PARAMETER NAME/

DESCRIPTION

DISPLAY SCREENS /

[MENU LOCATION]

 

DEFAULT SETTINGS

 

 

 

Rectifier Description

Displays the model number of the installed

Rect 1 Desc

#

{Status Only}

rectifier. NOTE: This information can be

MRF28H54

[MODULES/RECT/INFO]

viewed for each rectifier installed by using the

 

 

 

horizontal arrow keys.

 

 

Rectifier Fail 1-of-N Alarm

The output relay energized if Rectifier Fail 1-of-N

Rect 1ofN Almm+

Security Level {1}

alarm occurs. This is a special rectifier alarm

Minor

 

[SYSTEM/SET-ALM]

group that signifies that one rectifier has at least

 

 

 

one alarm condition.

 

 

Rectifier Fail 2-of-N Alarm

The output relay energized if Rectifier Fail 2-of-N

Rect 2ofN Almm+

Security Level {1}

alarm occurs This is a special rectifier alarm group

Major

 

[SYSTEM/SET-ALM]

that signifies that more than one rectifier has at

 

 

 

least one alarm condition.

 

 

Rectifier Fail Safe Voltage

Rectifier default output voltage if communication

Rect Fail Safem+

Security Level {1}

with the control unit fails.

-54.00 V

[MODULES/RECT/PARAM]

 

 

 

Rectifier Fan Fail Alarm

The output relay that is energized or special

Rect FF Alm

m+

Security Level {1}

rectifier alarm group n of N that occurs when a

n of N

 

[MODULES/RECT/SET-ALM]

rectifier fan has failed.

 

 

Rectifier Fan Fail Alarm Status

The status will be “ON” if the rectifier fan has

Rect 1 FF

#

{Status Only}

failed. NOTE: This information can be viewed

OFF

 

[MODULES/RECT/INFO]

for each rectifier installed by using the

 

 

 

horizontal arrow keys.

 

 

Rectifier Fault Alarm (RFA)

The status will be on if the rectifier output has

Rect 1 RFA

#

Status

failed. NOTE: This information can be viewed

OFF

 

{Status Only}

for each rectifier installed by using the

 

 

[MODULES/RECT/INFO]

horizontal arrow keys.

 

 

Rectifier RFA Alarm

The output relay that is energized or special

Rect RFA Alm

m+

Security Level {1}

rectifier alarm group n of N that occurs when a

n of N

 

[MODULES/RECT/SET-ALM]

rectifier output has failed.

 

 

Rectifier Standby Alarm

The output relay that is energized or special

Rect Stdby Almm+

Security Level {1}

rectifier alarm group n of N that occurs when the

n of N

 

[MODULES/RECT/SET-ALM]

control unit is holding a rectifier in the standby

 

 

 

mode.

 

 

Rectifier Standby Alarm Status

The status will be “ON” if the control unit is holding

Rect 1 Stdby

#

{Status Only}

the rectifier in the standby mode. NOTE: This

OFF

 

[MODULES/RECT/INFO]

information can be viewed for each rectifier

 

 

 

installed by using the horizontal arrow keys.

 

 

Store Configuration

Setting this parameter to “Enable” will cause the

Store Cfg

m+

Security Level {1}

current rectifier configuration to be stored (the

Disable

 

[SYSTEM/DIAG]

display toggles back to “Disable” after entry).

 

 

System Current

The total system output current (calculated as the

Sys Current

+

{Status Only}

sum of the individual rectifier output currents).

145.8

A

[STATUS]

 

 

 

System High Temperature

The output relay energized if the System

Sys HT Alm

m+

Alarm

Temperature exceeds the system high

Minor

 

Security Level {1}

temperature threshold.

 

 

[SYSTEM/SET-ALM]

 

 

 

System High Temperature

System Temperature is ambient temperature

Sys HT Thr

m+

Threshold

measured inside the controller. An alarm will be

70.0

C

Security Level {1}

reported if temperature is higher than the

 

 

[SYSTEM/SET-ALM]

temperature entered.

 

 