4.3.Final Inspection:
1.Verify that the interior and exterior of the system is clean and free from debris.
2.Ensure all wires connected and bolts are properly tightened.
3.Ensure the following the User, Service, and Calibration parameters are set properly on the controller (default settings are in parenthesis):
LVD (Param)
LVD1 Trip
Batt
Batt Disc Thr (10 A) Batt (Param)
Batt Float
Batt (Comp)
Comp Method (OFF)
4.Verify on the status menu that the system is functioning correctly with no alarms.
5.Be sure to leave the site as orderly and neat as possible.
MX28B1200/2400 MX28B1200/4800 | Page 31 |