Configuring Share-UPScontinued

Testing

To test the operation of Share-UPS, perform the following

Share-UPS

steps in the order given. If Share-UPS fails this test, see

 

“Troubleshooting: Table 12” on page 48.

1 Confirm that the UPS in on and that the battery is fully charged.

2 Verify that Share-UPS has been installed, con- nected, and configured.

3 Start the power management software on the serv- ers, with power management screens visible, if applicable.

4 Confirm that the Power and Status LEDs on Share-UPS are on, indicating normal operation.

5 Simulate a utility power failure.

6 Confirm that the On Batt LED of Share-UPS is on, indicating that Share-UPS is sending an On Bat- tery signal to the connected servers or devices. See “LEDs: Table 2” on page 8.

7 Confirm that all connected servers and devices have received the On Battery message from Share- UPS.

8 Restore utility power.

9 Confirm that all connected servers and devices have received the message that utility power has been restored.

Note: To check the shutdown mode of your config- uration, keep the utility power off long enough to allow all connected servers and devices to shut down. After all connected servers and devices have shut down, restore power and verify that they all restart.

28

Page 34
Image 34
American Power Conversion AP9207 manual Steps in the order given. If Share-UPS fails this test, see, Troubleshooting on