American Power Conversion MX28B2400 MX28B1200/2400 MX28B1200/4800 -48 VDC User’s Manual, Page

Models: MX28B2400 MX28B4800

1 70
Download 70 pages 19.33 Kb
Page 47
Image 47

PARAMETER NAME/

DESCRIPTION

DISPLAY SCREENS /

[MENU LOCATION]

 

DEFAULT SETTINGS

 

 

 

Output Relay 1 Delay

Delay between sensing of the alarm condition and

Out-Rly 1 Dly m+

Security Level {1}

activation of Output Relay 1. An alarm condition

0 sec

[SYSTEM/OUT-RLY/RLY-

must exist for longer than the delay to be

 

 

MAP]

activated.

 

 

 

 

 

Output Relay 6 Delay

Delay between sensing of the alarm condition and

Out-Rly 6 Dly m+

Security Level {1}

activation of Output Relay 6. An alarm condition

0 sec

[SYSTEM/OUT-RLY/RLY-

must exist for longer than the delay to be

 

 

MAP]

activated.

 

 

Output Relay Major Alias

An alternate name (alias) can be assigned to the

Relay Major

m+

Security Level {1}

major Relay if desired.

Major

 

[SYSTEM/OUT-RLY/ALIAS]

 

 

 

Output Relay Minor Alias

An alternate name (alias) can be assigned to the

Relay Minor

m+

Security Level {1}

Minor Relay if desired.

Minor

 

[SYSTEM/OUT-RLY/ALIAS]

 

 

 

PIN 1 change

Permanently change password (PIN) that permits

PIN

m+

Security Level {2}

security Level 1 parameter changes - limited

1111

[SYSTEM/SETUP]

access.

 

 

PIN 2 Change

Permanently change password (PIN) that permits

PIN 2

m+

Security Level {2}

security Level 2 parameter changes - unlimited

2222

[SYSTEM/SETUP]

access.

 

 

PIN Entry

Screen for entry of the active password (PIN).

PIN

m+

Security Level {0}

Before any changes can be made, the correct pin

0000

[PIN]

for the desires security level must be entered.

 

 

 

Level 0 – full read access. Level 1 –full read and

 

 

 

limited write access. Level 2 – full read and write

 

 

 

access.

 

 

Rectifier Communications Fail

The maximum rectifier communications response

RectFailComm

m+

Timeout

time allowed before a communications failure is

1 min

Security Level {1}

declared.

 

 

[MODULES/RECT/PARAM]

 

 

 

Rectifier Configuration Alarm

The output relay energized if the rectifier

Rect Cfg Alm

m+

Security Level {1}

configuration differs from its stored configuration.

Minor

 

[SYSTEM/SET-ALM]

This occurs if a rectifier is added after

 

 

 

configuration.

 

 

Rectifier Current Limit Alarm

The output relay that is energized or special

Rect CL Alm

m+

Security Level {1}

rectifier alarm group n of N that occurs when a

n of N

 

[MODULES/RECT/SET-ALM]

rectifier has been forced into the current limited

 

 

 

mode.

 

 

Rectifier Current Limit Alarm

The status will be “ON” if the rectifier has been

Rect 1 CL

#

Status

forced into its current limited mode. NOTE: This

OFF

 

{Status Only}

information can be viewed for each rectifier

 

 

[MODULES/RECT/INFO]

installed by using the horizontal arrow keys.

 

 

Rectifier Current Output Status

A display of the DC output current for the

Rect 1 Curr

#

{Status Only}

individual rectifier. NOTE: This information can

24.9 A

[MODULES/RECT/INFO]

be viewed for each rectifier installed by using

 

 

 

the horizontal arrow keys.

 

 

MX28B1200/2400 MX28B1200/4800 –48 VDC User’s Manual

Page 42

Page 47
Image 47
American Power Conversion MX28B2400, MX28B4800 manual MX28B1200/2400 MX28B1200/4800 -48 VDC User’s Manual, Page