMENTS
GAS CONNECTION: 3/4" NPT
CHECK PLUMBING CODES FOR PROPER SUPPLY LINE SIZING TO ATTAIN MINIMUM BURNER MANIFOLD PRESSURE SHOWN:
NATURAL GAS: 5" W.C.PROPANE GAS: 10" W.C.
MAXIMUM INLET PRESSURE: 14" W.C.
NOTE: If a flexible gas line is used, it must be AGA approved, commercial type and at least 3/4" I.D.
HOOD INSTALLATION IS REQUIRED
GAS VALVE MAY REQUIRE FIELD ADJUSTMENT
ABOVE 3,250' (991m)
AND IS NOT ADJUSTED AT THE FACTORY.
I n s t a l l a tio n
W a r n I n G
TO AVOID SERIOUS PERSONAL INJURY, installation of this appliance must conform to local, state, and national codes; the current edition of the American National Standard Z223.1, National Fuel Gas Code, and all local municipal building codes.
In Canada, installation must be in accordance with Standard CAN/CSA B 149.1 and Installation Codes - Gas Burning Appliances, and local codes.
GAS PRESSURE CHART
The appliance has been factory adjusted according to the
gas type specified on the identification name plate.
TECHNICAL SPECIFICATIONS
Natural GasMin. Connected | 7.0" W.C. | 1.12 kPa | |
Pressure | |||
|
| ||
|
|
| |
Max. Connected | 14.0" W.C. | 3.5 kPa | |
Pressure | |||
|
| ||
|
|
| |
| Propane Gas |
| |
Min. Connected | 11.0" W.C. | 1.99 kPa | |
Pressure | |||
|
| ||
|
|
| |
Max. Connected | 14.0" W.C. | 3.5 kPa | |
Pressure | |||
|
| ||
|
|
|