American Power Conversion MX28B4800 manual Parameter Locations, Descriptions, and Default Values

Models: MX28B2400 MX28B4800

1 70
Download 70 pages 19.33 Kb
Page 42
Image 42

1.Use the right or left arrow keys to position the cycling cursor below “SYSTEM”.

2.Press the down arrow key once.

3.Use the right arrow key to position the cycling cursor below “IN-RLY”.

4.Press the down arrow key once; the cursor will be cycling below “RLY-MAP”.

5.Press the down arrow key (repeatedly if necessary) until the desired parameter screen is displayed (there are eight parameter screens in this category).

After making any desired changes, return to the main menu press the up arrow key repeatedly. If a parameter requires a level 1 or level 2 security access to permit changes to it, the security level will be found in braces, i.e. Security Level {2}, in the “PARAMETER” column of the table.

Parameter Locations, Descriptions, and Default Values

PARAMETER NAME/

DESCRIPTION

DISPLAY SCREENS /

[MENU LOCATION]

 

DEFAULT SETTINGS

 

 

 

Address 1

Power plant address or identification - first line.

Address 1

m+

Security Level {1}

 

APC DCNS, Inc.

 

[SYSTEM/SETUP]

 

 

 

Address 2

Power plant address or identification - second line.

Address 2

m+

Security Level {1}

 

11035 Switzer

Av

[SYSTEM/SETUP]

 

 

 

Address 3

Power plant address or identification - third line.

Address 3

m+

Security Level {1}

 

Dallas, TX.

 

[SYSTEM/SETUP]

 

 

 

Alarms Item 1

Display of up to 16 active alarms (a typical alarm

Alarm Item 1

+

{Status Only}

screen is shown).

Batt LV Alm Onm

[ALARMS]

 

 

 

 

 

 

 

Alarms Item 16

Display of up to 16 active alarms (a typical alarm

Alarm Item 16

+

[ALARMS]

screen is shown).

No Alarms

 

Battery Current

Battery current measured by the system controller

Batt Current

+

{Status Only}

at the battery current shunt.

-15.0 A

[STATUS]

 

 

 

Battery Discharge Alarm

The output relay energized if the battery discharge

Batt Disc Alm m+

Security Level {1}

current exceeds the programmed battery

Minor

 

[BATT/SET-ALM]

discharge threshold.

 

 

Battery Discharge Threshold

An alarm is generated if the battery discharge

Batt Disc Thr m+

Security Level {1}

current exceeds this value.

10 A

[BATT/SET-ALM]

 

 

 

Battery Float Voltage

One of three parameters that control the DC

Batt Float

m+

Security Level {1}

output voltage. Set the Float Voltage at 25°C

-54.00 V

[BATT/PARAM]

battery temperature per the battery manufacturers

 

 

 

recommendations.

 

 

MX28B1200/2400 MX28B1200/4800 –48 VDC User’s Manual

Page 37

Page 42
Image 42
American Power Conversion MX28B4800 Parameter Locations, Descriptions, and Default Values, Parameter Name, Display Screens