PARAMETER NAME/

DESCRIPTION

DISPLAY SCREENS /

[MENU LOCATION]

 

DEFAULT SETTINGS

 

 

 

Circuit Breaker 1 Tripped

An alarm that indicates Circuit Breaker 1 is

Cir Bkr 1 Alm m+

Security Level {1}

tripped.

Major

[MODULES/CIRBKR/SET-

 

 

 

ALM]

 

 

 

 

 

 

Circuit Breaker 24 Tripped

An alarm that indicates Circuit Breaker 24 is

 

Security Level {1}

tripped.

Cir Bkr 72 Almm+

[MODULES/CIRBKR/SET-

 

 

Major

ALM]

 

 

 

 

Compensation High Knee

The temperature compensation high knee is the

Comp Hknee

m+

Security Level {1}

point above which there is no additional battery

40.0 C

[BATT/COMP]

voltage compensation for further increases in

 

 

 

temperature.

 

 

Compensation Low Knee

The temperature compensation low knee is the

Comp Lknee

m+

Security Level {1}

point below which there is no additional battery

0.0 C

[BATT/COMP]

voltage compensation for further decreases in

 

 

 

temperature.

 

 

Compensation Method

One of three parameters that control the DC

Comp Method m+

Security Level {1}

output voltage. Activate “ON” or de-activate “OFF”

OFF

[BATT/COMP]

battery temperature compensation.

 

 

Compensation Temperature

Temperature compensation coefficient between

Comp TC

m+

Coefficient

low knee and high knee in mV/cell/°C.

- 3.00mV

Security Level {1}

(Compensation equals zero at 25°C.)

 

 

[BATT/COMP]

 

 

 

Control Unit Revision

Hardware revision level of the control unit. This

Cntrl Rev

+

{Status Only}

parameter cannot be changed.

000002

[SYSTEM/SETUP]

 

 

 

Date

Internal system calendar date. Used as a date

Date

m+

Security Level {1}

stamp in the event log.

DEC 16 1999

[SYSTEM/DATE]

 

 

 

Display Type

Type number for the control unit display. This

Display Type

+

{Status Only}

parameter cannot be changed.

000255

[SYSTEM/SETUP]

 

 

 

Fahrenheit Scale

Enables selection of Fahrenheit or Celsius

Fahrenheit

m+

Security Level {1}

temperature scale (Fahrenheit “OFF” displays

OFF

[SYSTEM/SETUP]

readings in °C).

 

 

Firmware Version

Version number of the control unit firmware.

FW Version

+

{Status Only}

NOTE: Actual firmware version number

000189

[SYSTEM/SETUP]

displayed is the current version as of the date

 

 

 

of manufacture. This parameter cannot be

 

 

 

changed.

 

 

FUSE 1 Alias

An alternate name (alias) that can be assigned to

Fuse 1

m+

Security Level {1}

a FUSE Fuse 1 if desired.

-48V

 

[MODULES/FUSE/ALIAS]

 

 

 

 

 

 

 

FUSE 8 Alias

An alternate name (alias) that can be assigned to

FUSE 16

m+

Security Level {1}

a FUSE Fuse 8 if desired.

-48V

 

[MODULES/FUSE/ALIAS]

 

 

 

MX28B1200/2400 MX28B1200/4800 –48 VDC User’s Manual

Page 39

Page 44
Image 44