PARAMETER NAME/

DESCRIPTION

DISPLAY SCREENS /

[MENU LOCATION]

 

DEFAULT SETTINGS

 

 

 

System High Voltage alarm

The output relay energized if the System Voltage

Sys HV Alm

m+

Security Level {1}

is above the System High Voltage threshold.

Minor

 

[SYSTEM/SET-ALM]

 

 

 

System High Voltage

System Voltage is bus voltage measured by the

Sys HV Thr

m+

Threshold

controller. An alarm will be reported if voltage is

-58.00 V

Security Level {1}

higher than the voltage entered.

 

 

[SYSTEM/SET-ALM]

 

 

 

System Low Temperature

The output relay energized if the System

Sys LT Alm

m+

Alarm

Temperature is below the System Low

Minor

 

Security Level {1}

Temperature threshold.

 

 

[SYSTEM/SET-ALM]

 

 

 

System Low Temperature

System Temperature is ambient temperature

Sys LT Thr

m+

Threshold

measured inside the controller. An alarm will be

0.0 C

Security Level {1}

reported if temperature is lower than the

 

 

[SYSTEM/SET-ALM]

temperature entered.

 

 

System Low Voltage Alarm

The output relay energized if the System Voltage

Sys LV Alm

m+

Security Level {1}

is below the System Low Voltage threshold.

Minor

 

[SYSTEM/SET-ALM]

 

 

 

System Low Voltage Threshold

System Voltage is bus voltage measured by the

Sys LV Thr

m+

Security Level {1}

controller. An alarm will be reported if voltage is

-50.00 V

[SYSTEM/SET-ALM]

lower than the voltage entered.

 

 

System Temperature

System temperature measured within the control

Sys Temp

+

{Status Only}

unit.

26.7 C

[STATUS]

 

 

 

System Voltage

System output voltage measured between the

Sys Voltage

+

{Status Only}

MX28B DC power plant -48V and return buses.

-54.00 V

[STATUS]

 

 

 

Test Major Relay

Setting this parameter to “ON” de-energizes the

Test Maj Rly

m+

Security Level {1}

Major Relay and turns on the “MAJ” LED on the

OFF

 

[SYSTEM/DIAG]

control unit front panel. In normal operation Major

 

 

 

Relay is energized so that when a loss of –48

 

 

 

VDC power occurs, the relay will change state.

 

 

Test Minor Relay

Setting this parameter to “ON” energizes the Minor

Test Min Rly

m+

Security Level {1}

Relay and turns on the “MIN” LED on the control

OFF

 

[SYSTEM/DIAG]

unit front panel.

 

 

Test Relay 1

Setting this parameter to “ON” energizes Relay 1

Test Relay 1

m+

Security Level {1}

and turns on the “ALM1” LED on the control unit

OFF

 

[SYSTEM/DIAG]

front panel.

 

 

 

 

 

 

Test Relay 6

Setting this parameter to “ON” energizes Relay 6

Test Relay 6

m+

Security Level {1}

and turns on the “ALM6” LED on the control unit

OFF

 

[SYSTEM/DIAG]

front panel.

 

 

 

 

 

Test Relay Enable

This parameter must be set to “Enable” to permit

Test Relay En m+

Security Level {1}

the eight output relays to be manually tested;

Disable

 

[SYSTEM/DIAG]

otherwise, the state of the relays will be per

 

 

 

system conditions.

 

 

MX28B1200/2400 MX28B1200/4800 –48 VDC User’s Manual

Page 44

Page 49
Image 49
American Power Conversion MX28B2400 Sys HV Alm, Sys HV Thr, Sys LT Alm, Sys LT Thr, Sys LV Alm, Sys LV Thr, 50.00, 26.7 C