Paging Setup Menu

Paging and

When used in conjunction with a modem connected to the

Share-UPS

Management port (see “Connecting to the Management port

 

(via modem),” on page 31), Share-UPS can be set up to dial

 

a pager to report UPS problem events, such as on-battery

 

operation or problems with the UPS. To use paging, access

 

the Paging Setup menu by typing p from the Main menu,

 

and change the settings to work with your modem and

 

pager.

 

 

 

Format of

When paging is enabled and a UPS problem event occurs,

reported events

Share-UPS reports the condition by sending a code that

 

appears on the pager’s display:

 

[Site ID][space][event code]

 

For example, a pager displaying:

 

12345678

1

Share-UPS modem command string: Figure 9

tells you that the UPS whose Site ID you have assigned as “12345678” is reporting the event whose code you have chosen to be represented by “1.”

When a reportable event occurs, Share-UPS issues a modem command string like the one in the following figure.

Dial String

Pager Display

A T D T 9 , 1 8 0 0 5 5 5 1 2 1 2 @ 1 2 3 4 5 6 7 8 * 1 ;

Attention

Command

Issued by

Share-UPS

Phone Number

Modem

Commands

Dial Type

Command

Site ID

Space Character

Event Code

Return to Command Mode

Issued by Share-UPS

To be set using the Paging Setup menu.

Continued on next page