PARAMETER NAME/

DESCRIPTION

DISPLAY SCREENS /

[MENU LOCATION]

 

DEFAULT SETTINGS

 

 

 

FUSE 1 Blown

The Output Relay that is energized when FUSE

FUSE 1 Alm

m+

Security Level {1}

Fuse 1 is blown.

Major

[MODULES/FUSE/SET-ALM]

 

 

 

 

 

 

 

FUSE 8 Blown

The Output Relay that is energized when FUSE

FUSE 16 Alm

m+

Security Level {1}

Fuse 8 is blown.

Major

[MODULES/FUSE/SET-ALM]

 

 

 

Hardware Battery Current

The output relay energized if there is a hardware

Hw Batt C Almm+

Alarm

failure in the battery current monitoring function.

Minor

Security Level {2}

 

 

 

[SYSTEM/SET-ALM]

 

 

 

Hardware Battery Temperature

The output relay energized if there is a hardware

Hw Batt T Almm+

Alarm

failure in the battery temperature monitoring

Minor

Security Level {2}

function.

 

 

[SYSTEM/SET-ALM]

 

 

 

Hardware LVD Alarm

The output relay energized if there is a conflict

Hw LVD Alm

m+

Security Level {2}

between the commanded and sensed positions of

Minor

[SYSTEM/SET-ALM]

the LVD contactor. Generally the contactor is

 

 

 

open when it should be closed.

 

 

Hardware System Temperature

The output relay energized if there is a hardware

Hw Sys T Alm m+

Alarm

failure in the system temperature monitoring

Minor

Security Level {2}

function.

 

 

[SYSTEM/SET-ALM]

 

 

 

Hardware System Voltage

The output relay energized if there is a hardware

Hw Sys V Alm m+

Alarm

failure in the system voltage monitoring function.

Minor

Security Level {2}

 

 

 

[SYSTEM/SET-ALM]

 

 

 

Input Relay 1

The Output Relay that is energized when an

In-Rly 1 Alm

m+

Security Level {1}

external contact closure or opening at the Input

Ignore

[SYSTEM/IN-RLY/RLY-MAP]

Relay 1 connection changes state.

 

 

 

 

 

 

Input Relay 4

The Output Relay that is energized when an

 

Security Level {1}

external contact closure or opening at the Input

In-Rly 4 Alm

m+

[SYSTEM/IN-RLY/RLY-MAP]

Relay 4 connection changes state.

Ignore

 

 

Input Relay 1 Alias

An alternate name (alias) can be assigned to Input

In-Rly 1

m+

Security Level {1}

Relay 1 if desired.

Input Relay 1

[SYSTEM/IN-RLY/ALIAS]

 

 

 

 

 

 

 

Input Relay 4 Alias

An alternate name (alias) can be assigned to Input

 

Security Level {1}

Relay 1 if desired

In-Rly 4

m+

[SYSTEM/IN-RLY/ALIAS]

 

Input Relay

4

 

 

Lamp Test

Setting Lamp Test to “ON” will turn on the

Lamp Test

m+

Security Level {1}

“MAJOR”, “MINOR”, “NORMAL”, “MAJ”, and

OFF

[SYSTEM/DIAG]

“MIN” LEDs on the control unit front panel.

 

 

MX28B1200/2400 MX28B1200/4800 –48 VDC User’s Manual