Float / Boost/Equalize | Used to Control voltage on systems without a PSCU |
Switch |
|
|
|
Float Trim Pot | The float pot is used to adjust the default float voltage (54.5 VDC). |
|
|
Boost/Equalize Trim | The boost/equalize pot is used to adjust the default boost equalize |
Pot | voltage (57.5 VDC). |
|
|
Power Shelf Control Unit
Major (Red) | On when Major Relay is |
|
|
Minor (Yellow) | On when Minor Relay is energized |
|
|
Normal (Green) | On when no alarms are active |
|
|
ALM 1 (Red) | On when Output Relay 1 is energized |
|
|
ALM 2 (Red) | On when Output Relay 2 is energized |
|
|
ALM 3 (Red) | On when Output Relay 3 is energized |
|
|
ALM 4 (Red) | On when Output Relay 4 is energized |
|
|
ALM 5 (Red) | On when Output Relay 5 is energized |
|
|
ALM 6 (Red) | On when Output Relay 6 is energized |
|
|
MIN (Red) | On when Minor Relay is energized |
|
|
MAJ (Red) | On when Major Relay is |
|
|