PARAMETER NAME/

DESCRIPTION

DISPLAY SCREENS /

[MENU LOCATION]

 

DEFAULT SETTINGS

 

 

 

Battery High Temperature

The output relay energized if the battery

Batt HT Alm

m+

Alarm

temperature exceeds the Battery High

Minor

 

Security Level {1}

Temperature threshold.

 

 

[BATT/SET-ALM]

 

 

 

Battery High Temperature

Battery Temperature is temperature measured at

Batt HT Thr

m+

Threshold

the battery probe. An alarm is generated if the

70.0 C

Security Level {1}

battery temperature exceeds this value.

 

 

[BATT/SET-ALM]

 

 

 

Battery High Voltage Alarm

The output relay energized if the DC output

Batt HV Alm

m+

Security Level {1}

voltage rises above the battery high voltage

Minor

 

[BATT/SET-ALM]

threshold.

 

 

Battery High Voltage Threshold

An alarm will be reported if temperature is lower

Batt HV Thr

m+

Security Level {1}

than the temperature entered.

-58.00

V

[BATT/SET-ALM]

An alarm is generated if the DC output voltage

 

 

 

rises above this value.

 

 

Battery Low Temperature

The output relay energized if the Battery

Batt LT Alm

m+

Alarm

Temperature drops below the battery Low

Minor

 

Security Level {1}

Temperature threshold.

 

 

[BATT/SET-ALM]

 

 

 

Battery Low Temperature

Battery Temperature is temperature measured at

Batt LT Thr

m+

Threshold Security Level {1}

the battery probe. An alarm is generated if the

0.0 C

[BATT/SET-ALM]

battery temperature drops below this value.

 

 

Battery Low Voltage Alarm

The output relay energized if the DC output

Batt LV Alm

m+

Security Level {1}

voltage drops below the battery low voltage

Minor

 

[BATT/SET-ALM]

threshold.

 

 

Battery Low Voltage Threshold

An alarm is generated if the DC output voltage

Batt LV Thr

m+

Security Level {1}

drops below this value.

-44.00 V

[BATT/SET-ALM]

 

 

 

Battery Maximum Recharge

One of three parameters that control the DC

Batt Max Rechm+

Current

output voltage. If Battery Current surpasses the

50 A

Security Level {1}

Maximum Battery Recharge Current, the DC

 

 

[BATT/PARAM]

output voltage will be reduced (the system limits

 

 

 

the charging current to this programmable value).

 

 

Battery Temperature

Battery temperature measured by the system

Batt Temp

+

{Status Only}

controller at the optional battery temperature

25.2 C

[STATUS]

sensor probe.

 

 

Circuit Breaker 1 Alias

An alternate name (alias) that can be assigned to

Cir Bkr 1

m+

Security Level {1}

a circuit breaker if desired.

-48V

[MODULES/CIRBKR/ALIAS]

 

 

 

 

 

 

 

Circuit Breaker 24 Alias

An alternate name (alias) that can be assigned to

 

Security Level {1}

a circuit breaker if desired.

Cir Bkr 72

m+

[MODULES/CIRBKR/ALIAS]

 

-48V

 

 

MX28B1200/2400 MX28B1200/4800 –48 VDC User’s Manual

Page 38

Page 43
Image 43
American Power Conversion MX28B2400 Batt HT Alm, Batt HT Thr, 70.0 C, Batt HV Alm, Batt HV Thr, 58.00, Batt LT Alm, 44.00