Configuring Share-UPS

Shutdown

To configure Share-UPS, you must choose one of the three

modes

available modes of automatic shutdown of the UPS. Each

 

shutdown mode is described in this section.

 

Confirmed

 

Until Low Battery

 

Timer

 

 

 

DIP switches: Select the shutdown mode by using the DIP switches as

Table 5described in the following table. (An abbreviated form of this table also appears on the top panel of Share-UPS.)

 

 

Switch Setting (=0, =1)

Shutdown Mode

 

 

 

 

4

3

2

1

 

 

 

 

 

 

 

Confirmed

0

0

0

*

 

 

 

 

 

Until Low Battery

0

0

1

N/A

 

 

 

 

 

 

 

2 min.

0

1

0

N/A

 

 

 

 

 

 

 

5 min.

0

1

1

N/A

 

 

 

 

 

 

Timer

10 min.

1

0

0

N/A

 

 

 

 

 

15 min.

1

0

1

N/A

 

 

 

 

 

 

 

 

30 min.

1

1

0

N/A

 

 

 

 

 

 

 

Soft Timer

1

1

1

N/A

 

 

 

 

 

 

 

Await

0

0

0

0

* Server on

Confirmation

 

 

 

 

 

 

 

 

 

Advanced Port

Treat as

0

0

0

1

 

 

Confirmed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 